Plan Review Details - Permit 20020348
Plan Review Stops For Permit 20020348
Review Stop E ELECTRICAL
Rev No 2 Status N Date 2020-02-20 Cont ID  
Sent By jleahy Date 2020-02-20 Time 08:28 Rev Time 0.00
Received By rsklarew Date 2020-02-20 Time 08:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-02-12 Cont ID  
Sent By jleahy Date 2020-02-12 Time 10:49 Rev Time 0.00
Received By jleahy Date 2020-02-12 Time 10:28 Sent To  
Notes
2020-02-12 10:49:31FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 THIS UNIT IS BEING FED BY MORE THAN ONE CIRCUIT SO A
 PANEL BOARD AND GROUNDING SYSTEM NEEDS TO BE INSTALLED
 AT THE SEPARATE BUILDING.
  
 225.30 NUMBER OF SUPPLIES
 A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A
 BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE
 DISCONNECTING MEANS SHALL BE
 SUPPLIED BY ONLY ONE FEEDER OR BRANCH CIRCUIT UNLESS
 PERMITTED IN 225.30(A) THROUGH (E).

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-02-20 Cont ID  
Sent By rsklarew Date 2020-02-20 Time 08:28 Rev Time 0.00
Received By rsklarew Date 2020-02-20 Time 08:28 Sent To  
Notes
2020-02-19 13:52:38RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-02-12 Cont ID  
Sent By jleahy Date 2020-02-12 Time 10:49 Rev Time 0.00
Received By jleahy Date 2020-02-10 Time 14:02 Sent To  
Notes
2020-02-11 14:02:52REVISION ROUTED TO JLEAHY