| 2020-02-18 10:45:39 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M101: THE PREVIOUSLY UNCONDITIONED STORAGE |
| | BUILDING SHALL BE IN FULL COMPLIANCE WITH THE FLORIDA |
| | ENERGY CONSERVATION CODE- 2017 SIXTH EDITION. PLEASE |
| | SUBMIT A COMPLIANCE REPORT- SECTION C101.5 FBC EC. |
| | |
| | 2) M101: PLEASE CLARIFY WHY THE BUILDING IS BEING |
| | CONDITIONED. PROVIDE A BRIEF NARRATIVE DESCRIBING THE |
| | USE OF THE STORAGE SPACES. PLEASE NOTE THAT CHANGES OF |
| | OCCUPANCY SHALL COMPLY THE FLORDIA EXISTING BUILDING |
| | CODE- 2017 SIXTH EDITION (SECTION 101.2 FBC EX) AND MAY |
| | REQUIRE A FL. LICENSED DESIGN PROFESSIONAL TO PROVIDE |
| | PLANS AND SPECIFICATIONS. |
| | |
| | 3) M101: IT APPEARS THAT THE STORAGE SPACES HAVE GARAGE |
| | BAY DOORS WHICH INDICATES VEHICLES MAY BE STORED IN THE |
| | SPACES. REFER TO TABLE 403.3.1.1 AND SECTION 404: |
| | EXHAUST VENTILATION SYSTEMS REQUIRED. |
| | |
| | 4) M101: THE SUBMITTED AC HEAT LOAD CALCULATIONS DO NOT |
| | INDICATE BAY DOORS ON THE INPUT DATA SHEET- SECTION |
| | C403.2.1 FBC EC. |
| | |
| | 5) M101: THE CORRIDOR SHALL NOT BE USED TO RETURN AIR |
| | TO THE AIR HANDLER. PROVIDE DUCTED RETURNS- SECTION |
| | 601.2 FBC M. |
| | |
| | 6) PROVIDE AN ELECTRICAL PLAN AND ELECTRICAL SUB-PERMIT |
| | APPLICATION- SECTION 107.2.1 WPB. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |