Plan Review Details - Permit 20020362
Plan Review Stops For Permit 20020362
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2020-02-20 Cont ID  
Sent By rmcphers Date 2020-02-20 Time 12:00 Rev Time 0.00
Received By rmcphers Date 2020-02-20 Time 12:00 Sent To  
Notes
2020-02-20 12:01:33NOT REQUIRED - EXISTING SHELL BUILD OUT

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-05-11 Cont ID  
Sent By rmcphers Date 2020-05-11 Time 14:24 Rev Time 0.00
Received By rmcphers Date 2020-05-11 Time 14:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-04-06 Cont ID  
Sent By rmcphers Date 2020-04-06 Time 14:05 Rev Time 0.00
Received By rmcphers Date 2020-04-06 Time 13:55 Sent To  
Notes
2020-04-06 13:58:00BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) DRAWING S101 SHOWS WIND SPEED AS 169MPH - WIND SPEED
 SHOULD BE 170MPH
 2) DRAWING A1.1 = THE OCCUPANT LOAD SHOULD BE SHOWN AS
 "EXERCISE ROOM" - 1 PERSON PER 50 SQ.FT.GROSS - SEE FBC
 TABLE 1004.1.2
 3) STRUCTURAL DRAWINGS DO NOT SHOW AS ELECTRONICALLY
 SIGNED IN "ADOBE".
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-02-20 Cont ID  
Sent By rmcphers Date 2020-02-20 Time 12:00 Rev Time 0.00
Received By rmcphers Date 2020-02-19 Time 16:21 Sent To  
Notes
2020-02-20 11:58:58BUILD OUT -
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED -
 1) THE OCCUPANCY CLASSIFICATION SHOULD BE "B" PER FBC
 303.1.1
 2) PLEASE PROVIDE COMPLETE COPIES OF THE MIAMI DADE OR
 FLORIDA STATE PRODUCT APPROVALS FOR THE NEWLY INSTALLED
 STORE FRONT GLAZING, DOORS AND LOUVERS - (FBC EXISTING
 BUILDING 702.6) FBC BUILDING 1609.1.2 AND 1609.1.2.1
 3) PLEASE SHOW THE WIND DESIGN CRITERIA AND COMPONENT
 (WINDOW/DOOR) PRESSURES REQUIRED. FBC 1603.1.4
 4) PLEASE SHOW THE EXISTING EXIT DOOR LOCKS AND LATCHES
 TO COMPLY WITH FBC 1010.1.9.3 AND ANY REQUIRED DOOR
 LOCKING SIGNAGE TO COMPLY WITH FBC 1010.1.9.3 (2.2)
 5) PLEASE SHOW THE WALL AND CEILING INSULATION R VALUE
 AND TYPE TO MEET OR EXCEED THE R VALUE SHOWN ON THE
 ENERGY CALCS. (ENERGY CALCS. NOT YET SUPPLIED).
 6) ALL DRAWINGS IN "PROJECT DOX" NEED TO BE
 ELECTRONICALLY SIGNED AND SEALED.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-05-27 Cont ID  
Sent By jleahy Date 2020-05-27 Time 11:08 Rev Time 0.00
Received By jleahy Date 2020-05-27 Time 11:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-04-07 Cont ID  
Sent By jpearson Date 2020-04-07 Time 12:12 Rev Time 0.00
Received By jpearson Date 2020-04-07 Time 07:54 Sent To  
Notes
2020-04-07 07:55:05JAKE LEAHY REVIEWING.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-03-03 Cont ID  
Sent By jleahy Date 2020-03-03 Time 08:08 Rev Time 0.00
Received By jleahy Date 2020-03-03 Time 08:08 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2020-05-01 Cont ID  
Sent By pleduc Date 2020-05-01 Time   Rev Time 0.00
Received By pleduc Date 2020-05-01 Time 09:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-04-06 Cont ID  
Sent By pleduc Date 2020-04-06 Time   Rev Time 0.00
Received By pleduc Date 2020-04-06 Time 09:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-02-18 Cont ID  
Sent By pleduc Date 2020-02-18 Time   Rev Time 0.00
Received By pleduc Date 2020-02-14 Time 15:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-05-27 Cont ID  
Sent By jleahy Date 2020-05-27 Time 11:18 Rev Time 0.00
Received By jleahy Date 2020-05-13 Time 13:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-05-12 Cont ID  
Sent By jpearson Date 2020-05-12 Time 09:05 Rev Time 0.00
Received By jpearson Date 2020-04-30 Time 10:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-04-14 Cont ID  
Sent By lmarchan Date 2020-04-14 Time 16:58 Rev Time 0.00
Received By lmarchan Date 2020-04-03 Time 09:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-31 Cont ID  
Sent By shill Date 2020-03-31 Time 09:08 Rev Time 0.00
Received By lmarchan Date 2020-02-13 Time 15:49 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2020-03-31 Cont ID  
Sent By rmcphers Date 2020-03-31 Time 10:28 Rev Time 0.00
Received By rmcphers Date 2020-03-31 Time 10:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2020-05-21 Cont ID  
Sent By medwards Date 2020-05-21 Time 10:38 Rev Time 0.00
Received By medwards Date 2020-05-21 Time 14:05 Sent To  
Notes
2020-05-21 14:06:32DESIGNER CALLED AND WE WALKED THROUGH EACH COMMENT AND
 DRAWING, PROJECT IS APPROVED.
2020-05-21 10:39:22PLEASE RESPOND TO THE 2ND CYCLE REVIEWER'S COMMENTS.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-05-21 Cont ID  
Sent By medwards Date 2020-05-04 Time 10:57 Rev Time 0.00
Received By medwards Date 2020-05-21 Time 13:46 Sent To  
Notes
2020-05-21 13:53:15DESIGNER CALLED AND DISCUSSED THE ISSUES, WE WENT
 THROUGH THE PLANS TOGETHER AND ALL THE CORRECTIONS WERE
 MADE. THE MECHANICAL PLANS ARE APPROVED.
2020-05-04 10:58:143RD REVIEW FBC-2017 MECHANICAL
 PERMIT- 20020362
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SEE THE 2ND REVIEWERS COMMENTS BELOW: THIS
 DOES NOT APPEAR TO HAVE BEEN CORRECTED.
  
 6) M802: THE NARRATIVE RESPONSE REFERENCES STRUCTURAL
 DRAIWNGS FOR RTU INSTALLATION DETAILS, HOWEVER NONE ARE
 PROVIDED. THE 1ST REVIEW COMMENTS REMANINS- PROVIDE
 ENGINEERED DETAILS FOR ANCHORING THE NEW CONDENSERS-
 SECTION 301.15 FBC M. PLEASE NOTE THAT ENGINEERING AND
 ITEMS LISTED BELOW MAY BE DEFERRED SUIBMITTALS BY
 REQUEST.
  
 2) NOTE 1 OF PREVIOUS REVIEW WAS NOT ADDRESSED IN THE
 SUPPORTING FILES ENERGY CALCULATIONS V2 PAGES 22-24.
 PLEASE CORRECT THIS FOR THE NEXT REVIEW. FBC EC
 C403.2.1
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-04-08 Cont ID  
Sent By ccole Date 2020-04-08 Time 11:30 Rev Time 0.00
Received By ccole Date 2020-04-08 Time   Sent To  
Notes
2020-04-08 11:46:531ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20020362
 4/8/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE AC COOLING AND HEATING CALCULATIONS FOR AHU-1-1
 ARE INDICATING MIAMI AS THE PROJECT LOCATION. PLEASE
 CLARIFY WHY THE COOLING LOADS ARE BEING DETERMINED IN
 NOVEMBER AND THE HEATING LOADS IN MAY. WHY WOULDN'T
 THESE LOADS BE CALCULATED DURING PEAK TIMES- SECTION
 C403.2.1 FBC EC.
  
 2) SHEET M001: NO CHANGES WERE MADE TO THE DESIGN
 CONDITIONS INFO ON M0001. THE 1ST REVIEW COMMENT
 REMAINS- DESIGN CONDITIONS LISTED ARE INCORRECT. A)
 WEST PALM BEACH SUMMER OUTDOOR DRY BULB IS 91, WINTER
 DRY BULB IS 45. B) OCCUPIED HEATING- 72. REFER TO TABLE
 D101 FBC- 2017 PLUMBING WHICH IS BASED ON ASHRAE 183.
 .
 6) M802: THE NARRATIVE RESPONSE REFERENCES STRUCTURAL
 DRAIWNGS FOR RTU INSTALLATION DETAILS, HOWEVER NONE ARE
 PROVIDED. THE 1ST REVIEW COMMENTS REMANINS- PROVIDE
 ENGINEERED DETAILS FOR ANCHORING THE NEW CONDENSERS-
 SECTION 301.15 FBC M. PLEASE NOTE THAT ENGINEERING AND
 ITEMS LISTED BELOW MAY BE DEFERRED SUIBMITTALS BY
 REQUEST.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-02-26 Cont ID  
Sent By ccole Date 2020-02-26 Time 07:57 Rev Time 0.00
Received By ccole Date 2020-02-25 Time 17:13 Sent To  
Notes
2020-02-26 08:38:041ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20020362
 2/26/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW SYSTEMS IN ACCORDANCE WITH SECTION C403.2.1 FBC EC.
  
 2) REFER TO SECTION 809.2 FBC EX AND PROVIDE MINIMUM
 VENTILATION CALCULATIONS FOR ALL ROOMS AND SPACES PER
 TABLE 403.3.1.1 FBC ML. PROVIDE A SCHEDULE THAT
 INDICATES THE REQUIRED AND PROVIDED CFMS OF OUTDOOR
 AIR.
  
 3) SHEET M001: DESIGN CONDITONS LISTED ARE INCORRECT.
 A) WEST PALM BEACH SUMMER OUTDOOR DRY BULB IS 91,
 WINTER DRY BULB IS 45. B) OCCUPIED HEATING- 72. REFER
 TO TABLE D101 FBC- 2017 PLUMBING WHICH IS BASED ON
 ASHRAE 183.
  
 4) M201: SHOW THE REQUIRED CLEARANCES FOR THE O/A
 INTAKE- SECTION 401.4 FBC M.
  
 5) M002: CORRECT NOTE #34 SPECIFYING FLEX DUCT LONG
 LENGTH TO BE 6'. FLEX DUCTS SHALL BE SUPPORTED AT 5'
 INTERVALS PER MANUFACTURER'S RECOMMENDATIONS.
  
 6) M802: PROVIDE ENGINEERED DETAILS FOR ANCHORING THE
 NEW CONDENSERS- SECTION 301.15 FBC M.
  
 7) SUBMITTALS: A) MIAMI-DADE NOA OF FL. PRODUCT
 APPROVAL FOR THE O/A LOUVER. B) DUCT SMOKE DETECTOR. C)
 SPACE SENSORS FOR AC CONTROLS OPERATION.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-05-12 Cont ID  
Sent By jpearson Date 2020-05-12 Time 09:03 Rev Time 0.00
Received By jpearson Date 2020-05-12 Time 09:03 Sent To  
Notes
2020-05-12 09:02:5520020362 591 EVERNIA ST
  
  
 PLUMBING COMMENTS: APPROVED
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE
  
 20020362 591 EVERNIA ST
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-04-08 Cont ID  
Sent By jpearson Date 2020-04-08 Time 06:41 Rev Time 0.00
Received By jpearson Date 2020-04-07 Time 14:34 Sent To  
Notes
2020-04-07 14:34:06REVIEW BY JERRY SMITH:
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 20020362 591 EVERNIA ST
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
 PLEASE SEE MARKED UP PLAN SHEETS A3.1, P001 AND P601.
 1. SHEET A3.1: PROVIDE NOTE; ?MEN?S BATHROOM ELEV. RM.
 #108-SIMILAR TO WOMEN?S BATHROOM ELEV. RM. #109
 ENLARGED DETAILS?
 2. REGARDING ADA CTLS/SH-2: PLAN SHEET A301 INDICATES
 TWO CONTROL VALVES. WHAT IS THE PURPOSE OF THE CONTROL
 VALVE ADJACENT TO THE EMTRANCE? ADDITIONALLY, HOW IS
 THE ADA CONTROL VALVE ON THE SIDE WALL PLUMBED? PLAN
 SHEET P601 WATER RISER DOES NOT ADDRESS. PER WPB FBC
 107.2.1, CLARIFY. ADDITIONALLY, FIXTURE SCHEDULE ON
 P001 DOES NOT ADDRESS. AGAIN, CLARIFY.
 3. PROVIDE NOTE; PER FBC ACC 608.5.3, IN ALTERNATE
 ROLL-IN TYPE SHOWER COMPARTMENTS, THE CONTROLS,
 FAUCETS, AND SHOWER SPRAY UNIT SHALL BE LOCATED ABOVE
 THE GRAB BAR, BUT NO HIGHER THAN 48 INCHES (1220 MM)
 ABOVE THE SHOWER FLOOR. WHERE A SEAT IS PROVIDED, THE
 CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT SHALL BE
 LOCATED ON THE SIDE WALL ADJACENT TO THE SEAT 27 INCHES
 (685 MM) MAXIMUM FROM THE SIDE WALL BEHIND THE SEAT OR
 SHALL BE LOCATED ON THE BACK WALL OPPOSITE THE SEAT 15
 INCHES (380 MM) MAXIMUM, LEFT OR RIGHT, OF THE
 CENTERLINE OF THE SEAT. WHERE A SEAT IS NOT PROVIDED,
 THE CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT SHALL BE
 INSTALLED ON THE SIDE WALL FARTHEST FROM THE
 COMPARTMENT ENTRY.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
 ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE
 DESIGNER IN ACCORDANCE WITH FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-246-0882 MOBILE

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-03-19 Cont ID  
Sent By ccole Date 2020-03-19 Time 18:52 Rev Time 0.00
Received By ccole Date 2020-03-17 Time 16:46 Sent To  
Notes
2020-03-19 18:52:531ST REVIEW FBC-2017 PLUMBING
 PERMIT #20020362
 3/19/20
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH EDITION
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A1.1 & A3.1: THE PLANS SHALL BE DESIGNED IN
 ACCORDANCE WITH THE FBC PLUMBING AND ACCESSIBILITY-
 2017 SIXTH EDITIONS. PLEASE PROVIDE COMPLETE CODE DATA
 ON THE PLANS- SECTION 107.2.1WPB.
  
 2) SHEET A3.1: ENLARGED BATHROOM DETAILS ARE PROVIDED
 FOR WOMEN BUT NOT MEN- SECTION 213.2 FBC ACC.
  
 3) A3.1: PROVIDE THE CLEAR FLOOR SPACE DIMENSIONS AS
 SHOWN ON THE DRAWINGS FOR THE WATER CLOSET- SECTION
 604.3, AND THE SPACE BEYOND THE ARC OF THE DOOR-
 SECTION 603.2.3 (2) FBC ACC.
  
 4) A3.1 DETAIL 02: SHOW THE MINIMUM LENGTH OF THE REAR
 WALL GRAB BAR AND MINIMUM LENGTH EXTENSIONS ON EACH
 SIDE OF THE CENTERLINE- SECTION 604.5.2 FBC ACC.
  
 5) A3.1 DETAIL 03: SHOW THE MINIMUM 42" LENGTH OF THE
 SIDE WALL GRAB BAR, AND THE MINIMUM 54" REQUIRED
 EXTENSION FROM THE REAR WALL- SECTION 604.5.1 FBC ACC.
  
 6) A3.1 DETAIL 03: THE MEASUREMENT FROM THE FRONT OF
 THE WATER CLOSET TO THE CENTERLINE OF THE TOILET PAPER
 DISPENSER SHALL BE 7 INCHES MINIMUM AND 9 INCHES
 MAXIMUM- SECTION 604.7 FBC ACC.
  
 7) A3.1 & P401: SHOW THE LOCATIONS OF THE SHOWER
 CONTROLS- SECTION 608.5.3 FBC ACC.
  
 8) A3.1: PLEASE SHOW THE 6' MAXIMUM SPACE FROM ADJACENT
 WALLS OF THE SHOWER TO THE GRAB BARS- SECTION 608.3.3
 FBC ACC.
  
 9) A3.1 & P001: VERIFY THE SHOWER SPRAY UNIT HAS A
 MINIMUM 59" LONG HOSE, CAN BE USED BOTH AS A FIXED
 POSITION SHOWER HEAD AND AS A HAND-HELD SHOWER, AND HAS
 AN ON/OFF CONTROL WITH A NON-POSITIVE SHUT-OFF- SECTION
 608.6 FBC ACC.
  
 10) A3.1: SHOW THE HEIGHT OF THE SHOWER ENTRY
 THRESHOLD- SECTION 608.7 FBC ACC. PLEASE NOTE MAXIMUM
 1/2" ALLOWED.
  
 11) A3.1: PROVIDE ENLARGED DRINKING FOUNTAIN DETAILS
 SHOWING THE REQUIRED CLEAR FLOOR SPACE, SPOUT HEIGHT,
 AND SPOUT LOCATION- SEE SECTIONS 602.2, 602.4, AND
 602.5 FBC ACC.
  
 12) P001: PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE
 EWH AND SHOW COMPLIANCE WITH THE MINIMUM PERFORMANCE
 CRITERIA LISTED IN TABLE C404.2 FBC EC.
  
 13) P001: VERIFY THE CIRCULATION PUMP HAS CONTROLS THAT
 WILL TURN OFF THE PUMP WHEN THE WATER IN THE
 CIRCULATION LOOP HAS REACHED THE DESIRED TEMPERATURE,
 AND WHEN THERE IS NO DEMAND FOR HOT WATER- SECTION
 C404.6.1 FBC EC.
  
 14) P001: PLEASE INCLUDE THE LAVATORY FAUCETS IN THE
 FIXTURE SCHEDULE- C404.12.2 FBC EC.
  
 15) P402 & P601: SHOW THE REQUIRED TRAP PRIMER FOR THE
 FLOOR DRAIN- SECTION 1002.4 FBC P.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-05-21 Cont ID  
Sent By medwards Date 2020-05-21 Time 10:59 Rev Time 0.00
Received By medwards Date 2020-05-21 Time 10:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-05-11 Cont ID  
Sent By rmcphers Date 2020-05-11 Time 14:30 Rev Time 0.00
Received By rmcphers Date 2020-05-11 Time 14:30 Sent To  
Notes
2020-05-11 14:27:33ELECTRICAL DRAWINGS = ENGINEER CANNOT SELF-CERTIFY THE
 DIGITAL SIGNATURE
 668.003(2) AND (3), F.S.
 (2) A PROFESSIONAL ENGINEER UTILIZING A DIGITAL
 SIGNATURE TO ELECTRONICALLY SIGN AND SEAL ENGINEERING
 PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS SHALL HAVE
 THEIR IDENTITY AUTHENTICATED BY A CERTIFICATION
 AUTHORITY.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-04-06 Cont ID  
Sent By rmcphers Date 2020-04-06 Time 14:06 Rev Time 0.00
Received By rmcphers Date 2020-04-06 Time 14:06 Sent To  
Notes
2020-04-09 14:21:56ELECTRONIC SIGNATURES AND SEALS NOT PROVIDED ON THE
 ENERGYGAUGE COMPLIANCE FORM, AND THE AC COOLING AND
 HEATING CALCULATIONS- REFER TO SECTION C103.1.1.1.2 FBC
 EC-2017, AND FL. STATUTE 471.025 & FAC 61G15-23.005.
2020-04-06 14:08:21STRUCTURAL DRAWINGS DO NOT SHOW AS ELECTRONICALLY
 SIGNED IN "ADOBE"

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-02-20 Cont ID  
Sent By rmcphers Date 2020-02-20 Time 12:02 Rev Time 0.00
Received By rmcphers Date 2020-02-20 Time 12:01 Sent To  
Notes
2020-02-20 12:03:13ALL DRAWINGS IN "PROJECT DOX" NEED TO BE ELECTRONICALLY
 SIGNED AND SEALED.

Review Stop Z ZONING
Rev No 2 Status P Date 2020-04-14 Cont ID  
Sent By aaponte Date 2020-04-14 Time 16:53 Rev Time 0.00
Received By aaponte Date 2020-04-14 Time 16:53 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-03-20 Cont ID  
Sent By aaponte Date 2020-03-20 Time 16:05 Rev Time 0.00
Received By aaponte Date 2020-03-20 Time 16:05 Sent To  
Notes
2020-03-20 16:08:281. PLEASE PROVIDE FACADE DRAWINGS INDICATING HOW THE
 FACADE WILL BE MODIFIED WITH THE PROPOSED CHANGES.
 2. STOREFRONT SHALL MAINTAIN MINIMUM TRANSPARENCY
 REQUIREMENT, AND CANNOT BE BLOCKED BY BLINDS OR FILMS.
 MINIMUM TRANSPARENCY FOR ACTIVE USES IS 30% (SEE
 SECTION 94-109 FOR HOW TO MEASURE).
 FOR ADDITONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.