Plan Review Details - Permit 20020552
Plan Review Stops For Permit 20020552
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-02-20 Cont ID  
Sent By pleduc Date 2020-02-20 Time   Rev Time 0.00
Received By pleduc Date 2020-02-17 Time 13:52 Sent To I
Notes
2020-02-20 13:55:20THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ANY UNDERGROUND WORK SHALL BE SUBMITTED UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PLEASE ENSURE COMPLIANCE.
  
  
 2) PROVIDE PRV WHERE APPLICABLE PER THE REQUIRMENT OF
 NFPA 14
  
 7.2.3.2* WHERE THE STATIC PRESSURE AT A 21?2 IN. (65
 MM) HOSE
 CONNECTION EXCEEDS 175 PSI (12.1 BAR), AN APPROVED
 PRESSURE REGULATING
 DEVICE SHALL BE PROVIDED TO LIMIT STATIC AND RESIDUAL
 PRESSURES AT THE OUTLET OF THE HOSE CONNECTION TO 175
 PSI
 (12.1 BAR).
  
 PLEASE ENSURE COMPLIANCE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-02-20 Cont ID  
Sent By spalmer Date 2020-02-20 Time 17:45 Rev Time 0.00
Received By spalmer Date 2020-02-13 Time 13:02 Sent To  
Notes
2020-02-14 13:03:05ROUTED TO FIRE INBOX