| Plan Review Stops For Permit 20020015 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2020-02-06 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-02-06 |
Time |
14:46 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-02-06 |
Time |
06:58 |
Sent To |
|
|
| Notes |
| 2020-02-06 15:11:57 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | BUILDING REVIEW DENIED: | | | | | | 1. FBC B 107.1, PROVIDE (2) SURVEYS INDICATING THE | | | LOCATION OF ADDITIONS/NEW CONSTRUCTION. | | | 2. FBC R 4501.17, PROVIDE THE LOCATIONS AND | | | SPECIFICATIONS FOR SWIMMING POOL BARRIERS. | | | 3. FBC B 107.3.4.1, DEFERRED SUBMITTALS, ON THE PLANS, | | | LIST THE PRODUCT APPROVALS/SHOP DRAWINGS THAT ARE TO BE | | | DEFERRED, SUCH AS: RETRACTABLE SCREEN, ROOF TRUSS | | | ENGINEERING, INSULATION, ALL WINDOWS AND DOORS, AND | | | CURTAIN WALLS. ALL DEFERRED SUBMITTALS ARE TO BE REVIEW | | | STAMPED AND SIGNED BY DESIGNER OF RECORD. | | | 4. FBC B 107.1 PROVIDE (2) OF ALL SUBMITTED INFORMATION | | | INCLUDING PRODUCT APPROVALS. | | | 5. 61G15-23.003 PROCEDURES FOR PHYSICALLY SIGNING AND | | | SEALING PLANS, SPECIFICATIONS, REPORTS OR OTHER | | | DOCUMENTS. | | | ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER | | | DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN | | | ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025, | | | F.S., AND RULE 61G15-23.001, F.A.C. MUST BE PHYSICALLY | | | SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE | | | PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. | | | (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE | | | LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE | | | SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR | | | COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT BE | | | USED. | | | (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY | | | CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY | | | OVERLAPPING THE LICENSEE?S SIGNATURE ON EACH PAGE | | | REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL | | | NOT RENDER THE SIGNATURE ILLEGIBLE. | | | | | | | | | .PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY | | | RESULT IN NEW PLAN REVIEW COMMENTS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2020-03-01 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2020-03-01 |
Time |
11:57 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2020-03-01 |
Time |
11:57 |
Sent To |
I |
|
| Notes |
| 2020-03-01 11:56:19 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | BE ADVISED THAT PLAN SUBMISSION HAS MORE THAN 25 SHEETS | | | AND IS REQUIRED TO BE A DIGITAL SUBMISSION. ALL FUTURE | | | SUBMISSION SHALL BE IN DIGITAL FORMAT. WPB FBC 107.1 | | | | | | 1. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP | | | CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN. THE | | | RECEPTACLE OUTLET SHALL BE LOCATED ON A WALL OR | | | PARTITION THAT IS ADJACENT TO THE BASIN OR BASIN | | | COUNTERTOP, LOCATED ON THE COUNTERTOP, OR INSTALLED ON | | | THE SIDE OR FACE OF THE BASIN CABINET. THIS IS NOT | | | SHOWN FOR ALL BATHROOM BASINS. PROVIDE CORRECTION. NEC | | | 210.11(C)(3), 210.52(D); FBC RE E3901.6 | | | 2. NOTE 7 OF ELECTRICAL WIRING NOTES STATES THE 2011 | | | NEC AS BASIS OF DESIGN. THIS IS NOT THE CURRENT CODE. | | | PROVIDE CORRECTION. FBC PREFACE (ALSO SEE CURRENT CODES | | | ABOVE) | | | 3. NOTES UNDER PANEL SCHEDULES (2 LOCATIONS) STATE THAT | | | LIGHTING IN CLOSETS SHALL COMPLY WITH NEC 410.8 . THIS | | | CODE SECTION DOES NOT APPLY TO CLOSET LIGHTING. PROVIDE | | | CORRECTION OR NOTE OR COMPLIANCE. NEC 410.16; FBC RE | | | E4003.12 | | | 4. NOTES UNDER PANEL SCHEDULES (2 LOCATIONS) STATE THAT | | | RECEPTACLES SHALL BE TAMPER RESISTANT PER NEC 406.11. | | | THIS CODE SECTION DOES NOT APPLY TO TAMPER RESISTANT | | | RECEPTACLES. PROVIDE CORRECTION. NEC 406.12; FBC RE | | | E4002.14 | | | 5. SMOKE ALARMS MUST BE INSTALLED AT LEAST 3 FEET FROM | | | BATHROOM DOOR, 3 FEET FROM CEILING FANS, AND 3 FEET | | | FROM ANY MECHANICAL DUCT. PROVIDE CORRECTIONS. FBC RE | | | R314.3(4), NFPA 72:29.8.3.4 | | | 6. ALL RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS | | | SHALL HAVE GFCI PROTECTION. PROVIDE CORRECTION. NEC | | | 210.8(A)(9); FBC RE E3902.9 | | | 7. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING | | | REQUIREMENTS FOR RECEPTACLE OUTLETS. RECEPTACLES SHALL | | | BE INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY | | | ALONG THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 | | | FEET FROM A RECEPTACLE OUTLET. THE WALL SPACING | | | REQUIREMENTS FOR KITCHEN COUNTER SPACE STATE THAT | | | RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT NO POINT | | | ALONG THE WALL LINE IS MORE THAN 24 INCHES MEASURED | | | HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT SPACE. | | | THE PLAN PROVIDED DOES NOT MEET THIS CODE IN SOME | | | AREAS. PROVIDE CORRECTION. NEC 210.52(C)(1); FBC RE | | | E3901 | | | 8. | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH | | | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. | | | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL | | | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. | | | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD | | | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2020-02-05 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2020-02-05 |
Time |
15:28 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2020-02-05 |
Time |
15:28 |
Sent To |
|
|
| Notes |
| 2020-02-05 15:29:01 | GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN | | | THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN | | | PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND PLANS | | | WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE | | | RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT | | | REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE PER | | | THE WPB AMENDMENTS TO FBC SEC. 107.2.1. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-06-05 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2020-06-05 |
Time |
15:23 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2020-06-05 |
Time |
12:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2020-03-01 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-02-03 |
Time |
13:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2020-02-06 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-02-06 |
Time |
07:55 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-02-06 |
Time |
06:58 |
Sent To |
|
|
| Notes |
| 2020-02-06 07:56:49 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | IMPACT FEES - PAPER SUBMITTALS | | | | | | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL | | | (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE | | | PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE | | | RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS | | | APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE | | | QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE | | | FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD | | | MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2020-02-06 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-02-06 |
Time |
13:28 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-02-06 |
Time |
06:58 |
Sent To |
|
|
| Notes |
| 2020-02-06 13:37:49 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | MECHANICAL REVIEW DENIED: | | | | | | 1. FBC R M 1305.1.4/1401.4, PROVIDE ENGINEER'S | | | CONNECTION DETAILS FOR EXTERIOR CONDENSING UNITS TO | | | PADS. | | | 2. FBC BN 107.1, PLEASE PROVIDE (2) COMPLETED AND | | | SIGNED ORIGINALS OF ENERGY AND A/C CALCULATIONS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2020-02-05 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2020-02-05 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2020-02-05 |
Time |
07:20 |
Sent To |
|
|
| Notes |
| 2020-02-05 15:32:06 | 02/05/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. ISOMETRIC DOES NOT MATCH THE LAYOUT ON P1.01 AS | | | THESE PLANS BECOME PART OF CITY ARCHIVES FOR DIRECTION | | | AND LOCATION FOR FUTURE REMODELING OF PLUMBING | | | FIXTURES, PLEASE TRY TO MATCH AS CLOSE AS POSSIBLE PER | | | THE WPB AMENDMENT TO FBC SEC. 107.2.1.3 QUALITY OF | | | BUILDING PLANS. | | | | | | 2. THERE ARE 2 WET VENTS ON WASHING MACHINES STACK NEED | | | TO BE DOWNSTREAM OF THE INTERCONNECTION FROM BATHROOM | | | GROUP PER THE 2017 FBC SEC. R 3107.2. | | | | | | 3. PLEASE AND CLEAN OUT WHERE REQUIRED WITH 10' FROM | | | ENTRY TO THE BUILDING PER THE 2017 FBC SEC. R 3005.2.3 | | | | | | 4. IN GUESS ROOM 1 (122) ON THE WASHING MACHINE | | | STACKABLE THE VALVES SHALL BE ACCESSIBLE PER THE 2017 | | | FBC SEC. R 2903.9.3. | | | | | | 5. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED | | | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS | | | TO THE FBC SEC. 105.1. | | | | | | 6. A SUB GAS PERMIT IS REQUIRED BY A LICENSED | | | CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS | | | TO THE FBC SEC. 105.1. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | | [email protected] | | | 561-805-6720 | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2020-02-06 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-02-06 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-02-06 |
Time |
06:58 |
Sent To |
|
|
| Notes |
| 2020-02-06 14:46:26 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | ROOFING REVIEW DENIED: | | | | | | FBC B 107.2.1 PROVIDE ROOFING MATERIAL PRODUCT | | | APPROVALS/SPECIFICATIONS. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2020-02-12 |
|
|
Cont ID |
|
| Sent By |
rfalcone |
Date |
2020-02-12 |
Time |
15:49 |
Rev Time |
0.00 |
| Received By |
rfalcone |
Date |
2020-02-12 |
Time |
15:49 |
Sent To |
I |
|
| Notes |
| 2020-02-12 15:50:00 | 2/12/20 FAILED. | | | | | | PLEASE PROVIDE A SURVEY OF THE SUBJECT SITE WITH THE | | | ADDITIONS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME. | | | | | | RACHEL FALCONE, ASSOCIATE PLANNER | | | DEVELOPMENT SERVICES DEPARTMENT | | | E-MAIL: [email protected] | | | TEL: (561) 822-1442 | | | |
|
|