Plan Review Details - Permit 20020408
Plan Review Stops For Permit 20020408
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2020-02-19 Cont ID  
Sent By rmcphers Date 2020-02-19 Time 15:07 Rev Time 0.00
Received By rmcphers Date 2020-02-19 Time 15:07 Sent To  
Notes
2020-02-19 15:08:19NOT REQUIRED - NEW BUILDING BUILD OUT

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-05-01 Cont ID  
Sent By rmcphers Date 2020-05-01 Time 10:18 Rev Time 0.00
Received By rmcphers Date 2020-05-01 Time 10:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-03-30 Cont ID  
Sent By rmcphers Date 2020-03-30 Time 08:38 Rev Time 0.00
Received By rmcphers Date 2020-03-30 Time 08:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-02-19 Cont ID  
Sent By rmcphers Date 2020-02-19 Time 15:06 Rev Time 0.00
Received By rmcphers Date 2020-02-19 Time 11:15 Sent To  
Notes
2020-02-19 15:07:31BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED -
 1) NEED CONTRACTOR INFO ON THE BUILDING PERMIT
 APPLICATION.
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2020-05-12 Cont ID  
Sent By jleahy Date 2020-05-12 Time 11:57 Rev Time 0.00
Received By jleahy Date 2020-05-12 Time 10:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2020-05-06 Cont ID  
Sent By jleahy Date 2020-05-06 Time 12:22 Rev Time 0.00
Received By jleahy Date 2020-05-06 Time 12:22 Sent To  
Notes
2020-05-06 12:23:46TO DATE ONLY NOTE #5 HAS BEEN ADDRESSED SEE FIRST
 REVIEW FOR ALL PLAN REVIEW NOTES JLEAHY

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2020-03-28 Cont ID  
Sent By jleahy Date 2020-03-28 Time 12:32 Rev Time 0.00
Received By jleahy Date 2020-03-28 Time 12:32 Sent To  
Notes
2020-03-28 12:33:50ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 ONLY NOTE #5 FROM THE ORIGINAL REVIEW HAS BEEN
 ADDRESSED JLEAHY

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-04-07 Cont ID  
Sent By jpearson Date 2020-04-07 Time 15:33 Rev Time 0.00
Received By jpearson Date 2020-03-28 Time 11:32 Sent To  
Notes
2020-04-07 15:34:05REVIEWED BY JAKE LEAHY.
2020-03-28 11:33:57ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 ONLY PLAN REVIEW NOTE #5 HAS BEEN ADDRESSED.
  
 SEE ORIGINAL PLAN REVIEW NOTES FROM 3/2/20 JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-02 Cont ID  
Sent By jleahy Date 2020-03-02 Time 11:24 Rev Time 0.00
Received By jleahy Date 2020-03-02 Time 09:28 Sent To  
Notes
2020-03-02 11:14:55FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) VALUE IS LOW FOR THIS TYPE OF BUILDOUT. $200,000
  
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2) PAGE E110
 A FEW NOTES CALL FOR " BY OWNER" THIS NEEDS TO BE
 INCLUDED IN THE VALUE OF THE PERMIT.
 KITCHEN AND KITCHEN AREA SEEMS TO BE MISSING GFCI
 PROTECTION ON 15 AND 20 AMPR RECEPTACLES.
 210.8 (B) OTHER THAN DWELLING UNITS. ALL 125-VOLT,
 SINGLE-PHASE,
 15- AND 20-AMPERE RECEPTACLES INSTA LLED IN THE
 LOCATIONS SPECIFIED
 IN 210.8(B)(1) THROUGH (8) SHALL HAVE GROUND-FAULT
 CIRCUITINTERRUPTER
 PROTECTION FOR PERSONNEL. (2) KITCHENS (5) SINKS ?
 WHERE RECEPTACLES ARE INSTALLED WITHIN 1.8 M (6 FT)
 OF THE OUTSIDE EDGE OF THE SINK,
  
 3) NO PANEL SCHEDULES ARE INCLUDED WITH PLANS.
 PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION. EVERY
 CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY
 IDENTIFIED AS TO
 ITS CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. THE
 IDENTIFICATION SHALL INCLUDE AN APPROVED DEGREE OF
 DETAIL THAT ALLOWS
 EACH CIRCUIT TO BE DISTINGUISHED FROM ALL OTHERS. SPARE
 POSITIONS THAT CONTAIN UNUSED OVERCURRENT DEVICES OR
 SWITCHES SHALL BE
 DESCRIBED ACCORDINGLY. THE IDENTIFICATION SHALL BE
 INCLUDED IN A CIRCUIT DIRECTORY THAT IS LOCATED ON THE
 FACE OR INSIDE OF THE
 PANEL DOOR IN THE CASE OF A PANELBOARD AND AT EACH
 SWITCH OR CIRCUIT BREAKER IN A SWITCHBOARD OR
 SWITCHGEAR
  
 4) NO LOAD CALCULATION INCLUDED WITH THE PLANS.
 PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL LOADS.
 NEC 220
  
 5) NO FAULT CURRENT CALCULATION FOR AIC RATING INCLUDED
 WITH THE PLANS.
 PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT CURRENT
 AT NEW PANEL TO CONFIRM AIC RATING IS ADEQUATE. NEC
 110.10
 PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE MARKED
 WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT
 AVAILABLE PER NEC 110.24
 PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
  
 6) PAGE E710
 SEPARATE PERMIT REQUIRED FOR UPS SYTEM BY OWNER.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2020-02-26 Time 0:00 Rev Time 0.00
Received By sathomas Date 2020-02-26 Time 00:00 Sent To  
Notes
2020-03-10 11:29:04PROVISO - COLD SHELL ONLY

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2020-05-22 Cont ID  
Sent By jpearson Date 2020-05-22 Time 08:49 Rev Time 0.00
Received By jpearson Date 2020-05-22 Time 08:08 Sent To  
Notes
2020-05-22 08:08:42REVIEWED BY JERRY SMITH. NO CHANGES TO PREVIOUSLY
 APPROVED GAS PLAN.
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-04-07 Cont ID  
Sent By thunt Date 2020-04-07 Time 09:19 Rev Time 0.00
Received By tklarge Date 2020-03-28 Time 09:36 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-02-27 Cont ID  
Sent By jesmith Date 2020-02-27 Time 11:47 Rev Time 0.00
Received By jesmith Date 2020-02-27 Time 07:45 Sent To  
Notes
2020-02-27 11:47:53CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 58 = LIQUIFIED PETROLEUM GAS
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
  
 GAS COMMENTS: DENIED
 1. PLANS INDICATE A LPG SYSTEM. PREVIOUSLY ISSUED
 MASTER PERMIT 19081537 FOR BUILDING SHELL DOES NOT SHOW
 EVIDENCE OF SEPARATE GAS PERMIT BEING APPLIED FOR AND
 ISSUED. CONSEQUENTLY THERE IS NO RECORD OF ANY
 INSTALLATION OF THAT SYSTEM AND AS SUCH THE NOTE ON NEW
 PERMIT 20020408 SUMITTAL (PLAN PAGE SP101) INDICATING
 EXISTING 1000 GALLON LP TANK IS INCORRECT. IT SHOULD
 READ NEW 1000 GALLON LP TANK TO BE PROVIDED UNDER A
 SEPARATE PERMIT. ADDITIONALLY, THE PIPING NOTED ON MP
 19081537 PLAN PAGE P.01 SHALL BE INCORPORATED INTO MP
 20020408 AND SHALL CLEARLY INDICATE WHICH WILL BE UNDER
 THE OLD MP 19081537 AND WHICH IS TO BE UNDER THE NEW
 PERMIT. ADDITIONALLY, THE ORIGINAL MP DRAWINGS DO NOT
 PROVIDE FOR LONGEST LENGTH AND LOAD FOR THE 2 PSI
 PIPING AND CALCULATIONS SHALL BE PROVIDED FOR THE SAME.
 IF THE STEPDOWN REGULATOR IS IN MP 20020408 SCOPE OF
 WORK, THEN PROVIDE A DETAIL SHOWING REGULATOR WITH
 SHUTOFF VALVE, UNION AND DIRT LEG. PROVIDE
 MANUFACTURE'S SPECIFICATION; REGULATOR SHALL BE RATED
 FOR OUTDOORS. ALL VERBAGE ALLUDING TO EXISTING SHALL BE
 REMOVED AND INSTEAD SHALL REFERENCE WORK PROVIDED UNDER
 MP 19081537.
 2. SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS
 APPLIANCES. WHERE COMBUSTION AIR IS PROVIDED BY THE
 BUILDING'S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR. FBC FG
 304.9.3
 3. PER WPB FBC 107.2.1 SUBMIT MANUFACTURER'S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT INCLUDING BUT NOT LIMITED TO KITCHEN, WATER
 HEATER AND ROOFTOP AIR CONDITIONING UNITS. TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND FBC FG
 402.2, AND 301.3. GAS APPLIANCES SHALL BE LISTED AND
 LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
 4. PLAN SHEET A131: KES 13 (GRILL) AND KES 14 (RANGE)
 INDICATE NATURAL GAS AS FUEL; PLAN SHEET P100 INDICATES
 FUEL TYPE IS LP. PER WPB FBC 107.2.1, RECONCILE THE TWO
 PLAN SHEETS.
 5. PLAN SHEET P100; GAS RISER NOTES A SECTION OF
 HORIZONTAL PIPING DOWNSTREAM OF DWH-1 CONNECTION SIZED
 1 INCH. SHALL BE 1-1/4 INCH PER FBC FG TABLE 402.4(28).
 6. SUBMIT A COMPLETE DETAIL SHOWING THE TYPE, LOCATION,
 SIZE, TERMINATION POINT, HEIGHT ABOVE THE FINISH ROOF
 AND ANCHORING DETAILS OF THE GAS VENT(S) PER FBC FG 502
 THRU 505
 7. REVISE DETAIL SHOWING THE EMERGENCY HOOD SHUT DOWN
 SHUT OFF VALVE. EMERGENCY HOOD SHUT DOWN SHUT OFF VALVE
 SHALL BE BELOW THE CEILING. THE MANUAL SHUTOFF VALVE
 SHALL BE UPSTREAM. "UNION TO BE DOWN STREAM OF MANUAL
 VALVE". SECS. 10.4, 10.5 OF NFPA 96-08.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 20020408 7000 OKEECHOBEE BLVD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2020-05-22 Time   Rev Time 0.00
Received By lmarchan Date 2020-05-07 Time 10:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-05-06 Cont ID  
Sent By jleahy Date 2020-05-06 Time 12:24 Rev Time 0.00
Received By jleahy Date 2020-04-23 Time 15:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-04-07 Cont ID  
Sent By lmarchan Date 2020-04-07 Time 15:34 Rev Time 0.00
Received By lmarchan Date 2020-03-26 Time 12:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-10 Cont ID  
Sent By lmarchan Date 2020-03-10 Time 11:29 Rev Time 0.00
Received By lmarchan Date 2020-02-11 Time 13:24 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2020-02-19 Cont ID  
Sent By rmcphers Date 2020-02-19 Time 15:08 Rev Time 0.00
Received By rmcphers Date 2020-02-19 Time 15:08 Sent To  
Notes
2020-02-19 15:09:41NOT REQUIRED - BUILD OUT FOR AN EXISTING SHELL BUILDING

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-04-28 Cont ID  
Sent By ccole Date 2020-04-28 Time 08:36 Rev Time 0.00
Received By ccole Date 2020-04-27 Time 13:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-03-30 Cont ID  
Sent By medwards Date 2020-03-30 Time 07:54 Rev Time 0.00
Received By medwards Date 2020-03-30 Time 07:54 Sent To  
Notes
2020-03-30 07:57:222ND REVIEW FBC-2017 MECHANICAL
 PERMIT-20020408
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE AC AND HEATING CALCULATIONS REQUIRES THE
 ELECTRONIC SIGNATURE AND SEAL OF THE ENGINEER WHO
 PREPARED THE DOCUMENT. FL. STATUTE 471.025 AND SECTION
 61G15-23.005 FLORIDA ADMINISTRATIVE CODE.
 2) SHEET M100: PROVIDE CFM?S OF EACH SUPPLY AIR GRILL
 SUPPLIED FROM THE 20/16 DUCT FROM RTU-1 AT THE HOOD
 AREA.
 3) PLEASE INDICATE WHICH SHEET HAS THE GAS APPLIANCE
 CUT SHEETS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-02-24 Cont ID  
Sent By ccole Date 2020-02-24 Time 14:42 Rev Time 0.00
Received By ccole Date 2020-02-24 Time 14:39 Sent To  
Notes
2020-02-24 15:01:271ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20010408
 2/25/2020
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN
 EXHAUST HOODS, FIRE SUPPRESSION SYSTEMS, AND THE WALKIN
 COOLER- SECTION 107.2.1 WPB. PLEASE NOTE THAT THE COSTS
 ASSOCIATED WITH THESE PHASES OF THE PROJECT SHALL BE
 ALSO BE SEPARATED FROM THE MAIN PERMIT VALUE. PLEASE
 PROVIDE A COST BREAKDOWN FOR THE ENTIRE PROJECT TO
 VERIFY ACCURATE PERMIT VALLUE- SECTION 109.3 WPB
  
 2) THE COMCHECK ENERGY COMPLIANCE SUBMITTAL REQUIRES
 THE ELECTRONIC SIGNATURE AND SEAL OF THE ENGINEER WHO
 PREPARED THE DOCUMENT- FL. STATUTE 471.025 AND SECTION
 61G15-23.005 FLORIDA ADMINISTRATIVE CODE.
  
 3) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 RTU'S IN ACCORDANCE WITH SECTION C403.2.1 FBC EC.
  
 4) SHEET M600: PROVIDE MINIMUM VENTILATION CALCULATIONS
 FOR ALL OCCUPIED ROOMS AND SPACES- TABLE 403.3.1.1 FBC
 M. PROVIDE A SCHEDULE ON THE PLAN THAT INDICATES THE
 REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR.
  
 5) M600: INDICATE HOW COMBUSTION AIR IS BEING PROVIDED
 TO THE NEW GAS COOKING APPLIANCES AND PROVIDE
 CALCULATIONS- SECTION 304 FBC FG.
  
 6) M100 & M600: AUTOMATIC SHUTOFF DAMPERS, EITHER
 MOTORIZED OR GRAVITY, SHALL BE PROVIDED FOR THE O/A
 INTAKES- SECTION C403.2.4.3 FBC-EC.
  
 7) M700: PROVIDE DUCT HANGING AND CONNECTION DETAILS
 PER SMACNA STANDARDS- SECTION 603 FBC M.
  
 8) M100: PROVIDE CONDENSATE DISPOSAL DETAILS FOR THE
 RTU'S- SECTION 307.2.3 FBC M.
  
 9) M100: PROVIDE ENGINEERING FOR INSTALLATION OF THE
 RTU'S- SECTION 301.15 FBC M. PLEASE NOTE THAT
 ENGINEERING FOR THE THE KITCHEN HOOD FANS AND THE
 WALKIN COOLER CONDENSERS SHALL BE PROVIDED UNDER THE
 REQUIRED SEPARATE PERMITS.
  
 10) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 GAS-FIRE COOKING APPLIANCES- SECTION 623.1 FBC FG.
  
 11) ADVISORY: THE KITCHEN HOOD IS UNDER SEPARATE
 PERMIT, HOWEVER PLEASE BE ADVISED THAT THE TEMPERATURE
 DIFFERENTIAL BETWEEN THE EXHAUST HOOD MAKEUP AIR AND
 THE AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10
 DEGREES F- SECTION 508.1.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2020-05-22 Cont ID  
Sent By jpearson Date 2020-05-22 Time 08:48 Rev Time 0.00
Received By jpearson Date 2020-05-22 Time 08:08 Sent To  
Notes
2020-05-22 08:08:20REVIEWED BY JERRY SMITH.
  
 PLUMBING COMMENTS: APPROVED
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20020408 7000 OKEECHOBEE BLVD
  
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2020-05-05 Cont ID  
Sent By jpearson Date 2020-05-05 Time 11:34 Rev Time 0.00
Received By jpearson Date 2020-05-05 Time 08:43 Sent To  
Notes
2020-05-05 08:43:46REVIEWED BY JERRY SMITH.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 3RD REVIEW
 PLUMBING COMMENTS: DENIED
 1. GENERAL: ARCHITECTURAL RESPONSE TO COMMENT #1 TO
 PLUMBING COMMENTS PROVIDED BY TIM LARGE DATED 4/7/20 IS
 NOTED AND PROVIDES COMPLIANCE.
 HOWEVER, MEP DID NOT RESPOND TO PLUMBING COMMENTS
 PROVIDED BY TIM LARGE DATED 4/7/20 IN THE RESPONSE
 LETTER PREPARED BY MR. DENNIS ALT AND DATED 4/16/20;
 UPON FURTHER REVIEW OF THE PLANS I OFFER THE FOLLOWING:
 2. COMMENT #2: THREE COMPARTMENT SINK IS FOR POT WASH
 AND NOT FOOD PREP; AS SUCH, IT IS NOT SUBJECT TO THE
 REQUIREMENTS OF FBC PL 802.1.1 WHICH APPLIES TO FOOD
 PREP SINKS.
 3. COMMENT #3: RESPONSE IS REQUIRED.
 4. COMMENT #4: IT IS NOTED THAT NOTE 9 ON P110 CALLS
 FOR A ? INCH VALVED DRAIN FROM HOT FOOD TABLE TO THE
 FLOOR SINK IN QUESTION. THE TERM SML SEEMS TO APPLY TO
 KITCHEN EQUIPMENT SCHEDULE AND FLOOR PLAN (SEE A130 AND
 A131) WHICH DESCRIBES SHELVING. PER WPB FBC 107.2.1,
 PLEASE CLARIFY; REMOVE THE TERM SML FROM THE SANITARY
 RISER AND REPLACE WITH THE SYMBOL FOR NOTE 9.
 5. COMMENT #5: IT IS NOTED THAT NOTE 10 ON P110 CALLS
 FOR DRAINS FROM THE TEA TRAY DRAIN AND THE SODA MACHINE
 TO THE FLOOR SINK IN QUESTION. AS SUCH, THEY ARE NOT
 REQUIRED TO DISCHARGE TO THE GREASE INTERCEPTOR. PER
 WPB FBC 107.2.1, PLEASE REMOVE THE TERM UTENSIL COUNTER
 FROM THE SANITARY RISER AND REPLACE WITH THE SYMBOL FOR
 NOTE 10.
  
 ADDITIONAL COMMENT REGARDING COMMENT #12 OF REVIEW #1
 DATED 2/27/20: PLEASE NOTE THAT P110 REV 1 PLAN VIEW
 CORRECTED THE DEFICIENCY REGARDING THE HORIZONTAL DRY
 VENT AT THE THREE-COMPARTMENT SINK, BUT THE SANITARY
 RISER IS STILL NOT COMPLIANT. PER WPB FBC 107.2.1, SHOW
 COMPLIANCE ON THE SANITARY RISER AND RECONCILE TO THE
 PLAN VIEW.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20020408 7000 OKEECHOBEE BLVD
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-04-07 Cont ID  
Sent By thunt Date 2020-04-07 Time 10:17 Rev Time 0.00
Received By tklarge Date 2020-04-06 Time 10:01 Sent To  
Notes
2020-04-07 10:17:461) SHT. A710 - DETAIL #1 - SHOW THE DIMENSIONS OF THE
 REQUIRED CLEAR FLOOR SPACES FOR THE HANDICAP ACCESSIBLE
 FIXTURES ON THE PLAN. COMPLY WITH 2017 FBC-ACCESS.
 SECS. 305, 604.3, 606.2.
 2) SHT. P700 - DETAIL #2 - EACH WELL OF THE THREE
 COMPARTMENT SINK SHALL DISCHARGE INDEPENDENTLY TO A
 WASTE RECEPTOR. 2017 FBC-PLUMBING SEC.802.1.1.
 3) SHT. P 110 - THE RISER SHOWS AN ICE MACHINE
 DISCHARGING TO THE GREASE WASTE SYSTEM. WASTES THAT DO
 NOT REQUIRE TREATMENT OR SEPARATION SHALL NOT BE
 DISCHARGED INTO ANY INTERCEPTOR OR SEPARATOR.
 FBC-PLUMBING SEC.1003.2.
 4) SHT. P110 - IDENTIFY FIXTURE SML ON THE RISER
 DIAGRAM ON SHT. 110. THIS IS NOT SHOWN ON THE EQUIPMENT
 SCHEDULE ON SHT. P600. - CLARIFY.
 5) SUBMIT ADDITIONAL INFORMATION ON THE INDIRECT WASTE
 FROM THE UTENSIL COUNTER. IF THIS WASTE CONTAINS ANY
 GREASE IT SHALL DISCHARGE TO THE GREASE WASTE SYSTEM.
 FBC-PLUMBING SEC.1003.1.CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-02-27 Cont ID  
Sent By jesmith Date 2020-02-27 Time 15:41 Rev Time 0.00
Received By jesmith Date 2020-02-25 Time 16:16 Sent To  
Notes
2020-02-27 15:41:43CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 1. GENERAL: ELIMINATE ALL VERBAGE ALLUDING TO EXISTING
 WORK. INSTEAD, REFER TO WORK PERFORMED OR TO BE
 PERFORMED UNDER MP 19081537.
 2. PLAN PAGE SP101 INDICATES AN EXISTING 1250 GALLON
 GREASE TRAP. A PERMIT HAS BEEN ISSUED FOR THE GREASE
 TRAP AND PIPING OUT OF BUILDING INTO THE INTERCEPTOR
 AND CONNECTION TO THE SANITARY (SEE MASTER PERMIT
 19081537 PLAN PAGE P.01 AND SUB PERMIT 20010671)
 ADDITIONALLY A SUB PERMIT 20011040 HAS BEEN ISSUED FOR
 PLUMBING FOR THE SHELL. BOTH DISCIPLINES STILL APPEAR
 TO BE OPEN. INDICATE ON THE NEW PLANS THAT NEW WORK IS
 TO BE COORDINATED WITH WORK PERMITTED UNDER MASTER
 PERMIT 19081537. THERE ARE INCONSISTENCIES BETWEEN MP
 19081537 AND NEW MP 20020408. THE PIPING NOTED ON MP
 19081537 PLAN PAGE P.01 SHALL BE INCORPORATED INTO NEW
 MP 20020408 AND SHALL CLEARLY INDICATE WHICH WILL BE
 UNDER THE OLD MP 19081537 AND WHICH IS TO BE UNDER THE
 NEW PERMIT.
 3. PLAN SHEET P110, NOTE 7; REVISE TO READ ?TO 1250
 GALLON INTERCEPTOR INSTALLED UNDER MP 19081537, SUB
 PERMIT 20010671. REMOVE ALL VERBAGE ALLEGING EXISTING
 WORK.
 4. MP 19081537 PLAN SHEET P.01 INDICATES A BACKFLOW
 PREVENTER ON THE WATER SERVICE. NOWHERE DOES THERE
 APPEAR TO BE A SIZE OR LOCATION INDICATED ON THE PLANS
 FOR EITHER MP 19081537 OR NEW MP 20020408. PER WPB FBC
 107.2.1, PROVIDE ON PLAN SHEET SP101, A LOCATION OF THE
 BACKFLOW PREVENTER WITH A NOTE THAT STATES A SEPARATE
 PERMIT SHALL BE REQUIRED FOR THE BACKFLOW PREVENTER.
 5. REGARDING THE GREASE TRAP; PROVIDE CALCULATIONS TO
 CONFIRM THAT THE 1250 GALLON GREASE TRAP WILL BE
 SUFFICIENT FOR THE GREASY WASTE PER WPB FBC 107.2.1.
 6. P110, NOTE 5; PROVIDE BACKFLOW PREVENTER AT ICE
 MACHINE PER FBC PL 608.3.
 7. P110, NOTE 6; MOP SINK FAUCET SHALL BE PROVIDED WITH
 A VACUUM BREAKER PER FBC PL 608.2.
 8. P110, NOTE 6 AND 12; CHEMICAL DISPENSER FAUCET SHALL
 BE PROVIDED WITH A BACKFLOW PREVENTER PER FBC PL 608.3.
 9. PER WPB FBC 107.2.1, PROVIDE MANUFACTURER?S
 SPECIFICATION/CUT SHEETS ON ALL KITCHEN AND SPECIALTY
 EQUIPMENT APPURTENANCES THAT CONNECT TO WATER OR
 DRAINAGE, EITHER DIRECTLY OR INDIRECTLY.
 10. LAVATORY TEMPERATURE LIMITING DEVICES SHALL CONFORM
 TO ASSE 1070 PER FBC PL 416.5.
 11. THE HORIZONTAL DRY VENTS CONNECTING TO THE WATER
 CLOSET FIXTURE DRAINS ARE PROHIBITED PER FBC PL 905.3
 (A DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL
 CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN
 PIPE) AND 905.4 (A DRY VENT SHALL RISE VERTICALLY TO
 NOT LESS THAN 6 INCHES (152 MM) ABOVE THE FLOOD LEVEL
 RIM OF THE HIGHEST TRAP OR TRAPPED FIXTURE BEING
 VENTED)
 12. THE HORIZONTAL DRY VENT CONNECTING TO GREASY WASTE
 AT THE THREE COMPARTMENT SINK IS PROHIBITED PER FBC PL
 905.3 (A DRY VENT CONNECTING TO A HORIZONTAL DRAIN
 SHALL CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL
 DRAIN PIPE) AND 905.4 (A DRY VENT SHALL RISE VERTICALLY
 TO NOT LESS THAN 6 INCHES (152 MM) ABOVE THE FLOOD
 LEVEL RIM OF THE HIGHEST TRAP OR TRAPPED FIXTURE BEING
 VENTED)
 13. PROVIDE SIZING OF THE GREASY WASTE COMPLYING WITH
 THE REQUIREMENTS OF FBC PL 915.2.2 AND TABLE 915.2.2.
 14. PROVIDE SIZING OF THE SANITARY BUILDING DRAIN
 COMPLYING WITH THE REQUIREMENTS OF FBC PL 710.1 AND
 TABLE 710.1(1).
 15. PROVIDE TRAP PRIMERS FOR FLOOR DRAINS AND TRENCH
 DRAINS PER FBC PL 1002.4.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 20020408 7000 OKEECHOBEE BLVD
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-05-22 Cont ID  
Sent By jpearson Date 2020-05-22 Time 09:23 Rev Time 0.00
Received By jpearson Date 2020-05-22 Time 09:23 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-05-01 Cont ID  
Sent By rmcphers Date 2020-05-01 Time 10:18 Rev Time 0.00
Received By rmcphers Date 2020-05-01 Time 10:18 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-03-30 Cont ID  
Sent By rmcphers Date 2020-03-30 Time 08:27 Rev Time 0.00
Received By rmcphers Date 2020-03-30 Time 08:27 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-02-19 Cont ID  
Sent By rmcphers Date 2020-02-19 Time 15:10 Rev Time 0.00
Received By rmcphers Date 2020-02-19 Time 15:10 Sent To  
Notes
***NONE***