Plan Review Details - Permit 20020153
Plan Review Stops For Permit 20020153
Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2021-05-04 Cont ID  
Sent By rrossano Date 2021-05-04 Time   Rev Time 0.00
Received By rrossano Date 2021-05-04 Time 14:27 Sent To  
Notes
2021-05-04 14:00:30PASSED WITH PROVISO: REVIEWED UNDER FORMAL ENG
 SUBMITTAL E18110026. ADDRESS ANY OUTSTANDING FIRE
 COMMENTS.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2020-03-13 Cont ID  
Sent By rrossano Date 2020-03-13 Time   Rev Time  
Received By rrossano Date 2020-03-13 Time   Sent To I
Notes
2020-03-13 07:46:16PLEASE ADDRESS FIRE COMMENTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-05-05 Cont ID  
Sent By pleduc Date 2021-05-05 Time   Rev Time 0.00
Received By pleduc Date 2021-05-05 Time 12:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2021-04-23 Cont ID  
Sent By pleduc Date 2021-04-23 Time   Rev Time 0.00
Received By pleduc Date 2021-04-23 Time 14:22 Sent To  
Notes
2021-04-23 14:36:55THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE NEW SITE SHEET SUBMITTED IS NO BETTER THAN THE
 OLD ONE AND NO MANUFACTURERS SPECIFICATION SHEETS WERE
 SUBMITTED.
  
 THE UNDERGROUND FIRE LINE IS REQUIRED TO BE INSTALLED,
 TESTED AND INSTALLED PER NFPA 24.
  
 FOR DISCUSSION AND REQUIREMENT PURPOSES, THIS WORK HAS
 ALREADY BEEN COMPLETED.
  
 IT HAS ALSO NOT BEEN INSPECTED.
  
 THE FIRE DEPARTMENT HAS NOT SEEN NOR WITNESSED NOR
 TESTED NOR INSPECTED THIS WORK.
  
 PLEASE HIGHLIGHT ON THE NEW SITE SHEET WHERE ALL THE
 FIRE LINE PIPE IS EXACTLY AND PROVIDE THE EQUIPMENT
 SPEC SHEETS FOR THE INSTALLED EQUIPMENT.
  
 ON APPROVAL OF THIS PERMIT AFTER THE ABOVE INFORMATION
 IS RECEIVED, AN INSPECTION SHOULD BE CALLED IN. A (1)
 UNDERGROUND JOINT SHALL BE DUG OUT, AT THE CONTRACTOR
 AND INSPECTOR AGREED CHOICE, AND THE BOLTS ON THAT
 JOINT WILL BE VERIFIED PER THE SUBMITTED SPEC SHEETS.
  
 IF THE COLLAR/ BOLTS ARE NOT INSTALLED PER THE
 MANUFACTURE, THE INSPECTION WILL FAIL AND ALL THE
 JOINTS WILL BE EXPOSED AND CORRECTED.
  
 IF THE INSPECTION PASSES ON THIS 1 JOINT, I WILL
 REQUEST THAT AN EOR SUPPLY A FORMAL SIGNED AND SEALED
 LETTER STATING THAT THE REMAINING JOINTS HAVE BEEN
 INSTALLED PER THE MANUFACTURE.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT AND AGREEMENT.
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-03-06 Cont ID  
Sent By bwoods Date 2020-03-06 Time   Rev Time  
Received By bwoods Date 2020-03-06 Time   Sent To M
Notes
2020-03-06 09:16:27PERMIT # 20020153
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 UNDERGROUND FIRE LINE SHALL COMPLY WITH NFPA 24 CHAPTER
 4 GENERAL REQUIREMENTS
  
 4.1.3 WORKING PLANS SHALL BE DRAWN TO AN INDICATED
 SCALE ON
 SHEETS OF UNIFORM SIZE, WITH A PLAN OF EACH FLOOR AS
 APPLICABLE,
 AND SHALL INCLUDE THE FOLLOWING ITEMS THAT PERTAIN TO
 THE DESIGN
 OF THE SYSTEM:
 (1) NAME OF OWNER
 (2) LOCATION, INCLUDING STREET ADDRESS
 (3) POINT OF COMPASS
 (4) A GRAPHIC REPRESENTATION OF THE SCALE USED ON ALL
 PLANS
 (5) NAME AND ADDRESS OF CONTRACTOR
 (6) SIZE AND LOCATION OF ALL WATER SUPPLIES
 (7) SIZE AND LOCATION OF STANDPIPE RISERS, HOSE
 OUTLETS, HAND
 HOSE, MONITOR NOZZLES, AND RELATED EQUIPMENT
  
 (8) THE FOLLOWING ITEMS THAT PERTAIN TO PRIVATE FIRE
 SERVICE
 MAINS:
 (A) SIZE
 (B) LENGTH
 (C) LOCATION
 (D) WEIGHT
 (E) MATERIAL
 (F) POINT OF CONNECTION TO CITY MAIN
 (G) SIZES, TYPES, AND LOCATIONS OF VALVES, VALVE
 INDICATORS,
 REGULATORS, METERS, AND VALVE PITS
 (H) DEPTH AT WHICH THE TOP OF THE PIPE IS LAID BELOW
 GRADE
 (I) METHOD OF RESTRAINT
  
  
 (9) THE FOLLOWING ITEMS THAT PERTAIN TO HYDRANTS:
  
 (A) SIZE AND LOCATION, INCLUDING SIZE AND NUMBER OF
 OUTLETS
 AND WHETHER OUTLETS ARE TO BE EQUIPPED WITH INDEPENDENT
 GATE VALVES
 (B) THREAD SIZE AND COUPLING ADAPTER SPECIFICATIONS IF
 DIFFERENT FROM NFPA 1963
 (C) WHETHER HOSE HOUSES AND EQUIPMENT ARE TO BE
 PROVIDED,
 AND BY WHOM
 (D) STATIC AND RESIDUAL HYDRANTS USED IN FLOW
 (E) METHOD OF RESTRAINT
 (10) SIZE, LOCATION, AND PIPING ARRANGEMENT OF FIRE
 DEPARTMENT
 CONNECTIONS
 4.1.4 THE WORKING PLAN SUBMITTAL SHALL INCLUDE THE
 MANUFACTURER?S
 INSTALLATION INSTRUCTIONS FOR ANY SPECIALLY LISTED
 EQUIPMENT,
 INCLUDING DESCRIPTIONS, APPLICATIONS, AND LIMITATIONS
 FOR
 ANY DEVICES, PIPING, OR FITTINGS.
  
 4.2 INSTALLATION WORK.
 4.2.1 INSTALLATION WORK SHALL BE PERFORMED BY FULLY
 EXPERIENCED
 AND RESPONSIBLE PERSONS.
 4.2.2 THE AUTHORITY HAVING JURISDICTION SHALL ALWAYS BE
 CONSULTED
 BEFORE THE INSTALLATION OR REMODELING OF PRIVATE FIRE
 SERVICE
 MAINS.
  
  
  
 BRITTANY WOODS
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4754
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-05-08 Cont ID  
Sent By pvalenti Date 2021-05-08 Time 07:51 Rev Time 0.00
Received By pvalenti Date 2021-05-03 Time 14:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-04-23 Cont ID  
Sent By ccarvaja Date 2021-04-23 Time 16:06 Rev Time 0.00
Received By ccarvaja Date 2021-04-09 Time 07:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-03-23 Cont ID  
Sent By hmoser Date 2020-03-23 Time 09:12 Rev Time 0.00
Received By hmoser Date 2020-03-13 Time 06:51 Sent To  
Notes
2020-03-13 13:37:063/13 ROUTED TO MECHANICAL INBOX
2020-03-13 06:53:25PUT IN ENGINEERING BOX, RM
2020-02-06 16:05:41ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-05-08 Cont ID  
Sent By pvalenti Date 2021-05-08 Time 07:11 Rev Time 0.00
Received By pvalenti Date 2021-05-05 Time 06:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-03-23 Cont ID  
Sent By hmoser Date 2020-03-23 Time 09:11 Rev Time 0.00
Received By hmoser Date 2020-03-23 Time 09:10 Sent To I
Notes
2020-03-23 09:11:39PLAN DENIED REFER TO FIRE COMMENTS HM.