Plan Review Details - Permit 20020213
Plan Review Stops For Permit 20020213
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-02-22 Cont ID  
Sent By pvalenti Date 2020-02-22 Time 11:19 Rev Time 0.00
Received By pvalenti Date 2020-02-22 Time 11:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-02-08 Cont ID  
Sent By pvalenti Date 2020-02-08 Time 11:08 Rev Time 0.00
Received By pvalenti Date 2020-02-08 Time 11:08 Sent To  
Notes
2020-02-08 11:55:14***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 1) FOR TEMPORARY MEMBRANE STRUCTURES (TENTS) WITH A
 SPAN OF 40' OR GREATER IN ANY DIRECTION:
 A. PROVIDE DETAILS FOR STRUCTURAL CONNECTIONS.
 B. PROVIDE STRUCTURAL EVALUATION OF STRUCTURE.
 THESE DOCUMENTS SHALL BE REVIEWED, SIGNED AND SEALED BY
 A DESIGN PROFESSIONAL.
  
 2) FBC B TABLE 2902.1, ON SITE PLAN SHOW THE LOCATION
 OF SANITARY FACILITIES/RESTROOMS (PERMANENT AND/OR
 PORTABLE) AS PER THE REQUIREMENTS OF TABLE 2902.1 OF
 THE FLORIDA BUILDING CODE.
 NOTE: PROVIDE LOCATION OF ACCESSIBLE ROUTE FROM TENT TO
 ACCESSIBLE RESTROOMS ON SITE PLAN. THE ACCESSIBLE
 RESTROOMS SHALL BE LOCATED WITHIN 500' OF TENT.
  
 3) FBC A 402 PROVIDE LOCATION OF ACCESSIBLE ROUTE FROM
 PARKING TO TENT ENTRANCE.
  
 4) FBC B 602, ON SITE PLAN SHOW THE DISTANCE TO LOT
 LINES AND OTHER STRUCTURES.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-02-21 Cont ID  
Sent By pleduc Date 2020-02-21 Time   Rev Time 0.00
Received By pleduc Date 2020-02-21 Time 11:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-02-10 Cont ID  
Sent By pleduc Date 2020-02-10 Time   Rev Time 0.00
Received By pleduc Date 2020-02-10 Time 11:09 Sent To  
Notes
2020-02-10 11:23:32THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS NO INDICATION OF A FLOOR/SEATING PLAN.
  
 WHAT WILL THIS TENT BE USED FOR?
  
 WAHT IS THE NUMBER OF PROPOSED OCCUPANTS?
  
 A FLOOR/SEATING PLAN IS REQUIRED.
  
  
  
 2) THERE ARE NO INDICATIONS IF THE TENT WILL HAVE SIDES
 OR EXIT DOORS.
  
 PLEASE PROVIDE FOR EXITING PER THE NUMBER OF OCCUPANTS.
  
  
  
 3) WILL THIS TENT BE USED AT NIGHT?
  
 HOW WILL THE ELECTFICITY/LIGHTING BE PROVIDED?
  
  
  
 4) WHERE WILL THE TENT BE LOCATED?
  
 PER NFPA 1 CH 25
  
 25.2.1.2 TENTS SHALL BE ERECTED TO COVER NOT MORE THAN
 75 PERCENT
 OF THE PREMISES, UNLESS OTHERWISE APPROVED BY THE AHJ.
  
 25.2.3.3 TENTS NOT OCCUPIED BY THE PUBLIC AND NOT USED
 FOR THE
 STORAGE OF COMBUSTIBLE MATERIAL SHALL BE PERMITTED TO
 BE ERECTED
 LESS THAN 10 FT (3050 MM) FROM OTHER STRUCTURES WHERE
 THE AHJ
 DEEMS SUCH CLOSE SPACING TO BE SAFE FROM HAZARD TO THE
 PUBLIC.
  
 25.2.3.5 THE PLACEMENT OF TENTS RELATIVE TO OTHER
 STRUCTURES SHALL
 BE AT THE DISCRETION OF THE AHJ, WITH CONSIDERATION
 GIVEN TO
 OCCUPANCY, USE, OPENING, EXPOSURE, AND OTHER SIMILAR
 FACTORS.
  
 25.2.4 FIRE HAZARDS.
 25.2.4.1 THE FINISHED GROUND LEVEL ENCLOSED BY ANY
 TENT, AND THE
 FINISHED GROUND LEVEL FOR A REASONABLE DISTANCE, BUT
 FOR NOT LESS
 THAN 10 FT (3050 MM) OUTSIDE OF SUCH A TENT, SHALL BE
 CLEARED OF ALL
 FLAMMABLE OR COMBUSTIBLE MATERIAL OR VEGETATION THAT IS
 NOT USED
 FOR NECESSARY SUPPORT EQUIPMENT. THE CLEARING WORK
 SHALL BE
 ACCOMPLISHED TO THE SATISFACTION OF THE AHJ PRIOR TO
 THE ERECTION
 OF SUCH A TENT. THE PREMISES SHALL BE KEPT FREE FROM
 SUCH
 FLAMMABLE OR COMBUSTIBLE MATERIALS DURING THE PERIOD
 FOR WHICH
 THE PREMISES ARE USED BY THE PUBLIC. [101: 11.11.4.1]
  
  
 PLEASE PROVIDE A SITE PLAN INCLUDING PROPOSED
 DIMESNIONS FOR PROPERTY LINES AND OTHER STRUCTURES.
  
  
  
 5) THERE ARE NO INDICATIONS OF NO SMOKING SIGNS
  
 25.2.4.2 SMOKING.
 25.2.4.2.1 SMOKING SHALL NOT BE PERMITTED IN ANY TENT,
 UNLESS
 APPROVED BY THE AHJ. [101: 11.11.4.2.1]
 25.2.4.2.2 IN ROOMS OR AREAS WHERE SMOKING IS
 PROHIBITED, PLAINLY
 VISIBLE SIGNS SHALL BE POSTED THAT READ AS FOLLOWS:
 NO SMOKING
  
 PLEASE PROVIDE
  
  
  
 6) THERE ARE NO INDICATIONS OF FIRE EXTINGUISHERS
  
 25.2.5 FIRE-EXTINGUISHING EQUIPMENT. PORTABLE
 FIREEXTINGUISHING
 EQUIPMENT OF APPROVED TYPES SHALL BE FURNISHED AND
 MAINTAINED IN TENTS IN SUCH QUANTITY AND IN SUCH
 LOCATIONS AS
 DIRECTED BY THE AHJ.
  
 PLEASE PROVIDE CERTIFIED 5LB ABC EXTINGUISHERS WITHIN
 75FT TRAVLE DISTANCE.
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-02-22 Cont ID  
Sent By pvalenti Date 2020-02-22 Time 11:19 Rev Time 0.00
Received By pvalenti Date 2020-02-20 Time 11:08 Sent To  
Notes
***NONE***