Plan Review Details - Permit 20020611
Plan Review Stops For Permit 20020611
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2020-04-30 Cont ID  
Sent By rmcdouga Date 2020-04-30 Time 17:53 Rev Time 0.00
Received By rmcdouga Date 2020-04-30 Time 17:53 Sent To  
Notes
2020-04-24 17:38:38SEE ASBESTOS LETTER SUBMITTED WITH THIS RESUBMITTAL.
 JG.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-04-07 Cont ID  
Sent By jwitmer Date 2020-04-07 Time 12:06 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2020-04-07 12:06:04PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-02-24 Cont ID  
Sent By jwitmer Date 2020-02-24 Time 08:20 Rev Time 0.00
Received By jwitmer Date 2020-02-24 Time 06:22 Sent To  
Notes
2020-02-24 08:20:50PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-04-30 Cont ID  
Sent By rmcdouga Date 2020-04-30 Time 17:54 Rev Time 0.00
Received By rmcdouga Date 2020-04-30 Time 17:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-04-07 Cont ID  
Sent By jwitmer Date 2020-04-07 Time 12:03 Rev Time 0.00
Received By jwitmer Date 2020-04-07 Time 11:30 Sent To  
Notes
2020-04-07 12:03:452017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20020611
 ADD: 1200 S. FLAGLER DR. / SUITE: 1003
 CONT: R & B CONSTRUCTION INC.
 TEL: 561-346-8996
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. APRIL 07TH/ 2020
 ACTION: DENIED.
  
 1) COMPLIED.
 2) 2ND ROUND COMMENTS. WITH THE UNIT BEING REMODELED
 BEING ON THE 10TH FLOOR, AND THE FLOOR FINISHES ARE
 BEING REMOVED THEN THE NEW FLOORS WILL NEED TO MEET THE
 2017 FBC-B CODE, THEY WERE TOTALLY REMOVED NOT A
 REPAIR. 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
 WITH STATING THAT THE STRUCTURAL FLOORS ARE 8 INCH
 FLOOR SYSTEMS THEN THE TESTING REPORTS COULD BE FOR N 8
 INCH SLAB AND NO DROP CEILINGS. SEE THE 3 REQUIREMENTS
 THAT WILL NEED TO BE MET.
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2017)
 FOR TILE, STONE, MARBLE, AND WOOD FLOORING ALL NEED TO
 HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES
 TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 8 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 1A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 1B) FBC-B 2017 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 1ST ROUND OF COMMENTS. WITH THE SUITE # 1003 IT APPEARS
 IS ON THE 1ST FLOOR AND IS EXEMPT FROM THE REQUIREMENTS
 FOR SOUND INSULATION UNDER THE 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATIVE CODE SECTION 105.2(2). THIS BUILDING IS
 A HIGH RISE BUILDING AND STILL MEET THE REQUIREMENT
 FOUND IN THE 2017 FBC-B SECTION 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
 PLEASE PROVIDE TO THE CITY THE ACTUAL FLAME SPREAD TEST
 REPORT.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX,SFP & CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-02-24 Cont ID  
Sent By jwitmer Date 2020-02-24 Time 09:59 Rev Time 0.00
Received By jwitmer Date 2020-02-24 Time 06:22 Sent To  
Notes
2020-02-24 09:58:572017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20020611
 ADD: 1200 S. FLAGLER DR. / SUITE: 1003
 CONT: R & B CONSTRUCTION INC.
 TEL: 561-346-8996
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. FEB. 24/ 2020
 ACTION: DENIED.
  
 1) THE COVERSHEET LIST THE MINIMUM BUILDING TYPE AS AN
 TYPE II-B CONSTRUCTION. PLEASE NOTE IN AN UNSPRINKLERED
 R-2 OCCUPANCY THE BUILDING WOULD BE ALLOWED TO BE 4
 STORIES. IN THE 2017 FBC-B TABLE 404.4 INDICATES THE
 BUILDING MUST BE CLASSIFIED AS TYPE I-A CONSTRUCTION.
  
 2) WITH THE SUITE # 1003 IT APPEARS IS ON THE 1ST FLOOR
 AND IS EXEMPT FROM THE REQUIREMENTS FOR SOUND
 INSULATION UNDER THE 2017 WEST PALM BEACH AMENDMENTS TO
 THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATIVE
 CODE SECTION 105.2(2). THIS BUILDING IS A HIGH RISE
 BUILDING AND STILL MEET THE REQUIREMENT FOUND IN THE
 2017 FBC-B SECTION 603.1. EXCEPTION 2. INSULATION
 INSTALLED BETWEEN A FINISHED FLOOR AND SOLID DECKING
 WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A
 FLAME SPREAD INDEX OF NOT MORE THAN 200. PLEASE PROVIDE
 TO THE CITY THE ACTUAL FLAME SPREAD TEST REPORT.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX,SFP & CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-04-13 Cont ID  
Sent By jpearson Date 2020-04-13 Time 07:25 Rev Time 0.00
Received By jpearson Date 2020-04-07 Time 07:27 Sent To  
Notes
2020-04-13 07:25:39PASSED WITH PROVISO FOR LOAD CALCULATION.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-16 Cont ID  
Sent By jpearson Date 2020-03-16 Time 13:43 Rev Time 0.00
Received By jpearson Date 2020-03-16 Time 11:07 Sent To  
Notes
2020-03-16 13:43:22CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN HAS 3 RISER DIAGRAMS ON IT, WHAT IS THE PUPOSE
 OF THIS? THE LOAD CALCULAITON IS ALSO SHOWN TWICE.
 REMOVE REDUNDANT INFORMATION. PROVIDE CLARIFICATION.
 WPB FBC 107.2.1
 2. WIRE FOR FEEDER TO PANEL IS SPECIFIED AS # 2, WHICH
 IS RATED FOR 115 AMPS. THE LOAD CLACULATION PROVIDED
 STATES THAT THE LOAD IS 116 AMPS, SO THIS WIRE IS NOT
 SIZED TO HANDLE THE LOAD. PROVIDE CORRECTION. NEC 240.4
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-04-07 Cont ID  
Sent By pleduc Date 2020-04-07 Time   Rev Time 0.00
Received By pleduc Date 2020-04-07 Time 12:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-02-21 Cont ID  
Sent By pleduc Date 2020-02-21 Time   Rev Time 0.00
Received By pleduc Date 2020-02-21 Time 15:23 Sent To  
Notes
2020-02-21 15:25:03THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL
 AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS FOR CODE COVERAGE
 AND COMPLIANCE BY CERTIFIED CONTRACTORS.
  
 2) ANY AND ALL WORK ON THE FIRE SPRINKLER AND/OR FIRE
 ALARM SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS AND
 SHOP DRAWINGS BY CERTIFIED CONTRACTORS.
  
 3) THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL
 REMAIN ACTIVE THROUGHOUT THE DEMO AND CONSTRUCTION
 PERIODS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-05-12 Cont ID  
Sent By jgomez Date 2020-05-12 Time 11:06 Rev Time 0.00
Received By jgomez Date 2020-05-12 Time 11:01 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-05-08 Cont ID  
Sent By lmarchan Date 2020-05-08 Time 09:19 Rev Time 0.00
Received By lmarchan Date 2020-04-23 Time 17:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-04-13 Time   Rev Time 0.00
Received By lmarchan Date 2020-04-06 Time 16:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-03-17 Time   Rev Time 0.00
Received By lmarchan Date 2020-02-14 Time 13:34 Sent To  
Notes
2020-02-18 13:34:14B15

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-04-27 Cont ID  
Sent By ccole Date 2020-04-27 Time 15:27 Rev Time 0.00
Received By ccole Date 2020-04-27 Time 13:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-04-08 Cont ID  
Sent By ccole Date 2020-04-08 Time 16:11 Rev Time 0.00
Received By ccole Date 2020-04-08 Time   Sent To  
Notes
2020-04-08 16:17:582ND REVIEW FBC-2017 MECHANICAL
 PERMIT #20020611
 4/8/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 THE 1ST REVIEW COMMENTS LISTED BELOW STILL EXIST.
  
 THE ARCHITECT IS NOW INTENDING TO PROVIDE A LETTER ON
 THE 3RD RESUBMITTAL THAT WILL ADDRESS EXISTING BUILDING
 CONDITIONS AND THE TECHNICAL INFEASIBILTY OF MEETING
 THE CURRENT CODES.
  
 1) SHEET M1: PROVIDE RETURN AIR FROM THE BEDROOMS-
 SECTION 601.6 FBC M.
  
 2) M1: THE KITCHEN RANGE EXHAUST DUCT MUST RUN
 INDEPENDENTLY AND CANNOT BE LOCATED IN THE SAME SHAFT
 AS THE TOILET EXHAUST- SECTION 505.3 (12) FBC M.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-02-26 Cont ID  
Sent By ccole Date 2020-02-26 Time 12:31 Rev Time 0.00
Received By ccole Date 2020-02-26 Time 11:49 Sent To  
Notes
2020-02-26 12:40:441ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20020611
 2/26/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1: PROVIDE RETURN AIR FROM THE BEDROOMS-
 SECTION 601.6 FBC M.
  
 2) M1: THE KITCHEN RANGE EXHAUST DUCT MUST RUN
 INDEPENDENTLY AND CANNOT BE LOCATED IN THE SAME SHAFT
 AS THE TOILET EXHAUST- SECTION 505.3 (12) FBC M.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-04-07 Cont ID  
Sent By jwitmer Date 2020-04-07 Time 14:11 Rev Time 0.00
Received By jwitmer Date 2020-04-07 Time 13:54 Sent To  
Notes
2020-04-07 13:59:482017 FBC- PLUMBING PLAN REVIEW
 W. P. B. PERMIT: 20020611
 ADD: 1200 S. FLAGLER DR. SUITE: 1003
 CONT: R & B CONSTRUCTION INC
 TEL: 561-346-8996
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. APRIL 07TH/ 2020
 ACTION: PLUMBING PROVISO
  
 1) 2017 FBC-P SECTION 504.7.1. THE PAN SHAALL BE
 DRAINED BY AN INDIRECT WASTE PIPE HAVING A DIAMETER OF
 NOT LESS THAN 3/4 INCH.
 PIPING FOR SAFETY PAN DRAINS SHALL BE OF THOSE
 MATERIALS LISTED IN TABLE 605.4.
 PLUMBING PLAN REVIEW
 JIM WITMER

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-03-17 Cont ID  
Sent By jwitmer Date 2020-03-17 Time   Rev Time 0.00
Received By jwitmer Date 2020-04-07 Time 13:45 Sent To  
Notes
2020-03-17 14:21:232017 FBC- PLUMBING PLAN REVIEW
 W. P. B. PERMIT: 20020611
 ADD: 1200 S. FLAGLER DR. SUITE: 1003
 CONT: R & B CONSTRUCTION INC
 TEL: 561-346-8996
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MARCH 17TH/ 2020
 ACTION: DENIED
  
 1) SHEET A1.1THE EXISTING FLOOR PLAN AND PROPOSED FLOOR
 PLAN IT WOULD APPEAR THE RANGE AND KITCHEN SINK HAVE
 CHANGED LOCATIONS. THE P1 SHEET DOES NOT SHOW A RISER
 FOR THE NEW LOCATION OF THE KITCHEN SINK FOR SANITARY
 NOR THE SUPPLY LINES. THE LOCATION OF THE RISER NOR THE
 SIZE OF THE LATERAL ARE SHOWN ON SHEET P1.
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1 OF THE ADMINISTRATIVE CODE 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) MASTER BATHROOM THE P1 SANITARY RISER INDICATES A
 NEW TOILET WHEREAS THERE SEEMS TO BE A RELOCATION OF
 THE TOILET ABOUT 6 INCHES CLOSER TO THE NEW SHOWER
 ENCLOSURE. THE PLAN DOES NOT INDICATE ANY NEW OR
 RELOCATED HOLE THROUGH THE FLOOR SLAB AND FIRE
 RESISTANCE RATING OF THE SLAB AS REQUIRED BY SECTION
 307.3 OF THE 2017 FBC-PLUMBING CODE. PENETRATIONS OF
 FLOOR/ CEILING ASSEMBLIES AND ASSEMBLIES REQUIRED TO
 HAVE A FIRE-RESISTANCE RATING SHALL BE PROTECTED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING.
 PLEASE SHOW HOW COMPLIANCE WILL BE ACHIEVED FOR
 714.4.1.2 THROUGH- PENETRATION (HORIZONTAL) FIRESTOP
 SYSTEMS.
  
 3) SHEET P1 RISER P1 SHOWS A NEW TOILET, JUST
 RELOCATED, WHAT IS MISSING ON THIS RISER ARE THE 2
 LAVATORIES (1 NEW) SIZE OF THE LATERAL AND LENGTH OF
 THE LATERAL TO THE VERTICAL SANITARY. 2017 FBC-P TABLE
 710.1(2).
  
 4) SHEET P1 ON THE RISER P2 FOR THE GUEST BATH THE
 SANITARY RISER ONLY SHOWS THE TUB TO SHOWER CHANGE OF
 LOCATION, MISSING IS THE WATER CLOSET CHANGE OF
 LOCATION. 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 5) SHEET P1 WITH THE NEW LOCATION OF THE SHOWER AND
 WATER CLOSET AGAIN MISSING INFORMATION FOR THE
 THROUGH THE FLOOR AND FIRE RATED FLOOR/CEILING
 ASSEMBLY, 307.3 OF THE 2017 FBC-PLUMBING CODE.
 PENETRATIONS OF FLOOR/ CEILING ASSEMBLIES AND
 ASSEMBLIES REQUIRED TO HAVE A FIRE-RESISTANCE RATING
 SHALL BE PROTECTED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING. PLEASE SHOW HOW COMPLIANCE
 WILL BE ACHIEVED FOR 714.4.1.2 THROUGH- PENETRATION
 (HORIZONTAL) FIRESTOP SYSTEMS.
  
 6) SHEET A1.1 ALSO SHOWS THE FOYER AND UTILITY CLOSET
 BEING REARRANGED. THE LOCATION OF THE STACKED WASHER/
 DRYER HAS MOVED BUT THERE IS NO MENTION AS TO HOW OR
 WHERE THE LATERAL FORM THE WASHER WILL TIE INTO THE
 VERTICAL WASTE RISER. PLEASE SHOW COMPLIANCE WITH THE
 2017 FBC-P SECTION 406.2 THE TRAP AND FIXTURE DRAIN FOR
 AN AUTOMATIC CLOTHES WASHER STANDPIPE SHALL NOT BE LESS
 THAN 2 INCHES IN DIAMETER. THE FIXTURE DRAIN FOR THE
 STANDPIPE SERVING AN AUTOMATIC CLOTHES WASHER SHALL
 CONNECT TO A 3 INCH OR LARGER DIAMETER FIXTURE BRANCH
 OR STACK.
  
 7) SHEET P-1 DOES NOT SHOW THE LOCATION OF THE CLOTHES
 WASHER SHUT OFF VALVES AND IS BLOCKED IN BY THE WATER
 HEATER ON ONE SIDE AND A WALL ON THE OTHER. THE PLAN
 DOES NOT SHOW HOW COMPLIANCE WITH THE 2017 FBC-P
 SECTION 606.3 ACCESS SHALL BE PROVIDED TO ALL SHUT OFF
 VALVES WITHOUT THE HAVING TO MOVE THE APPLIANCES
 (CLOTHES WASHER).
  
 8) THE P-1 SHEET DOES NOT SHOW ANY RISERS FOR THE
 SUPPLY LINES. THE DISHWASHER AND CLOTHES WASHER HAVE
 QUICK CLOSING VALVES ARE BEING UTILIZED AND NEED TO
 SHOW COMPLIANCE WITH 604.9 WATER HAMMER ARRESTORS.
  
 9) THE P-1 SHEET SHOWS AN ELECTRIC WATER HEATER DETAIL
 AND DRAIN PAN. THE PAN DOES NOT SHOW A ? INCH DRAIN
 PIPE FROM THE PAN. SEE FBC-P SECTION 504.7.1 PAN SIZE
 AND DRAIN.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 JAMES A. WITMER BN, PX, SFP & CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-05-12 Cont ID  
Sent By jgomez Date 2020-05-12 Time 11:03 Rev Time 0.00
Received By jgomez Date 2020-05-12 Time 11:01 Sent To  
Notes
2020-05-12 11:05:5905/12/2020 MECHANICAL REVIEW LETTER RECEIVED WITH
 ARCHITECT'S ORIGINAL SEAL /SIGNATURE. LETTER SENT TO
 LIBRARY UNDER "DONE" STACK. JG.
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-05-08 Cont ID  
Sent By lmarchan Date 2020-05-08 Time 09:19 Rev Time 0.00
Received By lmarchan Date 2020-05-08 Time 09:19 Sent To  
Notes
2020-04-24 17:35:40ARCHITECT'S MECHANICAL RESPONSE LETTER HAS A COPY OF
 THE ARCHITECT'S SEAL AND SIGNATURE. JG.
  
 NO PLANS SUBMITTED THIS TIME. SEE SIGNATURE REVIEW
 COMMENTS ON FIRST ROUND. JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-04-07 Cont ID  
Sent By shill Date 2020-04-07 Time 06:45 Rev Time 0.00
Received By shill Date 2020-04-07 Time 06:45 Sent To  
Notes
2020-04-07 06:46:40SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FS471, 481
  
 1. PAGES ARE NOT DIGITALLY SIGNED. EITHER EMAIL
 DIGITALLY SIGNED DOCUMENTS TO ME, OR SUBMIT ONE SIGNED
 AND SEALED ORIGINAL AFTER ALL REVIEWS ARE COMPLETE.
 (PAPER ORIGINALS ORIGINALLY SUBMITTED HAVE BEEN
 SUPERSEDED, ALL SHEETS).
  
 2. THE APPLICATION LACKS THE SIGNATURE OF THE QUALIFIER
 OF R&B CONSTRUCTION INC. THE APPLICATION IS SIGNED BY
 THE OWNERS ON EACH SIDE (THOMAS DUNN, CINDY DUNN).
  