| 2020-03-17 13:00:14 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #20020654 |
| | 3/17/20 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED |
| | |
| | 1) THE PLANS SHOW MULTIPLE MODEL TOWNHOUSES. PLEASE |
| | PROVIDE A MASTER LIST THAT LINKS TOWN HOUSE MODELS WITH |
| | ADDRESSES- SECTION 107.2.1 WPB. IT WOULD ALSO BE |
| | HELPFUL TO A SITE PLAN OF THE TOWNHOUSE DEVELOPMENT |
| | THAT IDENTIFIES EACH BUILDING LOCATION, THE STREETS AND |
| | THE ADDRESSES OF THE TOWNHOUSES- SEE ZONING REVIEW. |
| | |
| | 2) IN ORDER TO REVIEW THE ENERGY AND AC CALCULATIONS, |
| | PLEASE PROVIDE DOOR AND WINDOW SCHEDULES ON THE PLAN- |
| | SECTIONS R402 & R403.7.1 FBC EC. |
| | |
| | 3) SHEET M1, NAVARRE MODEL: |
| | A) IT APPEARS THAT FLEX DUCTS WILL BE INSTALLED IN THE |
| | GARAGE. PLEASE PLACE A NOTE TO VERIFY THE DUCTS WILL BE |
| | INSTALLED ABOVE THE REQUIRED DRYWALL CEILING- SECTION |
| | R302.5.2 FBC RES |
| | B) PROVIDE A RETURN FROM THE MASTER BEDROOM WALK-IN |
| | CLOSET- SECTION M1602.2(3) FBC RES. |
| | C) THE MAIN RETURN TO THE AC CLOSET IS SLIGHTLY |
| | UNDERSIZED- 50 SQ. INCHES PER 100 CFMS REQUIRED. A |
| | 24X24 GRILL WILL BE ADEQUATE. |
| | D) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE CLOTHES |
| | DRYER AND RANGE HOOD- SECTIONS M1502.4.5.2 AND M1503.1 |
| | FBC RES. PLEASE NOTE THAT A LOUVERED DOOR OR GRILL TO |
| | PROVIDE MAKEUP AIR MAY BE REQUIRED FOR THE CLOTHES |
| | DRYER- SECTION 1307.1 FBC RES. |
| | |
| | 4) SHEET M2, GRAYTON MODEL: |
| | A) PROVIDE A RETURN FROM THE MASTER BEDROOM WALK-IN |
| | CLOSET- SECTION M1602.2(3) FBC RES. |
| | B) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE CLOTHES |
| | DRYER AND RANGE HOOD- SECTIONS M1502.4.5.2 AND M1503.1 |
| | FBC RES. PLEASE NOTE THAT A LOUVERED DOOR OR GRILL TO |
| | PROVIDE MAKEUP AIR MAY BE REQUIRED FOR THE CLOTHES |
| | DRYER- SECTION 1307.1 FBC RES. |
| | |
| | 5) THE ENERGYGAUGE PERFORMANCE COMPLIANCE FORM |
| | R405-2017 SHALL BE ELECTRONICALLY SIGNED AND SEALED BY |
| | THE ENGINEER WHO PREPARED THE DOCUMENT. PLEASE NOTE |
| | THAT A BLOWER DOOR TEST WILL BE REQUIRED AND THE TEST |
| | FORM (ATTACHED WITH THE REPORT) SHALL BE FILLED OUT AND |
| | SUBMITTED FOR FINAL CO. |
| | |
| | 6) THE ELITE HVAC COOLING AND HEATING CALCULATIONS |
| | ATTACHED WITH THE ENERGY FORMS ARE NOT INDICATED TO BE |
| | "WORST CASE" AND THERE IS NO SECTION IN THE FBC EC THAT |
| | ALLOWS FOR A WORST CASE HEAT LOAD CALCULATION. |
| | CALCULATIONS SHALL BE SUBMITTED FOR EACH PERMITTED |
| | TOWNHOUSE. PLEASE NOTE THAT THE REVISED CALCULATIONS |
| | SHALL BEAR THE TOWNHOUSE MODEL NAME AND ADDRESS- |
| | SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |