Plan Review Details - Permit 20020292
Plan Review Stops For Permit 20020292
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2020-04-30 Cont ID  
Sent By rmcdouga Date 2020-04-30 Time 17:25 Rev Time 0.00
Received By rmcdouga Date 2020-04-30 Time 17:25 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-04-29 Cont ID  
Sent By rmcdouga Date 2020-04-29 Time 17:47 Rev Time 0.00
Received By rmcdouga Date 2020-04-29 Time 17:47 Sent To  
Notes
2020-04-29 17:48:36SEE PREVIOUS COMMENTS, WHICH HAVE NOT BEEN ADDRESSED.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-02-18 Cont ID  
Sent By jwitmer Date 2020-02-18 Time 06:55 Rev Time 0.00
Received By jwitmer Date 2020-02-18 Time 06:54 Sent To  
Notes
2020-02-18 06:55:21ASBESTOS COMMERCIAL. PLEASE PROVIDE A SIGNED
 ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD,
 STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF
 ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF
 HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT
 NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL
 INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE
 FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-05-01 Cont ID  
Sent By rmcdouga Date 2020-05-01 Time 13:08 Rev Time 0.00
Received By rmcdouga Date 2020-05-01 Time 13:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-04-29 Cont ID  
Sent By rmcdouga Date 2020-04-29 Time 17:25 Rev Time 0.00
Received By rmcdouga Date 2020-04-29 Time 14:58 Sent To  
Notes
2020-04-29 17:37:35PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS HAVE NOT BEEN SIGNED AND SEALED BY THE
 ARCHITECT AS REQUIRED BY CHAPTER 481, FLORIDA STATUTES
 & 61G1 FLORIDA ADMINISTRATIVE CODE. THIS SUBMITTAL WAS
 CONVERTED TO DIGITAL PLANS TO EXPEDITE THE REVIEWS DUE
 TO THE CURRENT SITUATION. WHEN YOU RESUBMIT
 ELECTRONICALLY, THE PLANS WILL BE REQUIRED TO BE
 DIGITALLY SIGNED AND SEALED BY THE DESIGNER OF RECORD.
 ALSO REFER TO THE COMMENTS UNDER THE SIGNATURE REVIEW
 STOP.
  
 2) THE COMMENTS UNDER THE ASBESTOS REVIEW STOP WERE NOT
 ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-02-18 Cont ID  
Sent By jwitmer Date 2020-02-18 Time 08:17 Rev Time 0.00
Received By jwitmer Date 2020-02-18 Time 06:54 Sent To  
Notes
2020-02-18 08:17:042017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20020292
 ADD: 215 N OLIVE AVE. SUITE: 110
 CONT: JFB CONSTRUCTION & DEVELOPMENT
 TEL: 561-582-9840 EXT. # 1
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. FEB. 18/2020
 ACTION: DENIED
  
 1) NEITHER THE LIFE SAFETY SHEET A-1 OR SHEET A-2 SHOW
 ANY ACCESSIBILITY ELEMENTS FOR DINING, PLEASE SHOW
 COMPLIANCE WITH THE 2017 FBC-EXISTING BUILDING SECTION
 806.1 A BUILDING, OR FACILITY, OR ELEMENT THAT IS
 ALTERED SHALL COMPLY WITH THE PROVISIONS OF THE FLORIDA
 BUILDING CODE, ACCESSIBILITY CODE. THE LIFE SAFETY
 SHEET DOES NOT SHOW COMPLIANCE WITH THE 2017
 FBC-ACCESSIBILITY CODE;
 1A) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
  
 1B) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 1C) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN
 RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL
 BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR
 SUNKEN DINING AREAS, BAR TOPS, HIGH TOPS AND OR OUTDOOR
 DINING AREAS.
  
 1D) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK
 SURFACES INCLUDE WRITING SURFACES, BABY CHANGING AND
 OTHER TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON
 COUNTERS, AND WHERE COVERED BY THE ADA SCOPING
 PROVISIONS.
  
 1D)(1)BE PROVIDED. KNEE AND TOE CLEARANCE COMPLYING
 WITH 306 SHALL BE PROVIDED OF THE 2017
 FBC-ACCESSIBILITY CODE.
  
 1D)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND, 2017
 FBC-ACCESSIBILITY CODE.
  
 1E) NEITHER THE LIFE SAFETY SHEET A-1 OR SHEET A-2 SHOW
 ACCESSIBILITY COMPLIANCE WITH THE REQUIRED COUNTER
 HEIGHT FOR THE POINT OF SALE. 2017 ACCESSIBILITY CODE.
 SALES & SERVICE COUNTERS. 904.4.1. A PORTION OF THE
 COUNTER SURFACE THAT IS 36 INCHES LONG MINIMUM AND 36
 INCHES HIGH MAXIMUM ABOVE THE FINISH FLOOR SHALL BE
 PROVIDED. A CLEAR FLOOR OR GROUND SPACE COMPLYING WITH
 305 SHALL BE POSITIONED FOR A PARALLEL APPROACH
 ADJACENT TO THE 36 INCH MINIMUM LENGTH COUNTER.
  
 2) SHEET A-4:
  
 2A) THE DOOR SCHEDULE IDENTIFIES DOOR D-2 VARIOUS
 LOCATIONS BUT NEITHER SHEET A-1 OR A-2 SHOW THE
 LOCATIONS FOR DOOR TYPE D-2. 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATIVE CODE SECTION 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED, CODE COMPLIANCE CANNOT BE
 DETERMINED. ACCESS. CODE 404.2.3 CLEAR WIDTH. DOOR
 OPENINGS SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES
 MINIMUM. CLEAR OPENING OF DOORWAYS WITH SWINGING DOORS
 SHALL BE MEASURED BETWEEN THE FACE OF THE DOOR AND THE
 STOP, WITH THE DOOR OPEN 90 DEGREES.
 2B) PLEASE REVIEW DETAILS B & D FOR THE DISTANCE THE
 WATER CLOSET CAN BE INSTALLED FROM THE SIDE WALL, THE
 PLANS SHOW A DISTANCE OF 1 FOOT 7 INCHES OR 19 INCHES
 CENTER LINE AWAY FROM THE SIDE WALL. PLEASE REVIEW IN
 THE ACCESSIBILITY CODE SECTION 604.2 AND FIGURE 604.2
 (A) 16-18 INCHES. FIGURE 604.2 (B) 17-19 INCHES IS FOR
 AMBULATORY ACCESSIBLE STALLS. PLEASE CORRECT THE PLAN
 DETAILS.
  
 2C) THE FLOOR PLAN NOR THE ELEVATION DETAILS A-D
 PROVIDE WHAT THE OVERALL WALL DIMENSIONS ARE WITHIN THE
 ACCESSIBLE RESTROOMS. CODE COMPLIANCE CANNOT BE
 DETERMINED FOR 304.3.1 OR 304.3.2 TURNING SPACE IN THE
 2017 FBC-ACCESSIBILITY CODE.
  
 2D) THE ELEVATION DETAILS A-D DO NOT PROVIDE THE HEIGHT
 THAT THE LAVATORY IS INSTALLED. PLEASE SHOW COMPLIANCE
 WITH: 2017 FBC-ACCESSIBILITY CODE SECTION 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 2017 FBC-ACCESSIBILITY CODE 606.4 FAUCETS. CONTROLS FOR
 FAUCETS SHALL COMPLY WITH 309. HAND-OPERATED METERING
 FAUCETS SHALL REMAIN OPEN FOR 10 SECONDS MINIMUM.
  
 2017 FBC-ACCESSIBILITY CODE 606.5 EXPOSED PIPES AND
 SURFACES. WATER SUPPLY AND DRAIN PIPES UNDER LAVATORIES
 AND SINKS SHALL BE INSULATED OR OTHERWISE CONFIGURED TO
 PROTECT AGAINST CONTACT. THERE SHALL BE NO SHARP OR
 ABRASIVE SURFACES UNDER LAVATORIES AND SINKS.
  
 2E) MIRRORS. 2017 FBC-ACCESSIBILITY CODE 603.3. MIRRORS
 LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL BE
 INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE 35 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
  
 3) THE PERMIT APPLICATION INDICATES THAT $130,534
 DOLLARS OF WORK IS TO BE ACCOMPLISHED UNDER THIS
 PERMIT. PLEASE PROVIDE A LETTER EITHER FROM THE
 CONTRACTOR OR DESIGNER OF RECORD ON THEIR LETTERHEAD
 WHERE UP TO 20 % OF THE CONTRACT VALUE ($26,106.00) IS
 GOING TO BE SPENT IN ACCESSIBLE UPGRADES TO THE
 PROJECT. IF ALL EXISTING CONDITIONS ARE COMPLETED
 (COMPLIED) BEFORE DISPROPORTIONATION COST IS MET A
 LETTER IS NOT REQUIRED. SHOW COMPLIANCE WITH THE:
 2017 FBC-ACCESSIBILITY CODE SECTION 202.4.1
 DISPROPORTIONATE COST. ALTERATIONS MADE TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO THE ALTERED AREA WILL BE
 DEEMED DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN
 THE COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO
 THE PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2020-05-13 Cont ID  
Sent By jpearson Date 2020-05-13 Time 12:15 Rev Time 0.00
Received By jpearson Date 2020-05-13 Time 12:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-05-08 Cont ID  
Sent By jpearson Date 2020-05-08 Time 12:25 Rev Time 0.00
Received By jpearson Date 2020-05-08 Time 12:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-04-28 Cont ID  
Sent By jpearson Date 2020-04-28 Time 17:02 Rev Time 0.00
Received By jpearson Date 2020-04-28 Time 15:51 Sent To  
Notes
2020-04-28 16:50:29CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. SHEET E-1 DOES NOT HAVE THE ARCHITECTS SEAL AND
 SIGNATURE. PER THE WPB AMENDMENTS TO THE FBC, PLAN
 (EACH SHEET OF BOTH COPIES) IS REQUIRED TO BEAR THE
 NAME AND BE SIGNED AND SEALED BY THE PERSON RESPONSIBLE
 FOR THE DESIGN. PROVIDE CORRECTION. WPB FBC 107.1,
 107.2; FS 471, 481 (DIGITAL SIGNATURES PROVIDED, BUT
 NOT CORRECT. ENGINEER IS NOT PERMITTED TO SELF-CERTIFY
 HIS SIGNATURE. PROVIDE PROPER THIRD-PARTY VERIFICATION
 FOR ALL SHEETS.)
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
  
 NEW COMMENT:
  
 6. PANEL SCHEDULES PROVIDED SHOW A LOAD OF 0 AMPS.
 PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-02-25 Cont ID  
Sent By jpearson Date 2020-02-25 Time 13:23 Rev Time  
Received By jpearson Date   Time   Sent To I
Notes
2020-02-25 13:23:00CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SHEET E-1 DOES NOT HAVE THE ARCHITECTS SEAL AND
 SIGNATURE. PER THE WPB AMENDMENTS TO THE FBC, PLAN
 (EACH SHEET OF BOTH COPIES) IS REQUIRED TO BEAR THE
 NAME AND BE SIGNED AND SEALED BY THE PERSON RESPONSIBLE
 FOR THE DESIGN. PROVIDE CORRECTION. WPB FBC 107.1,
 107.2; FS 471, 481
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND GFCI PROTECTION WHERE APPLICABLE TO COMPLY WITH
 CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5, 408.4;
 WPB FBC 107.3.5
 3. RECEPTACLE OUTLETS IN BATHROOMS REQUIRE GFCI
 PROTECTION. PROVIDE CORRECTION. NEC 210.8
 4. PROVIDE SCOPE OF WORK DETAIL. WPB FBC 107.2.1
 5. PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT
 SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-04-28 Cont ID  
Sent By pleduc Date 2020-04-28 Time   Rev Time 0.00
Received By pleduc Date 2020-04-28 Time 09:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-02-12 Cont ID  
Sent By pleduc Date 2020-02-12 Time   Rev Time 0.00
Received By pleduc Date 2020-02-12 Time 11:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2020-05-13 Time   Rev Time 0.00
Received By lmarchan Date 2020-05-08 Time 14:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2020-05-08 Time   Rev Time 0.00
Received By lmarchan Date 2020-05-01 Time 10:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-04-29 Cont ID  
Sent By rmcdouga Date 2020-04-29 Time 17:49 Rev Time 0.00
Received By rmcdouga Date 2020-04-28 Time 07:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-02-25 Time   Rev Time 0.00
Received By lmarchan Date 2020-02-07 Time 13:54 Sent To  
Notes
2020-02-10 13:54:25B09

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2020-02-18 Cont ID  
Sent By jwitmer Date 2020-02-18 Time 07:15 Rev Time 0.00
Received By jwitmer Date 2020-02-18 Time 06:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By hmoser Date 2020-02-11 Time 13:19 Sent To  
Notes
2020-02-11 13:46:24NO AIR CONDITIONING OR MECHANICAL WORK BEING DONE AT
 THIS TIME
 ANY A/C OR MECHANICAL WORK BEING DONE AT A LATER DATE
 WILL
 REQUIRE AN APPLICATION, PLAN AND PERMIT.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2020-05-12 Cont ID  
Sent By ccole Date 2020-05-12 Time 08:48 Rev Time 0.00
Received By ccole Date 2020-05-12 Time 07:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-04-29 Cont ID  
Sent By ccole Date 2020-04-29 Time 09:44 Rev Time 0.00
Received By ccole Date 2020-04-28 Time 15:25 Sent To  
Notes
2020-04-29 09:56:36PLEASE SEE SIGNATURE REVIEW COMMENTS BY J.PEARSON.
 FINAL PERMIT ISSUANCE PENDING RESUBMITTAL OF
 ELECTRONICALLY SIGNED AND SEALED PLANS BY ARCHITECT AND
 THE ENGINEER.

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-02-19 Cont ID  
Sent By gjohnson Date 2020-02-19 Time 10:52 Rev Time 0.00
Received By gjohnson Date 2020-02-19 Time 09:38 Sent To  
Notes
2020-02-19 10:53:131ST REVIEW: 20020292
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. A-4 SHOW CLEAR FLOOR SPACE FOR TOILETS. PER FBC
 ACC 604.3.1
  
 2. SHT A-4 SHOW THE DIMENSIONS ON THE CLEAR FLOOR SPACE
 ON THE LAVATORY AND TOILET. PER WPB AMEND TO FBC
 107.2.1
  
 3. SHT. A-4 THE TOP RIM OF THE LAVATORY SHALL BE 34"
 MAX PER FBC ACC 606.3
  
 4. SHT. A-4 THE BOTTOM EDGE OF THE REFLECTIVE SURFACE
 OF THE MIRROR SHALL BE MAX OF 40". PER FBC ACC 603.3
  
 5. PLEASE PROVIDE A SANITARY AND WATER ISOMETRIC
 DRAWING. PER WPB AMEND TO FBC 107.2.1
  
 6. TEMPERED WATER REQUIRED AT THE LAVATORY'S DELIVERED
 THROUGH A TEMPERATURE LIMITING DEVICE COMPLYING WITH
 ASSE 1070 OR CSA B125.3
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-05-13 Cont ID  
Sent By shill Date 2020-05-13 Time 15:18 Rev Time 0.00
Received By shill Date 2020-05-13 Time 15:18 Sent To  
Notes
2020-05-13 15:19:03ONE PAPER ORIGINAL RECEIVED, ROUTED TO RECORDS
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2020-05-13 Cont ID  
Sent By shill Date 2020-05-13 Time 11:06 Rev Time 0.00
Received By shill Date 2020-05-13 Time 11:06 Sent To  
Notes
2020-05-13 11:07:46****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 MEP DIGITALLY SIGNED PLANS IN THE SIGNTURE FOLDER FOR
 DOCUMENTS SUBMITTED FIRST REVIEW HAS BEEN REMOVED AS
 ALL MEP PAGES WERE SUPERSEDED BY DIGITALLY SIGNED
 PAGES.
  
 THE ARCHITECTURAL PAGES ARE ALSO IN THE SIGNATURE
 FOLDER BUT THE PDF IS NOT DIGITALLY SIGNED. PLEASE
 PROVIDE A DIGITALLY SIGNED PDF OR SUBMIT ONE PAPER
 ORIGINAL AFTER ALL REVIEWS HAVE PASSED. THIS CAN BE
 SUBMITTED TO THE BUILDING DIVISION WITH A PLAN REVIEW
 REQUEST FORM, DESCRIPTION SHOULD BE "SIGNATURE
 DOCUMENTS".
  
 THE ARCHITECTURAL PAGES LACK THE SEAL REQUIRED, ALSO
 LACKS THE LICENSE NUMBER FOR THE ARCHITECT, CLAUDIA
 DE-NARVAEZ (AR98739). PLEASE HAVE HER CALL ME TO
 DISCUSS.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-05-03 Cont ID  
Sent By shill Date 2020-05-03 Time 10:48 Rev Time 0.00
Received By shill Date 2020-05-03 Time 10:47 Sent To  
Notes
2020-05-03 10:50:17****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 MEP DIGITALLY SIGNED PLANS ARE IN THE SIGNTURE FOLDER
  
 THE ARCHITECTURAL PAGES ARE ALSO IN THE SIGNATURE
 FOLDER BUT THE PDF IS NOT DIGITALLY SIGNED. PLEASE
 PROVIDE A DIGITALLY SIGNED PDF OR SUBMIT ONE PAPER
 ORIGINAL AFTER ALL REVIEWS HAVE PASSED. THIS CAN BE
 SUBMITTED TO THE BUILDING DIVISION WITH A PLAN REVIEW
 REQUEST FORM, DESCRIPTION SHOULD BE "SIGNATURE
 DOCUMENTS".
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-04-28 Cont ID  
Sent By jpearson Date 2020-04-28 Time 16:37 Rev Time 0.00
Received By jpearson Date 2020-04-28 Time 16:37 Sent To  
Notes
2020-04-28 16:37:27COVER SHEET, DEMO SHEETS, AND A SHEETS ARE MISSING
 SIGNATURE. ELECTRICAL AND PLUMBING SHEETS ARE
 SELF-CERTIFIED BY THE ENGINEER. PER THE WPB AMENDMENTS
 TO THE FBC, EACH SHEET OF PLAN IS REQUIRED TO BE SIGNED
 AND SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. A
 DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE WITH THE
 PROPER THIRD PARTY VERIFICATION. PROVIDE CORRECTION.
 ALTERNATIVELY, A SIGNED/SEALED PAPER SET MAY BE
 SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL TRADES ARE
 APPROVED. WPB FBC 107.1; FS 471/481