| 2020-02-13 06:01:11 | 1) YOU HAVE SUBMITTED A PE PIPE SIZING SHEET WITH TWO |
| | DIFFERENT SIZING TABLES ON IT. WHICH ONE IS BEING USED |
| | TO SIZE THE PE SYSTEM? ALSO, WHERE IS THIS SIZING TABLE |
| | FROM? THE SYSTEM MUST BE SIZED BASED ON THE TABLES IN |
| | THE 2017 FBC-FUEL GAS CODE OR USING THE SIZING TABLES |
| | INCLUDED IN A LISTED PIPING SYSTEM'S MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. 2017 FBC-FUEL GAS CODE |
| | SEC.402.3. |
| | 2) THE SIZING TABLE SUBMITTED FOR THE SCH. 40 METALLIC |
| | PIPE IS FROM THE UNIFORM PLUMBING CODE. THIS IS NOT A |
| | REFERENCED STANDARD IN THE 2017 FBC-FUEL GAS CODE OR |
| | PLUMBING CODE. THEREFORE THIS SIZING TABLE IS |
| | UNACCEPTABLE. SUBMIT A SIZING TABLE FROM ONE OF THE |
| | REQUIREMENTS IN THE 2017 FBC-FUEL GAS CODE SEC.402.3. |
| | 3) SUBMIT TWO COPIES OF A HOUSE PLAN / FLOOR PLAN |
| | SHOWING THE LOCATION OF THE TANKLESS WATER HEATER AND |
| | THE LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR |
| | WINDOWS IN RELATION TO THE TANKLESS WATER HEATER. THE |
| | LOCATION OF THE TANKLESS WATER HEATER SHALL COMPLY WITH |
| | THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE HOUSE |
| | PLAN / FLOOR PLAN CAN BE HAND DRAWN. WPB AMEND. TO FBC |
| | SEC. 107.2.1. |
| | 4) THE BTU LOAD OF THE RANGE ON THE GAS DRAWING IS |
| | SHOWN AS 28,100 BTU'S. ADDING UP THE BTU LOAD OF THE |
| | BURNER'S ON THE MANUFACTURER'S SPECIFICATION SHEET |
| | COMES TO 54,600 BTU'S. WHERE DDID THE 28,100 BTU LOAD |
| | COME FROM? |
| | 5) A SEPARATE PERMIT WILL BE REQUIRED FOR THE ELECTRIC |
| | THAT NEEDS TO BE INSTALLED. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |