| 2020-02-19 13:07:12 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20020370 |
| | ADD: 416 CLEMATIS ST. |
| | CONT: GM CONSTRUCTION |
| | TEL: 561-742-3200 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. FEB. 19TH/ 2020 |
| | ACTION: DENIED |
| | |
| | 1) DISCREPANCY IN PLANS SHEET A-3 DETAIL # 2 IS FOR A 1 |
| | HOUR FIRE RATED WALL. THIS DETAIL SHOWS A 20 FT. PLUS |
| | 25 GAUGE 3 5/8 INCH STEEL STUD WHEREAS THE STRUCTURAL |
| | SHEET S100 DETAIL # 6 SHOWS STRUCTURAL STEEL STUD |
| | 400S200-43 AND PLATFORM CONSTRUCTION WITH THE 2ND FLOOR |
| | FRAMING AND FLOOR SHEATHING. THIS PLAN DOES NOT SHOW |
| | THE 2ND FLOOR WALL OF THE STAIRWELL NOR A FIRE RATING |
| | OR ANY FIRE RATED DRYWALL. THE STRUCTURAL DETAIL ALSO |
| | INDICATES THERE TO BE A LAYER OF 5/8 INCH APA PLYWOOD |
| | TO BE APPLIED TO BOTH SIDES OF THE STRUCTURAL STEEL |
| | STUD CREATING THE STAIRWELL TO THE 2ND FLOOR. |
| | 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1 ADMINISTRATIVE CODE SECTION 107.2.1.2 |
| | ADDITIONAL INFORMATION IS REQUIRED. DISCREPANCY IN |
| | PLANS. |
| | 2017 FBC-B SECTION 1023.2. CONSTRUCTION. ENCLOSURES FOR |
| | INTERIOR EXIT STAIRWAYS SHALL BE CONSTRUCTED AS FIRE |
| | BARRIERS IN ACCORDANCE WITH SECTION 707 OF THE FBC-B. |
| | THE FIRE RESISTANCE RATING OF NOT LESS THAN 1 HOUR FOR |
| | A 2 STORY BUILDING. PLEASE PROVIDE THE UL FIRE RATING |
| | FOR THE ASSEMBLY INCLUDING THE 5/8 INCH PLYWOOD |
| | SUB-SHEATHING AND OR GYPSUM ASSOCIATION LISTING. |
| | |
| | 2) THE HEIGHT OF THE 2ND FLOOR IS NOT GIVEN NEITHER THE |
| | TOP ROUGH FRAMING HEIGHT, NOR FLOOR FINISH ON THE A1 |
| | SHEET, A2 SHEET, THE INSET STAIR DETAIL FOUND ON SHEET |
| | A1 REFERENCES SEE THE STRUCTURAL SHEET S100. THE |
| | STRUCTURAL SHEET S100 DOES NOT PROVIDE AT WHAT HEIGHT |
| | THE FINISH FLOOR IS OR THE TOP OF THE STEEL FLOOR |
| | JOIST. |
| | 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 3) SHEET A1 DETAIL FOR TYPICAL STAIR SECTION IS NOT |
| | DRAWN FOR THIS APPLICATION, THERE IS A MID-LANDING |
| | SHOWN IN THE TYPICAL DETAIL WHEREAS BOTH THE |
| | ARCHITECTURAL AND STRUCTURAL FLOOR PLAN DOES NOT SHOW A |
| | MID-LANDING AND EITHER A 90 DEGREE OR 180 DEGREE TURN |
| | AT THE MID-LANDING. THE SHEET A-1 STAIR DETAIL DOES NOT |
| | GIVE THE RISE NOR RUN FOR RISER AND TREAD (FBC-B |
| | 1011.5.2 RISER HEIGHT AND TREAD DEPTH) DOES THE PLAN |
| | STATE THE TREAD IS TO BE 2 INCH CONCRETE SLAB ON STEEL |
| | PAN WHEREAS THE SHEET S100 DETAIL # 6 INDICATES THE |
| | STAIR TREAD TO BE A 2X12, AGAIN DISCREPANCY IN PLANS. |
| | THE ARCHITECTURAL PLAN SHOWS A STEEL STAIR CARRIAGE |
| | WHEREAS THE STRUCTURAL PLAN DETAIL # 6 SHOWS THE 2X12 |
| | TREADS ANCHORED WITH 4X4 STEEL ANGLE SUPPORTS BENEATH |
| | THE TREAD ANCHORED INTO THE VERTICAL FRAMING MEMBERS, |
| | AGAIN DISCREPANCY BETWEEN THE 2 PLANS. |
| | |
| | 4A) SHEET A-1 THE FLOOR PLAN SHOWS BENEATH THE |
| | STAIRWELL A NEW AHU-2 UNIT. THE WALLS AROUND THE |
| | STAIRWELL ARE SHOWN AS WALL TYPE G A ONE-HOUR FIRE |
| | RATED WALL, BUT THERE IS NO MENTION AS TO THE FIRE |
| | RATING OF THE CEILING UNDER THE STAIRWELL. SEE 2017 |
| | FBC-B 1011.7.3 ENCLOSURES UNDER STAIRWAYS. |
| | |
| | 4B) SHEET M-1 SHOWS A AHU-2 AIR HANDLER UNDER THE FIRE |
| | RATED STAIRS, WHICH REQUIRES A 1 HOUR FIRE RATED WALLS |
| | (2017 FBC-B 1011.7.3) AND FIRE DAMPERS IN COMPLIANCE |
| | WITH (2017 FBC-B 717.3.2.1). |
| | |
| | 5) SHEET A-1 DOOR # 15 INSWING DOOR IT APPEARS THERE |
| | MAY NOT BE 18 INCHES ON THE LATCH SIDE OF THE DOOR. THE |
| | PLANS WILL NEED TO SHOW COMPLIANCE WITH THE 2017 |
| | ACCESS. CODE 404.2.4 MANEUVERING CLEARANCES. FIGURE |
| | 404.2.4.1(A). DOORS. MINIMUM MANEUVERING CLEARANCES AT |
| | DOORS AND GATES SHALL COMPLY WITH 404.2.4. MANEUVERING |
| | CLEARANCES SHALL EXTEND THE FULL WIDTH OF THE DOORWAY |
| | AND THE REQUIRED LATCH SIDE FOR SIDE CLEARANCE. |
| | |
| | 6A) SHEET A-1 IN LAB ROOM 114 THERE IS A DETAIL 2/A-2. |
| | THE LAB SINK IS AT 36 INCHES IN HEIGHT. PLEASE REVIEW |
| | THE 2017 FBC-ACCESSIBILITY CODE CHARGING SECTION 212.3. |
| | SINKS. WHERE SINKS ARE PROVIDED, AT LEAST 5 PERCENT, |
| | BUT NOT FEWER THAN ONE, OF EACH TYPE PROVIDED IN EACH |
| | ACCESSIBLE ROOM OR SPACE SHALL COMPLY WITH 606. |
| | |
| | 6B) 2017 FBC-ACCESSIBILITY CODE 606.2 CLEAR FLOOR |
| | SPACE. A CLEAR FLOOR SPACE COMPLYING WITH 305, |
| | POSITIONED FOR A FORWARD APPROACH, AND KNEE AND TOE |
| | CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED. |
| | EXCEPTIONS: |
| | 1.A PARALLEL APPROACH COMPLYING WITH 305 SHALL BE |
| | PERMITTED TO A KITCHEN SINK, IN A SPACE WHERE A COOK |
| | TOP OR CONVENTIONAL RANGE IS NOT PROVIDED, AND TO WET |
| | BARS. |
| | |
| | 6C) 2017 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT. |
| | LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT |
| | OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 6D) 2017 FBC-ACCESSIBILITY CODE 606.4 FAUCETS. CONTROLS |
| | FOR FAUCETS SHALL COMPLY WITH 309. HAND-OPERATED |
| | METERING FAUCETS SHALL REMAIN OPEN FOR 10 SECONDS |
| | MINIMUM. |
| | |
| | 6E) 2017 FBC-ACCESSIBILITY CODE 606.5 EXPOSED PIPES AND |
| | SURFACES. WATER SUPPLY AND DRAIN PIPES UNDER LAVATORIES |
| | AND SINKS SHALL BE INSULATED OR OTHERWISE CONFIGURED TO |
| | PROTECT AGAINST CONTACT. THERE SHALL BE NO SHARP OR |
| | ABRASIVE SURFACES UNDER LAVATORIES AND SINKS. |
| | |
| | 7) SHEET A-1 INDICATES THERE WILL BE AN EXCHANGE OF |
| | DRINKING FOUNTAINS A SINGLE FOUNTAIN FOR A HIGH/ LOW |
| | ADA DRINKING FOUNTAIN. THERE IS NO SECTION OR DETAIL |
| | THROUGH THIS AREA NOR MENTION OF COMPLIANCE WITH THE |
| | 2017 FBC-ACCESSIBILITY CODE FOR PROTRUDING OBJECTS SEE |
| | THE ACCESS. CODE 307.2. THE CONCERN IS WITH THE HIGH |
| | SIDE DRINKING FOUNTAIN, THE BOTTOM OF THE DRINKING |
| | FOUNTAIN MAYBE HIGHER THAN THE LEADING EDGE A MAXIMUM |
| | ALLOWABLE 27 INCHES FROM FINISH FLOOR. SEE FIGURE |
| | 307.2. |
| | |
| | 8) SHEET A1 AND A2 SHOW DIFFERENT FIRE AREAS. SHEET A-1 |
| | SHOWS A MERCANTILE OCCUPANCY ON THE 1ST FLOOR WHEREAS |
| | THE 2ND FLOOR SHOWS A PROPOSED BUSINESS OCCUPANCY. |
| | SHEET A-3 DETAIL # 1 SHOWS THE FLOOR CEILING ASSEMBLY |
| | WITHOUT ANY HORIZONTAL FIRE BARRIER AS REQUIRED BY THE |
| | 2017 FBC-B TABLE 707.3.10. THE TABLE INDICATES FOR |
| | MERCANTILE/ BUSINESS A MIXED OCCUPANCY A 2 HOUR FIRE |
| | BARRIER WOULD BE REQUIRED. |
| | |
| | 8A) IN THIS SET OF PLANS 1ST REVIEW THERE ARE NO |
| | REFLECTIVE CEILING PLANS. 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATIVE CODE SECTION: |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE |
| | EXAMINATION OF THE DOCUMENTS BY |
| | THE BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING |
| | MINIMUM CRITERIA AND DOCUMENTS: A FLOOR PLAN; |
| | REFLECTIVE CEILING PLAN, FLOOR CEILING PLAN,? |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | (8) FLOOR SYSTEMS |
| | |
| | 8B) THE M-1 MECHANICAL PLAN SHOWS THE 1ST FLOOR TRUNK |
| | LINES THAT RUN 90 DEGREES TO THE STEEL FLOOR JOIST, ARE |
| | THESE TRUNK LINES BELOW THE FIRE RATED 1ST FLOOR |
| | CEILING? THERE ARE NO CUT SECTIONS THROUGH THE BUILDING |
| | SHOWING THE LOCATION OF THIS SYSTEM. IF THE A/C TRUNK |
| | LINES ARE ABOVE THE REQUIRED 2 HOUR FIRE RATED CEILING |
| | THEN ALL PENETRATIONS OF THE RATED CEILING WILL NEED |
| | CEILING RADIATE DAMPERS. 2017 FBC-B 717.3.3.4. |
| | |
| | 8C) THE SAME SITUATION OCCURS IN THE 1ST FLOOR CEILING |
| | OF NOVEAU HEALTH AND WELLNESS THE ELECTRICAL SHEET E-2 |
| | SHOWS 6 INCH DOWN LIGHTS PENETRATING THE 2 HOUR FIRE |
| | RATED CEILING, PLEASE SHOW HOW COMPLIANCE WILL BE MET |
| | FOR SECTION FBC-B 714.4. |
| | |
| | 9) NOTE NO ACTION REQUIRED. COMPONENTS AND CLADDING |
| | PRESSURES FOR WALL ZONES 4 & 5 IN VASD ARE GOOD. |
| | |
| | 10) COMPONENTS AND CLADDING REQUIRES COMPLIANCE WITH |
| | 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS, |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 11) IDENTIFY GLAZING/ MULLIONS. THE SUBMITTED PRODUCT |
| | APPROVALS THE ELEMENTS LISTED BELOW ARE NOT IDENTIFIED. |
| | PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE |
| | SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION |
| | TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH |
| | GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, |
| | TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED |
| | OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND |
| | ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B |
| | 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S |
| | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 12) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 13) THE ROOF TOP A/C STAND PRODUCT APPROVAL A |
| | MIAMI-DADE NOA # 17-1218.02 WAS SUBMITTED, NOT REVIEWED |
| | BY THE DESIGNER OF RECORD. PLEASE IDENTIFY THE |
| | FOLLOWING REQUIREMENTS CALCULATING THE AREA (SIDE VIEW) |
| | OF THE ROOF TOP COMPRESSORS, CONFIGURATION ON STAND, |
| | THE MEAN ROOF HEIGHT OF THE STAND AND COMPRESSORS, |
| | WEIGHT, CIRCLED THE DESIGN PARAMETERS IN THE TABLES, |
| | ANCHORS AND UPLIFT VERSES MOMENT FOR THE UNIT TO THE |
| | STAND AND THE STAND TO THE ROOF. THE PRODUCT APPROVAL |
| | IS TO BE REVIEWED BY THE DESIGNER OF RECORD, APPROVED |
| | BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. |
| | |
| | 14) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS (COMPONENT & CLADDING |
| | PRODUCT APPROVALS) SHALL HAVE THE PRIOR APPROVAL OF THE |
| | BUILDING OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL |
| | IN RESPONSIBLE CHARGE SHALL LIST THE DEFERRED |
| | SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY |
| | THE BUILDING OFFICIAL. |
| | |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 15) SHEET S-100: |
| | PLAN ORIENTATION TO NORTH. THE LEFT SIDE OF THE PLAN |
| | FRONT OF BUILDING IS NORTH, TOP OF PLAN IS EAST, THE |
| | RIGHT HAND SIDE OF THE PLAN IS SOUTH AND THE BOTTOM OF |
| | THE PLAN IS WEST. IN THE |
| | |
| | 15A) SHEET S-100 INDICATES COLUMN TYPE C-1. SECTION 7 |
| | SHOWS THE REQUIREMENT TO WELD BOTH TOP AND BOTTOM |
| | PLATES TO THE HSS 4X4X ? INCH STEEL COLUMN. THERE IS A |
| | SECOND DETAIL B THAT REQUIRES A BUILT UP BEAM TO BE |
| | WELDED TO THE COLUMN. THERE IS NO WELDING MARKINGS |
| | INDICATING THE TYPE OF WELD, THICKNESS OF WELD, AND |
| | LENGTH OF WELDS. 2017 FBC-B 2204.1. |
| | |
| | 15B) WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS |
| | REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS & |
| | WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN |
| | ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF |
| | INSPECTION. IN ACCORDANCE WITH THE AMERICAN WELDING |
| | SOCIETY. |
| | 2017 FBC-B 2204.1 WELDING. AMERICAN WELDING SOCIETY AWS |
| | B2.1 SPECIFICATIONS FOR WELDING PROCEDURES AND |
| | PERFORMANCE QUALIFICATIONS. WELDS WILL NEED TO BE |
| | REVIEWED BY AN INDEPENDENT 3RD PARTY AGENCY. |
| | 2017 FBC-B 2204.2 BOLTING. |
| | IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS |
| | FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING |
| | INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU. |
| | |
| | 15C) AS STATED IN COMMENT # 2 THERE IS NO HEIGHT GIVEN |
| | FOR THE TOP OF THE 2ND FLOOR, FLOOR JOIST OR THE HEIGHT |
| | OF THE FINISH FLOOR. THERE ARE DETAILS 1-7, B & C BUT |
| | NONE OF THESE DETAILS PROVIDE THE 2ND FLOOR FINISH |
| | FLOOR OR TOP OF JOIST ELEVATION. THIS WILL BE CRITICAL |
| | TO BE ABLE TO DETERMINE THE PROPOSED HEIGHTS OF THE |
| | STEEL STUD LOAD BEARING WALLS AS WE LL AS THE HEIGHTS |
| | OF THE C1 COLUMN TYPES. 107.2.1.2 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 15D) IN THE DETAIL B THERE IS A JOIST THAT APPEARS TO |
| | RUN NORTH TO SOUTH AND THE JOIST ATTACHES TO THE EMBED |
| | PLATE AT 16 AND THE OTHER END TO THE COLUMN C1. THIS |
| | SITUATION IT WOULD APPEAR HAPPENS TWICE, AT EACH OF THE |
| | C-1 COLUMNS. THERE IS NO JOIST SIZE AT THE DETAIL B NOR |
| | ON THE JOIST LAYOUT PLAN. THE 2ND ISSUE WITH THIS |
| | DETAIL THERE IS NO CONNECTION INFORMATION, IS THE |
| | CONNECTION A WELD, BOLT AND OR SELF DRILLING SCREW? |
| | 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 15E) QUESTION, AS TO WHAT TYPE OF FRAMING IS OVER THE |
| | NORTH STOREFRONT WINDOW/ DOOR SYSTEM, IS THERE JUST A |
| | SINGLE FJ3 CEILING JOIST OR IS THERE A BOX BEAM |
| | (LINTEL) TO HELP TRANSFER THE WIND LOADS THAT ARE BEING |
| | TRANSFERRED INTO THE FRAMING MEMBER ABOVE, PART OF THE |
| | MWFRS (MAIN WIND FORCE RESISTING SYSTEM). THE NOTE IN |
| | DETAIL MAKES IT SOUND AS IF THE BEAM AND COLUMN ARE TO |
| | BE WELDED TOGETHER? 107.2.1.2 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 15F) IN DETAIL C THE TOP OF THE CEILING JOIST IS AT |
| | ELEVATION 8 FEET 9 ? INCHES, THE STRUCTURAL FRAMING |
| | MEMBER IS 8 INCHES IN HEIGHT, BOTTOM OF JOIST IS 8 FEET |
| | 1 ? ABOVE THE FINISH FLOOR. THE PLAN CALLS OUT FOR THE |
| | ATTACHMENT OF 5/8 INCH THICK PLYWOOD AND THEN AND THEN |
| | STUCCO. THERE IS NO MENTION IN EITHER THE ARCHITECTS |
| | PLAN NOR THE SHEET S-100 THE REQUIREMENTS FOR |
| | PROTECTING OF THE PLYWOOD (WATER-RESISTIVE BARRIER |
| | FBC-B 2510.6), NOR THE LATHING AND FURRING FOR WIRE |
| | LATH 2510.3 AND ASTM C 1063 REQUIREMENTS. |
| | |
| | 15G) THE SHEET S-100 IS SILENT AS TO THE VERTICAL |
| | FRAMING MEMBERS, MULLIONS FOR THE WINDOW WALL SYSTEM |
| | AND EXTERIOR DOORS. WHICH DESIGN PROFESSIONAL IS GOING |
| | TO TAKE THE RESPONSIBILITY FOR REVIEWING THE COMPONENTS |
| | AND CLADDING THAT ARE GOING TO BE ANCHORED TO THE NEW |
| | STEEL FRAMING MEMBERS? THE STRUCTURAL ENGINEER OR THE |
| | DESIGNER OF RECORD? |
| | W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 16) IMPACT FEES- PAPER SUBMITTALS. PLANS REQUIRE REVIEW |
| | BY THE PBC IMPACT FEE OFFICE. CALL (561) 233-5025. UPON |
| | APPROVAL, YOU MAY CHECK OUT ONE PLAN SET AND TAKE TO |
| | THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED AND |
| | WITH A COPY OF THE RECEIPT AS APPLICABLE. PLEASE |
| | PROVIDE THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO |
| | THE PBC IMPACT FEE OFFICE. THE FORM CAN BE FOUND AT: |
| | HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPAC |
| | TFEES/FORMS/QUESTIONNAIRE.PDF |
| | |
| | 17) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |