Plan Review Details - Permit 20020614
Plan Review Stops For Permit 20020614
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-03-18 Cont ID  
Sent By tklarge Date 2020-03-18 Time 03:21 Rev Time 0.00
Received By tklarge Date 2020-03-16 Time 11:40 Sent To  
Notes
2020-03-17 11:40:48RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-03-04 Cont ID  
Sent By tklarge Date 2020-03-04 Time 13:57 Rev Time 0.00
Received By tklarge Date 2020-03-02 Time 14:18 Sent To  
Notes
2020-03-03 14:18:47RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-02-24 Cont ID  
Sent By tklarge Date 2020-02-24 Time 09:15 Rev Time 0.00
Received By tklarge Date 2020-02-14 Time 13:13 Sent To  
Notes
2020-02-18 13:13:35ROUTED TO PLUMBING INBOX

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-03-18 Cont ID  
Sent By tklarge Date 2020-03-18 Time 03:20 Rev Time 0.00
Received By tklarge Date 2020-03-18 Time 02:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-03-04 Cont ID  
Sent By tklarge Date 2020-03-04 Time 13:56 Rev Time 0.00
Received By tklarge Date 2020-03-04 Time 13:32 Sent To  
Notes
2020-03-04 13:56:521) SHOW THE RECIRCULATING LINE ON THE WATER RISER
 DIAGRAM IN ITS ENTIRETY. WPB AMEND. TO FBC SEC.107.2.1.
 2) SANITARY VENTS EXCEEDING 40 FEET IN DEVELOPED LENGTH
 SHALL BE INCREASED BY ONE NOMINAL PIPE SIZE FOR THE
 ENTIRE DEVELOPED LENGTH OF THE VENT PIPE PER 2017
 FBC-PLUMBING SE. 906.2. THE SUBMITTED NARRATIVE
 RESPONSE STATES TO REFER TO SHT. P-5.THIS SHEET IS THE
 WATER RISER NOT THE SANITARY RISER AND THE SANITARY
 RISER ON P-4 HAS NOT BEEN REVISED. 2ND REQUEST.
 3) PROVIDE A KEYNOTE LEGEND FOR THE KEYNOTE NUMBERS
 SHOWN ON THE WATER HEATER DETAIL ON SHT. P-6.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-02-24 Cont ID  
Sent By tklarge Date 2020-02-24 Time 09:15 Rev Time 0.00
Received By tklarge Date 2020-02-24 Time 05:20 Sent To  
Notes
2020-02-24 09:15:351) A HOT WATER RECIRCULATING LINE IS REQUIRED PER 2017
 FBC - PLUMBING SEC. 607.2.
 2) SANITARY VENTS EXCEEDING 40 FEET IN DEVELOPED LENGTH
 SHALL BE INCREASED BY ONE NOMINAL PIPE SIZE FOR THE
 ENTIRE DEVELOPED LENGTH OF THE VENT PIPE PER 2017
 FBC-PLUMBING SE. 906.2.
 3) THE SINK BY TOILET ROOM #232 IS LABELED S-3 ON THE
 SANITARY RISER AND S-1 ON THE WATER RISER. CLARIFY.
 4) THE SINK IN THE LAB/PHLEBOTOMY ROOM #227 IS LABELED
 AS S-1 ON THE SANITARY RISER AND S-2 ON THE WATER
 RISER. CLARIFY.
 5) SUBMIT A DETAIL OF THE THERMOSTATIC MIXING VALVE AND
 PIPING ARRANGEMENT TO THE VALVE. COMPLY WITH 2017
 FBC-PLUMBING SEC.607.2.2.
 6) PROVISIONS SHALL BE MADE FOR THERMAL EXPANSION
 CONTROL PER 2017 FBC-PLUMBING SEC.607.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  