Plan Review Details - Permit 20020258
Plan Review Stops For Permit 20020258
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-02-18 Cont ID  
Sent By jwitmer Date 2020-02-18 Time 13:02 Rev Time 0.00
Received By jwitmer Date 2020-02-18 Time 13:01 Sent To  
Notes
2020-02-18 13:02:35PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-02-18 Cont ID  
Sent By jwitmer Date 2020-02-18 Time 13:35 Rev Time 0.00
Received By jwitmer Date 2020-02-18 Time 13:02 Sent To  
Notes
2020-02-18 13:34:562017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20020258
 ADD: 5600 N. FLAGLER DR. SUITE: PH206
 CONT: WALL TO WALL WE DO IT ALL
 TEL: 561-463-9708
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. FEB. 18TH/ 2020
 ACTION: DENIED
  
 1) SHEET 1 PALM BEACH HOUSE FLOOR PLAN OF UNIT NOT TO
 SCALE, SMALLER THAN 1/8 INCH SCALE. 2017 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1 ADMINISTRATIVE CODE 107.2.1.3 QUALITY OF BUILDING
 PLANS. BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8
 INCH SCALE UPON SUBSTANTIAL PAPER. THE BUILDING
 OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY,
 OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, IN ORDER
 TO PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM.
  
 2) 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE
 THE EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
  
 3) 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. THE
 PERMIT APPLICATION UNDER THE DESCRIPTION OF WORK
 INDICATES INSTALL TILE, DRYWALL, PART. PLEASE PROVIDE A
 BETTER DESCRIPTION OF WORK. SHEET 2 OF 3 IT WOULD
 APPEAR THERE IS STILL A TUB IN THE BATHROOM BUT SHEET 3
 OF 3 IT WOULD APPEAR THE TUB HAS BEEN REMOVED AND A NEW
 SHOWER, (5 INCH CURB) IS BEING PROPOSED.
  
 4) FOR NEW SUB-SURFACES/ BASE FOR TILE MUST SHOW
 COMPLIANCE WITH 2509.2 OF THE 2017 FBC-B:
 GLASS MAT GYPSUM BACKING PANEL ASTM C1178
 NONASBESTOS FIBER-CEMENT BACKER BOARD ASTM C1288 OR ISO
 8336 CATEGORY C
 NONASBESTOS FIBER-MAT REINFORCED CEMENTITIOUS BACKER
 UNIT ASTM C1325
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-01 Cont ID  
Sent By jpearson Date 2020-03-01 Time 13:38 Rev Time 0.00
Received By jpearson Date 2020-03-01 Time 13:38 Sent To I
Notes
2020-03-01 13:38:32CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR SIGNED BY
 THE ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-02-12 Cont ID  
Sent By pleduc Date 2020-02-12 Time   Rev Time 0.00
Received By pleduc Date 2020-02-12 Time 14:59 Sent To  
Notes
2020-02-12 15:06:21THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE APPLICATION INDICATES "INSTALL TILE, DRYWALL,
 PART,"(?)
  
 WHAT DOES "PART" MEAN?
  
 PLEASE PROVIDE A DETAILED SCOPE OF WORK
  
  
 2) THE SUBMITTED PLANS DO NOT CONTAIN ORGANIZED OR
 DETAILED INFORMATION THAT COULD BE REVIWED FOR LIFE
 SAFETY PURPOSES.
  
 PLEASE PROVIDE GREATER DETAIL WITH MORE ACCURATE FLOOR
 PLANS AND WHAT AND WHERE THE ACTUAL WORK IS LOCATED
 THAT MATCHES THE SCOPE OF WORK NOTED ABOVE.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-03-01 Time   Rev Time 0.00
Received By lmarchan Date 2020-02-07 Time 13:35 Sent To  
Notes
2020-02-10 13:35:41B08

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-02-24 Cont ID  
Sent By jesmith Date 2020-02-24 Time 13:27 Rev Time 0.00
Received By jesmith Date 2020-02-24 Time 13:23 Sent To  
Notes
2020-02-24 13:24:46CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 1) SHEET 1 PALM BEACH HOUSE FLOOR PLAN OF UNIT NOT TO
 SCALE, SMALLER THAN 1/8 INCH SCALE. 2017 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1 ADMINISTRATIVE CODE 107.2.1.3 QUALITY OF BUILDING
 PLANS. BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8
 INCH SCALE UPON SUBSTANTIAL PAPER. THE BUILDING
 OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY,
 OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, IN ORDER
 TO PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM.
 2) PER WPB FBC 107.2.1, PROVIDE OWNER?S NAME AND FULL
 ADDRESS INCLUDING UNIT ON EACH PLAN SHEET.
 3) PER WPB FBC 107.2.1, PROVIDE SEQUENCE NUMBERING OF
 PLANS AND INDICATE EXISTING AND PROPOSED PLANS.
  
 4) IF THE INTENT IS TO REPLACE THE BATHTUB WITH A
 SHOWER, THEN PER WPB FBC 107.2.1 AND FBC PL SECTION
 417, PROVIDE AN ELEVATION DETAIL OF SHOWER STALL
 SHOWING;
  
 A) DRAIN PIPE THROUGH THE FLOOR; SPECIFY TYPE OF
 MATERIAL TO BE USED AND THAT WHICH IT IS CONNECTING TO
 BELOW THE SLAB
 B) DRAIN BODY WITH CLAMPING MEMBRANE
 C) SHOWER LINING TO A POINT 2 INCHES ABOVE THE TOP OF
 THE THRESHOLD; SPECIFY MATERIAL TYPE. REFERENCE FBC PL
 417.5.2.1 THROUGH 417.5.2.6 FOR APPROVED MATERIAL
 TYPES.
 D) PITCH OF MINIMUM 2% FROM WALLS/CURB TO DRAIN BETWEEN
 SLAB AND LINER
 E) INDICATE HOW FLOOR PENETRATION WILL BE FIRESAFED.
  
 5) PER WPB FBC 107.2.1, PROVIDE AN ENLARGED,
 DIMENSIONED FLOOR PLAN OF THE PROPOSED REMODELED
 BATHROOM. (8-1/2 X 11 SIZE PAPER IS SUFFICIENT)
  
 A) PROVIDE FINISH INSIDE DIMENSIONS OF THE SHOWER
 SHOWING COMPLIANCE WITH FBC PL 417.4.
 B) COMPLY WITH FBC PL 405.3.1; WATER CLOSET SHALL NOT
 BE CLOSER THAN 15 INCHES FROM IT?S CENTER TO ANY SIDE
 WALL, VANITY, OR OTHER OBSTRUCTION AND NO LESS THAN 30
 INCHES CLEAR BETWEEN TWO FIXTURES
  
 6) PROVIDE PRINTED NAME OF DESIGNER AND SIGNATURE OF
 THE SAME ON EACH PLAN. WPB FBC 107.3.4.3 CERTIFICATION
 BY CONTRACTOR. PLEASE NOTE THE EXCEPTION TO ENGINEERED
 PLANS UNDER 471.003(H) ELECTRICAL/ PLUMBING/
 MECHANICAL, 481.229(1)(C) (BUILDING) REQUIRES THE
 CONTRACTOR FOR THAT TRADE THAT WILL BE LICENSED IN THAT
 TRADE, WILL ALSO BE THE CONTRACTOR THAT DESIGNS THE
 SYSTEM UNDER THAT TRADE. FOR EACH TRADE THE CONTRACTOR
 RESPONSIBLE FOR THE DESIGN UNDER THE TRADE LICENSED IN
 MUST PRINT THEIR NAME, SIGN THEIR NAME AND LICENSE
 NUMBER, NOTE THESE PLANS APPEAR TO BE DRAWN BY ONE
 INDUVIAL, THEY WOULD HAVE TO BE LICENSED AS A BUILDING,
 ELECTRICAL AND PLUMBING CONTRACTOR TO SUBMIT ALL THESE
 TRADES UNDER ONE SHEET.
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 AS THE PLANS ARE NOT SIGNED AND SEALED BY A
 PROFESSIONAL ENGINEER OR ARCHITECT, THE PLUMBING PLAN
 SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE
 DESIGNER PER WPB FBC 107.2.1.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 20020258 5600 N FLAGLER DR PH206