| 2020-02-25 06:15:02 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND |
| | SIGNED/SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY THE |
| | ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS |
| | 471.003(2)(H); 471.025; WPB FBC 107.1 |
| | |
| | 2. DISCONNECT NOT CODE COMPLIANT WITH NEC 600.6A1 |
| | |
| | EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR FEEDER |
| | CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR OUT-LINE |
| | LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN EXTERNALLY |
| | OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL OPEN ALL |
| | UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN NEC |
| | 600.6(A)(1) |
| | |
| | 3. VALUE LOW FOR AMOUNT OF WORK SHOWN. |
| | |
| | CITY ORDINANCE AND FBC 109.3 BUILDING PERMIT |
| | VALUATIONS. IF, IN THE OPINION OF THE BUILDING |
| | OFFICIAL, THE CLAIMED VALUATION OF BUILDING, |
| | ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR |
| | PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE |
| | APPLICATION, THE PERMIT SHALL BE DENIED, UNLESS THE |
| | APPLICANT CAN SHOW DETAILED, QUANTITY ESTIMATES, AND/OR |
| | BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO |
| | MEET THE APPROVAL OF THE BUILDING OFFICIAL. FOR |
| | PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS |
| | SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| | |
| | 4. NEW CIRCUIT TO SIGN REQUIRES SEPARATE ELECTRICAL |
| | PERMIT BY LICENSED ELECTRICIAN. FBC 105.1, F.S. 489.505 |
| | (#19) AND F.A.C. 61G6-7.001 SPECIALTY ELECTRICAL |
| | CONTRACTORS (#2 SIGN SPECIALTY CONTRACTOR) |
| | |
| | PLEASE REFERENCE PERMIT NUMBER FOR SEPARATE ELECTRICAL |
| | PERMIT THATS REQUIRED TO SHOW COMPLIANCE. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |