Plan Review Details - Permit 20020425
| Plan Review Stops For Permit 20020425 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2020-03-18 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2020-03-18 |
Time |
13:14 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2020-03-18 |
Time |
13:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2020-02-25 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2020-02-25 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2020-02-25 |
Time |
10:03 |
Sent To |
I |
|
| Notes |
| 2020-02-25 10:03:17 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET | | | OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE | | | SIGNED AND SEALED BY THE DESIGN PROFESSIONAL OF RECORD. | | | PROVIDE CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481 | | | 2. PROVIDE NARRATIVE OF REVISIONS. WPB FBC 107.2.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH | | | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. | | | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL | | | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. | | | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD | | | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2020-03-31 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2020-03-31 |
Time |
07:59 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-03-25 |
Time |
14:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2020-03-23 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-03-16 |
Time |
15:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2020-02-25 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-02-11 |
Time |
14:29 |
Sent To |
|
|
| Notes |
| 2020-02-12 14:29:20 | REVISION ROUTED TO CCOLE |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2020-03-27 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-03-27 |
Time |
11:03 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-03-27 |
Time |
10:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2020-03-23 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-03-23 |
Time |
07:31 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2020-03-20 |
Time |
09:16 |
Sent To |
|
|
| Notes |
| 2020-03-23 07:35:00 | 2ND REVIEW FBC-2017 MECHANICAL | | | PERMIT #20020425 | | | 3/23/20 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) REVISED SHEET M-102 WAS NOT RESUBMITTED FOR REVIEW | | | WITH THE OTHER PLAN SHEETS- SECTION 107.2.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | | SEPARATELY AND MARK "VOID" OR "OLD" ON THEM. PLEASE | | | RETAIN THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. | | | THIS PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | | UPDATED. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2020-02-13 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-02-13 |
Time |
10:08 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2020-02-13 |
Time |
10:08 |
Sent To |
E |
|
| Notes |
| 2020-02-13 10:13:24 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #20020425 | | | 2/13/20 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M-102: THE ENGINEER AND ARCHITECT OF RECORD | | | SHALL PROVIDE THEIR RAIDED OR INK SEALS AND WET | | | SIGNATURES ON THE PLANS- FL. STATUTE 471.025 AND | | | SECTION 61G15-23.005 FLORIDA ADMINISTRATIVE CODE & FL | | | STATUTE 481.221 AND SECTION 61G-16.005 FLORIDA | | | ADMINISTRATIVE CODE. | | | | | | 2) M-102: PLEASE EXPAND ON NOTE #7 REGARDING THE | | | EXHAUST SYSTEMS. PROVIDE EXHAUST VENTILATION | | | CALCULATIONS AND THE SEQUENCES OF OPERATION FOR THE | | | FANS- SECTION 107.2.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD | | | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER | | | SEPARATELY AND MARK "VOID" OR "OLD" ON THEM. PLEASE | | | RETAIN THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. | | | THIS PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS | | | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR | | | UPDATED. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2020-03-31 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-03-31 |
Time |
07:19 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-03-31 |
Time |
07:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2020-03-18 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2020-03-18 |
Time |
13:14 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2020-03-18 |
Time |
13:14 |
Sent To |
|
|
| Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |