Plan Review Details - Permit 20020383
Plan Review Stops For Permit 20020383
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-08-20 Cont ID  
Sent By rmcphers Date 2020-08-20 Time 08:51 Rev Time 0.00
Received By rmcphers Date 2020-08-20 Time 08:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-07-24 Cont ID  
Sent By rmcphers Date 2020-07-24 Time 09:36 Rev Time 0.00
Received By rmcphers Date 2020-07-24 Time 09:21 Sent To  
Notes
2020-07-24 09:27:09 
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-06-16 Cont ID  
Sent By rmcphers Date 2020-06-16 Time 07:37 Rev Time 0.00
Received By rmcphers Date 2020-06-15 Time 15:48 Sent To  
Notes
2020-06-15 16:01:25SFR ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN THE
 ROOFING PRODUCT APPROVAL (18-0919.07) - MAY NEED TO
 PROVIDE ADDITIONAL ATTACHMENT DETAILS FROM AN ARCHITECT
 OR ENGINEER FOR ROOF ZONES 2 AND 3 WHICH MAY REQUIRE A
 HIGHER WIND PRESSURE THAN THE MAXIMUM PRESSURE SHOWN
 FOR THE ROOFING SYSTEM CHOSEN IN THE PRODUCT APPROVAL -
 SEE THE PRODUCT APPROVAL GENERAL LIMITATION NUMBER 7.
 (SIGNED AND SEALED ENGINEERING DOCUMENTS WILL NEED TO
 BE ELECTRONICALLY SIGNED BY THE ARCHITECT OR ENGINEER
 TO BE USED IN ELECTRONIC PLAN REVIEW.
 2) PRODUCT APPROVAL FOR THE CASEMENT WINDOW
 (17-0614.12) REQUIRES SHUTTERS TO MEET IMPACT
 REQUIREMENTS - PLEASE PROVIDE THE COMPLETE MIAMI DADE
 OR FLORIDA STATE PRODUCT APPROVAL FOR THE SHUTTERS.
 3) DRAWINGS SHOULD SHOW THE REQUIRED ATTIC OR RAFTER
 SPACE VENTILATION REQUIREMENTS TO COMPLY WITH FBC
 R806.1 OR SHOW THE DESIGN FOR THE UNVENTED SPACE TO
 COMPLY WITH FBC R806.5
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-02-27 Cont ID  
Sent By rmcphers Date 2020-02-27 Time 15:30 Rev Time 0.00
Received By rmcphers Date 2020-02-27 Time 12:51 Sent To  
Notes
2020-02-27 15:29:53SFR ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED -
 1) PLEASE REMOVE THE PERGOLA FROM THE DRAWINGS OR NOTE
 ON THE DRAWINGS THAT THE PERGOLA WILL BE ON A SEPARATE
 PERMIT.
 2) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE NEW EXTERIOR WINDOWS AND
 DOORS. FBC WPB AMENDMENTS 107.2.1.1
 3) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE ROOF SHINGLES AND THE FLAT
 ROOFING SYSTEM TO BE USED. FBC WPB AMENDMENTS 107.2.1.1
 4) DRAWINGS SHOW SHINGLES TO BE INSTALLED ON THE LOW
 SLOPE ROOF. CANNOT HAVE SHINGLES ON A ROOF SLOPE LESS
 THAN 2 IN 12. FBC R905.2.2
 5) PLEASE SHOW THE HURRICANE STRAPPING AND CONNECTION
 FOR THE 2X12 JOIST TO DOUBLE 2X12 RIDGE BEAM AND THE
 GLULAM BEAM FOR THE COVERED PORCH. FBC WPB AMENDMENTS
 107
 6) DRAWING "S02" IS MISSING PER THE INDEX ON THE FRONT
 PAGE. (ONLY MISSING FROM 1 OF THE SETS)
 7) PLEASE SHOW THE REQUIRED ATTACHMENTS FOR THE HUSC
 412 BEAM BUCKET BRACKET TO THE EXISTING STRUCTURE AND
 THE BEAM. FBC WPB AMENDMENTS 107.2.1.1
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-07-24 Cont ID  
Sent By jleahy Date 2020-07-24 Time 13:20 Rev Time 0.00
Received By jleahy Date 2020-07-24 Time 13:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-06-19 Cont ID  
Sent By jpearson Date 2020-06-19 Time 11:07 Rev Time 0.00
Received By jpearson Date 2020-06-19 Time 08:03 Sent To  
Notes
2020-06-19 09:23:13CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR
 THE DESIGN. PROVIDE CORRECTION. FS 481.229; WPB FBC
 107.1, 107.2.1, 107.3.5.1.2 (SEE SIGNATURE COMMENTS.
 ALTHOUGH THE EXEMPTION APPLIES AND AN ARCHITECT OR
 ENGINEER IS NOT REQUIRED FOR THE PLANS, SOMEONE HAS TO
 TAKE RESPONSIBILITY AND SIGN EACH SHEET OF THE PLAN,
 THIS IS THE PERSON DESIGNING THE PLAN AS THE
 RESPONSIBLE PERSON. IF AN ARCHITECT OR ENGINEERING FIRM
 BLOCK STAMP IS ON THE PLAN, THEN IT MUST BE
 SIGNED/SEALED PER FLORIDA STATUTES.)
 2. PLAN SHOWS A TYPICAL RISER DIAGRAM. PROVIDE THE
 ACTUAL RISER DIAGRAM OF THE EXISTING SERVICE. SHOW ALL
 DETAILS OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD
 SERVICE, WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO
 ANY SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; WPB FBC 107.2.1 (RISER DIAGRAM QUOTES THE 2008
 NEC AS THE BASIS FOR DESIGN. THIS IS NOT THE CURRENT
 CODE. PROVIDE CORRECTION. SEE CURRENT CODES ABOVE.)
 3. CORRECTED, SEE NEW COMMENT BELOW.
 4. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE
 E3602.2 (LOAD CALCULATION IS NOT CODE COMPLIANT. SEE
 FBC 3602 FOR METHOD OF CALCULATION REQUIRED.)
 5. CORRECTED.
  
 NEW COMMENTS:
  
 6. PANEL SCHEDULE SHOWS A 100 AMP PANEL WITH 164 AMPS
 LOAD. RISER DIAGRAM ONLY SHOWS ONE 200 AMP PANEL, IS
 THERE ANOTHER PANEL? WHY IS THIS PANEL LABELED UNIT 3?
 PROVIDE CLARIFICATIONS AND/OR CORRECTIONS AS NEEDED.
 NEC 215.5, 230, 250.50, 250.94, 408.30; FBC RE E3706.1,
 E3608.1, E3609.3; WPB FBC 107.2.1
 7. PLAN SHOWS A NEW TANKLESS WATER HEATER WITH A LOAD
 OF 18,000 VA SUPPLIED BY #8 WIRE ON A 40 AMP BREAKER. A
 LOAD OF 18,000 VA WOULD DRAW 75 AMPS. PROVIDE CORRECTED
 WIRING AND OVERCURRENT PROTECTION FOR THIS WATER
 HEATER. NEC 240.4, 310.15(B)(16); FBC RE E3705.1
 8. ELECTRICAL PLAN DOES NOT SHOW THE NEW MINI-SPLIT
 A/C. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR
 SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE
 EQUIPMENT PER CODE. NEC 210.63; FBC RE E3901.12
 9. PLAN SHOWS A 15 AMP CIRCUIT FEEDING TWO NEW
 BATHROOMS. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT
 SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE
 OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS.
 PROVIDE CORRECTION. NEC 210.11(C)(3) , FBC RE E3703.4
 10. NOTE 19 REFERS TO THE 2011 NEC FOR AFCI
 REQUIREMENTS. THIS IS NOT THE CURRENT CODE AND THE
 REQUIREMENTS HAVE CHANGED. ALL BRANCH CIRCUITS THAT
 SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS, DINING
 ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902; FBC EX 607.1.1 OR 801.1,
 801.2, OR 901.2 AS APPLICABLE.
 11. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE
 SUITABLE FOR DAMP LOCATIONS. PROVIDE CORRECTION OR NOTE
 FOR COMPLIANCE. NEC 410.10(D); FBC RE E4003.11
 12. NOTE 20 STATES THAT RECEPTACLES SHALL BE TAMPER
 RESISTANT PER NEC 406.11 FROM THE 2011 NEC. THIS IS NOT
 THE CURRENT CODE AND THIS CODE SECTION DOES NOT APPLY
 TO TAMPER RESISTANT RECEPTACLES. PROVIDE CORRECTION.
 NEC 406.12; FBC RE E4002.14
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-09 Cont ID  
Sent By jpearson Date 2020-03-09 Time 12:20 Rev Time 0.00
Received By jpearson Date 2020-03-09 Time 07:43 Sent To  
Notes
2020-03-09 11:48:24CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR
 THE DESIGN. PROVIDE CORRECTION. FS 481.229; WPB FBC
 107.1, 107.2.1, 107.3.5.1.2
 2. PLAN SHOWS A TYPICAL RISER DIAGRAM. PROVIDE THE
 ACTUAL RISER DIAGRAM OF THE EXISTING SERVICE. SHOW ALL
 DETAILS OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD
 SERVICE, WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO
 ANY SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1,
 E3609.3; WPB FBC 107.2.1
 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
 4. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE
 E3602.2
 5. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING
 ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS
 NEW INSTALLATIONS, OR PROVIDE A NOTE REQUIRING
 COMPLIANCE. FBC RE R314.3, R315.1; WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-08-20 Cont ID  
Sent By rmcphers Date 2020-08-20 Time 08:52 Rev Time 0.00
Received By rmcphers Date 2020-07-30 Time 15:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-07-30 Cont ID  
Sent By cpuell Date 2020-07-30 Time 11:49 Rev Time 0.00
Received By cpuell Date 2020-07-08 Time 08:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-07-01 Time   Rev Time 0.00
Received By lmarchan Date 2020-06-04 Time 13:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-11 Cont ID  
Sent By lmarchan Date 2020-03-11 Time 07:45 Rev Time 0.00
Received By lmarchan Date 2020-02-10 Time 13:49 Sent To  
Notes
2020-02-11 13:49:08R07

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2020-08-21 Cont ID  
Sent By lmarchan Date 2020-08-21 Time 14:55 Rev Time 0.00
Received By lmarchan Date 2020-08-20 Time 10:23 Sent To  
Notes
2020-08-21 14:55:22NO IMPACT FEES DUE - SEE UPLOADED EMAIL. LEM
2020-08-20 10:24:09EMAILED IMPACT FEE OFFICE FOR REVIEW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-02-27 Cont ID  
Sent By rmcphers Date 2020-02-27 Time 15:37 Rev Time 0.00
Received By rmcphers Date 2020-02-27 Time 15:37 Sent To  
Notes
2020-02-27 15:37:44PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-07-20 Cont ID  
Sent By medwards Date 2020-07-20 Time 07:32 Rev Time 0.00
Received By medwards Date 2020-07-20 Time 07:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-06-12 Cont ID  
Sent By medwards Date 2020-06-12 Time 12:44 Rev Time 0.00
Received By medwards Date 2020-06-12 Time 10:28 Sent To  
Notes
2020-06-12 12:46:202ND REVIEW FBC-2017 MECHANICAL
 PERMIT-20020383
  
 CODES IN EFFECT:
  
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET E-01 SHOWS A WALL RUNNING ALL THE WAY ACROSS
 THE BACK OF THE ROOM CREATING A SMALL ROOM BEHIND. THE
 CCU-01 IS LOCATED INSIDE THIS ROOM. WHAT IS THIS ROOM?
 SHEET M-00 DOES NOT SHOW A RETURN DUCT WHICH WOULD MEAN
 THE RETURN IS COMING FROM THE MYSTERY ROOM. IS THIS
 ROOM CONDITIONED? PLEASE LABEL THIS ROOM AND SHOW THE
 RETURN PATH TO THE CCU-01. PLEASE BE CONSISTENT BETWEEN
 DRAWINGS. FBC FS 107.2.1
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-03-10 Cont ID  
Sent By medwards Date 2020-03-10 Time 17:33 Rev Time  
Received By medwards Date 2020-03-10 Time   Sent To  
Notes
2020-03-10 17:35:10PERMIT # 20020383
  
 MECHANICAL REVIEW
  
 CODES IN EFFECT:
  
 2017 EDITIONS OF:
 FBC RE = FLORIDA RESIDENTIAL CODE, 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION, 6TH
 EDITION
  
 MICHAEL EDWARDS
 MECHANICAL PLANS EXAMINER II
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6728
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
  
  
 1) PLEASE PROVIDE CALCULATIONS FROM ACCA MANUAL S, J
 AND D.
  
 FBC CHAPTER 1 ADMINISTRATION- 107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS -107.3.5.1.4 MECHANICAL;
 ALSO SEE FBC CE SECTION R403.7 PLEASE PROVIDE
 CALCULATIONS FROM ACCA MANUAL J.
  
 2) PROVIDE THE SPEC SHEETS FOR THE MITSUBISHI
 PUZ-A12NKA7.
  
 FBC CHAPTER 1 ADMINISTRATION- 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE
 SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL
 THAT IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
 SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. (SEE ALSO SECTION 107.3.5).
  
  
 3) PLEASE SHOW THE RETURN AIR PATH BACK TO THE CCU-01
 UNIT. RETURN AIR MUST NOT BE TAKEN FROM A CLOSET.
  
 M1602.2 RETURN AIR OPENINGS. (4) RETURN AIR SHALL NOT
 BE TAKEN FROM A CLOSET, BATHROOM, TOILET ROOM, KITCHEN,
 GARAGE, MECHANICAL ROOM, BOILER ROOM, FURNACE ROOM OR
 UNCONDITIONED ATTIC.
  
 4) PROVIDE DUCT SIZE FOR DUCT AT AIR DEVICE A-3.
  
 FBC CHAPTER 1 ADMINISTRATION- 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE
 SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL
 THAT IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
 SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC, AND THE
 TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE OR IN
 PART, NOR SHALL THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. (SEE ALSO SECTION 107.3.5).
  
  
 5) MECHANICAL DRAWINGS MUST BE SIGNED BY DESIGNER.
  
 1) . FBC CHAPTER 1 ADMINISTRATION- 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE
 SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL
 THAT IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
 SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. (SEE ALSO SECTION 107.3.5).
  
 6) PLEASE PROVIDE SPEC SHEETS FOR THE HOOD AND THE
 APPLIANCE GOING UNDER THIS HOOD THAT IS LOCATED ON THE
 PORCH.
  
 . FBC CHAPTER 1 ADMINISTRATION- 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE
 SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL
 THAT IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
 SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. (SEE ALSO SECTION 107.3.5).
  
 7) PLEASE SHOW THE AUXILIARY OR SECONDARY CONDENSATE
 DRAINAGE SYSTEM FOR THE CCU-01.
  
 M1411.3.1AUXILIARY AND SECONDARY DRAIN SYSTEMS.
 IN ADDITION TO THE REQUIREMENTS OF SECTION M1411.3, A
 SECONDARY DRAIN OR AUXILIARY DRAIN PAN SHALL BE
 REQUIRED FOR EACH COOLING OR EVAPORATOR COIL WHERE
 DAMAGE TO ANY BUILDING COMPONENTS WILL OCCUR AS A
 RESULT OF OVERFLOW FROM THE EQUIPMENT DRAIN PAN OR
 STOPPAGE IN THE CONDENSATE DRAIN PIPING. SUCH PIPING
 SHALL MAINTAIN A MINIMUM HORIZONTAL SLOPE IN THE
 DIRECTION OF DISCHARGE OF NOT LESS THAN 1/8 UNIT
 VERTICAL IN 12 UNITS HORIZONTAL (1-PERCENT SLOPE).
 DRAIN PIPING SHALL BE NOT LESS THAN 3/4-INCH (19 MM)
 NOMINAL PIPE SIZE. ONE OF THE FOLLOWING METHODS SHALL
 BE USED:
 1. 1.AN AUXILIARY DRAIN PAN WITH A SEPARATE DRAIN SHALL
 BE INSTALLED UNDER THE COILS ON WHICH CONDENSATION WILL
 OCCUR. THE AUXILIARY PAN DRAIN SHALL DISCHARGE TO A
 CONSPICUOUS POINT OF DISPOSAL TO ALERT OCCUPANTS IN THE
 EVENT OF A STOPPAGE OF THE PRIMARY DRAIN. THE PAN SHALL
 HAVE A MINIMUM DEPTH OF 1.5 INCHES (38 MM), SHALL BE
 NOT LESS THAN 3 INCHES (76 MM) LARGER THAN THE UNIT OR
 THE COIL DIMENSIONS IN WIDTH AND LENGTH AND SHALL BE
 CONSTRUCTED OF CORROSION-RESISTANT MATERIAL. GALVANIZED
 SHEET STEEL PANS SHALL HAVE A MINIMUM THICKNESS OF NOT
 LESS THAN 0.0236-INCH (0.6010 MM) (NO. 24 GAGE).
 NONMETALLIC PANS SHALL HAVE A MINIMUM THICKNESS OF NOT
 LESS THAN 0.0625 INCH (1.6 MM).
 2. 2.A SEPARATE OVERFLOW DRAIN LINE SHALL BE CONNECTED
 TO THE DRAIN PAN INSTALLED WITH THE EQUIPMENT. THIS
 OVERFLOW DRAIN SHALL DISCHARGE TO A CONSPICUOUS POINT
 OF DISPOSAL TO ALERT OCCUPANTS IN THE EVENT OF A
 STOPPAGE OF THE PRIMARY DRAIN. THE OVERFLOW DRAIN LINE
 SHALL CONNECT TO THE DRAIN PAN AT A HIGHER LEVEL THAN
 THE PRIMARY DRAIN CONNECTION.
 3. 3.AN AUXILIARY DRAIN PAN WITHOUT A SEPARATE DRAIN
 LINE SHALL BE INSTALLED UNDER THE COILS ON WHICH
 CONDENSATION WILL OCCUR. THIS PAN SHALL BE EQUIPPED
 WITH A WATER LEVEL DETECTION DEVICE CONFORMING TO UL
 508 THAT WILL SHUT OFF THE EQUIPMENT SERVED PRIOR TO
 OVERFLOW OF THE PAN. THE PAN SHALL BE EQUIPPED WITH A
 FITTING TO ALLOW FOR DRAINAGE. THE AUXILIARY DRAIN PAN
 SHALL BE CONSTRUCTED IN ACCORDANCE WITH ITEM 1 OF THIS
 SECTION.
 4. 4.A WATER LEVEL DETECTION DEVICE CONFORMING TO UL
 508 SHALL BE INSTALLED THAT WILL SHUT OFF THE EQUIPMENT
 SERVED IN THE EVENT THAT THE PRIMARY DRAIN IS BLOCKED.
 THE DEVICE SHALL BE INSTALLED IN THE PRIMARY DRAIN
 LINE, THE OVERFLOW DRAIN LINE OR THE EQUIPMENT-SUPPLIED
 DRAIN PAN, LOCATED AT A POINT HIGHER THAN THE PRIMARY
 DRAIN LINE CONNECTION AND BELOW THE OVERFLOW RIM OF
 SUCH PAN.
 M1411.3.1.1WATER-LEVEL MONITORING DEVICES.
 ON DOWN-FLOW UNITS AND OTHER COILS THAT DO NOT HAVE
 SECONDARY DRAIN OR PROVISIONS TO INSTALL A SECONDARY OR
 AUXILIARY DRAIN PAN, A WATER-LEVEL MONITORING DEVICE
 SHALL BE INSTALLED INSIDE THE PRIMARY DRAIN PAN. THIS
 DEVICE SHALL SHUT OFF THE EQUIPMENT SERVED IN THE EVENT
 THAT THE PRIMARY DRAIN BECOMES RESTRICTED. DEVICES
 SHALL NOT BE INSTALLED IN THE DRAIN LINE.
  
 8) PLEASE PROVIDE AN ENGINEER?S SEAL AND SIGNATURE ON
 THE CONDENSER MOUNTING DETAIN DESIGN.
  
 . FBC CHAPTER 1 ADMINISTRATION- 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE
 SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL
 THAT IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
 SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. (SEE ALSO SECTION 107.3.5).
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-07-13 Cont ID  
Sent By ccole Date 2020-07-13 Time 08:30 Rev Time 0.00
Received By ccole Date 2020-07-13 Time 08:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-07-01 Cont ID  
Sent By ccole Date 2020-07-01 Time 13:11 Rev Time 0.00
Received By ccole Date 2020-07-01 Time 11:51 Sent To  
Notes
2020-07-01 13:12:022ND REVIEW FBC-2017 RES. PLUMBING.
 PERMIT- 20020383
 7/1/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1.0: THE WATER CLOSETS REQUIRE 3" FIXTURE
 DRAINS PER SECTION 2712.1 FBC RES AND TABLE 709.1 FBC
 P. THE DRAWINGS ARE INDICATING 2" PLEASE CORRECT.
  
 2) P1.0: THE ECOSMART ECO 18 WATER HEATER WITH MAX 4.4
 GPM FLOW RATE MAY BE UNDERSIZED FOR THE REQUIRED GPM
 FLOW OF HOT WATER TO THE FIXTURES. VERIFY THAT SIZING
 WAS DONE ACCORDING TO MANUFACTURER'S SPECIFICATIONS-
 SECTION M2005.1 FBC RES.
  
 3) SIGNATURE OF CONTRACTOR OR DESIGN PROFESSIONAL IS
 REQUIRED ON THE PLUMBING PLANS- SECTION 107.2.1 WPB.
 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS AND ACCOMPANYING DATA SHALL
 BEAR THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-03-02 Cont ID  
Sent By lcrespo Date 2020-03-02 Time 15:55 Rev Time 0.00
Received By lcrespo Date 2020-03-02 Time 07:26 Sent To  
Notes
2020-03-02 15:56:1403/02/2020 PLUMBING 1ST REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF
 THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH
 FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA
 STATUTE 471. WPB AMENDMENTS TO THE FBC SEC. 107.1
 GENERAL.
  
 2. PLEASE SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ELECTRIC WATER HEATER
 EQUIPMENT TO VERIFY COMPLIANCE PER THE WPB AMENDMENTS
 TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 3. THE SECOND BATHROOM DOWN STREAM NEED TO BE ON A
 SEPARATE SYSTEM ON A BRANCH I HAVE NOTED ON ONE OF THE
 PLANS THE CORRECT WAY SO YOU CAN HAND WRITE IN THE
 SECOND SET OF PLANS PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. THERE ARE SHOWERS ON THE ISOMETRIC AND TUB ON THE
 FLAT, IF YOU ARE PUTTING SHOWERS PLEASE A DETAIL
 CONFORMING WITH 2017 FBC SECTION R2709.2 AND IS
 RECESSED IN CONCRETE PLEASE NOTE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM
 [email protected]
 561-805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status P Date 2020-08-20 Cont ID  
Sent By rmcphers Date 2020-08-20 Time 08:52 Rev Time 0.00
Received By rmcphers Date 2020-08-20 Time 08:52 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2020-07-24 Cont ID  
Sent By rmcphers Date 2020-07-24 Time 09:35 Rev Time 0.00
Received By rmcphers Date 2020-07-24 Time 09:35 Sent To  
Notes
2020-07-24 09:35:39SFR ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) THE HIGHLIGHTED ROOFING SYSTEM ON THE PROVIDED FLAT
 DECK PRODUCT APPROVAL HAS A MAXIMUM WIND PRESSURE OF
 (-52.5) - PLEASE PROVIDE ADDITIONAL SIGNED AND SEALED
 ATTACHMENT DETAILS FROM AN ARCHITECT OR ENGINEER FOR
 ROOF WIND ZONE 3 WHICH REQUIRES A HIGHER WIND PRESSURE
 THAN THE MAXIMUM PRESSURE SHOWN FOR THE ROOFING SYSTEM
 CHOSEN IN THE PRODUCT APPROVAL - SEE THE PRODUCT
 APPROVAL GENERAL LIMITATION NUMBER 7.
  
 FYI = SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO
 BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.
 DRAWINGS DO NOT SHOW IN "ADOBE READER" AS
 DIGITALLY/ELECTRONICALLY SIGNED. - OR - IF YOUR
 ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROP BOX) THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS ALONG
 WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE REASON
 FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY E MAILING [email protected]
 AND ASKING FOR THE FORM. (AT THIS TIME DROP BOX ITEMS
 MAY TAKE 2 TO 3 WEEKS TO PROCESS, TO SEND TO PLAN
 REVIEW - DUE TO LIMITED STAFF INSIDE THE BUILDING
 DEPT.)

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2020-06-16 Cont ID  
Sent By rmcphers Date 2020-06-16 Time 07:37 Rev Time 0.00
Received By rmcphers Date 2020-06-16 Time 07:37 Sent To  
Notes
2020-06-16 07:38:14SEE BUILDING PLAN REVIEW

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2020-02-27 Cont ID  
Sent By rmcphers Date 2020-02-27 Time 15:31 Rev Time 0.00
Received By rmcphers Date 2020-02-27 Time 15:31 Sent To  
Notes
2020-02-27 15:31:58SEE BUILDING COMMENTS

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-07-20 Cont ID  
Sent By medwards Date 2020-07-20 Time 07:56 Rev Time 0.00
Received By medwards Date 2020-07-20 Time 07:32 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-06-16 Cont ID  
Sent By rmcphers Date 2020-06-16 Time 07:38 Rev Time 0.00
Received By rmcphers Date 2020-06-16 Time 07:38 Sent To  
Notes
2020-06-19 09:45:15PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED (AND SEALED FOR DESIGN
 PROFESSIONALS) BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED OR SIGNED/SEALED
 PAPER SET MAY BE SUPPLIED TO THE BUILDING DEPARTMENT
 WHEN ALL TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
2020-06-16 07:39:04SEE BUILDING PLAN REVIEW

Review Stop Z ZONING
Rev No 3 Status P Date 2020-07-30 Cont ID  
Sent By awooten Date 2020-07-30 Time   Rev Time 0.00
Received By awooten Date 2020-07-30 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2020-06-12 Cont ID  
Sent By awooten Date 2020-06-12 Time   Rev Time 0.00
Received By awooten Date 2020-06-12 Time   Sent To  
Notes
2020-06-12 11:09:28******************************ZONING REVIEW
 FAILED*************************************
  
 RESPONSE LETTER MENTIONS A SURVEY, NO SURVEY ATTACHED.
 PLEASE PROVIDE A SURVEY FOR PROPERTY.
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By awooten Date 2020-02-20 Time   Rev Time  
Received By   Date 2020-02-20 Time   Sent To  
Notes
2020-02-20 13:02:01********************************ZONING REVIEW
 FAILED****************************
  
 THE REAR SETBACK FOR THE ADDITION IN THIS ZONING
 DISTRICT IS REQUIRED TO BE 10% OF THE LOT DEPTH. THE
 MINIMUM REAR SETBACK IS 10.9 FEET.
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]