Plan Review Details - Permit 20020015
Plan Review Stops For Permit 20020015
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-02-06 Cont ID  
Sent By pvalenti Date 2020-02-06 Time 14:46 Rev Time 0.00
Received By pvalenti Date 2020-02-06 Time 06:58 Sent To  
Notes
2020-02-06 15:11:57***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 1. FBC B 107.1, PROVIDE (2) SURVEYS INDICATING THE
 LOCATION OF ADDITIONS/NEW CONSTRUCTION.
 2. FBC R 4501.17, PROVIDE THE LOCATIONS AND
 SPECIFICATIONS FOR SWIMMING POOL BARRIERS.
 3. FBC B 107.3.4.1, DEFERRED SUBMITTALS, ON THE PLANS,
 LIST THE PRODUCT APPROVALS/SHOP DRAWINGS THAT ARE TO BE
 DEFERRED, SUCH AS: RETRACTABLE SCREEN, ROOF TRUSS
 ENGINEERING, INSULATION, ALL WINDOWS AND DOORS, AND
 CURTAIN WALLS. ALL DEFERRED SUBMITTALS ARE TO BE REVIEW
 STAMPED AND SIGNED BY DESIGNER OF RECORD.
 4. FBC B 107.1 PROVIDE (2) OF ALL SUBMITTED INFORMATION
 INCLUDING PRODUCT APPROVALS.
 5. 61G15-23.003 PROCEDURES FOR PHYSICALLY SIGNING AND
 SEALING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS.
 ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN
 ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025,
 F.S., AND RULE 61G15-23.001, F.A.C. MUST BE PHYSICALLY
 SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT BE
 USED.
 (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY
 CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY
 OVERLAPPING THE LICENSEE?S SIGNATURE ON EACH PAGE
 REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL
 NOT RENDER THE SIGNATURE ILLEGIBLE.
  
  
 .PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS MAY
 RESULT IN NEW PLAN REVIEW COMMENTS.

Review Stop E ELECTRICAL
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-03-01 Cont ID  
Sent By jpearson Date 2020-03-01 Time 11:57 Rev Time 0.00
Received By jpearson Date 2020-03-01 Time 11:57 Sent To I
Notes
2020-03-01 11:56:19CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 BE ADVISED THAT PLAN SUBMISSION HAS MORE THAN 25 SHEETS
 AND IS REQUIRED TO BE A DIGITAL SUBMISSION. ALL FUTURE
 SUBMISSION SHALL BE IN DIGITAL FORMAT. WPB FBC 107.1
  
 1. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN. THE
 RECEPTACLE OUTLET SHALL BE LOCATED ON A WALL OR
 PARTITION THAT IS ADJACENT TO THE BASIN OR BASIN
 COUNTERTOP, LOCATED ON THE COUNTERTOP, OR INSTALLED ON
 THE SIDE OR FACE OF THE BASIN CABINET. THIS IS NOT
 SHOWN FOR ALL BATHROOM BASINS. PROVIDE CORRECTION. NEC
 210.11(C)(3), 210.52(D); FBC RE E3901.6
 2. NOTE 7 OF ELECTRICAL WIRING NOTES STATES THE 2011
 NEC AS BASIS OF DESIGN. THIS IS NOT THE CURRENT CODE.
 PROVIDE CORRECTION. FBC PREFACE (ALSO SEE CURRENT CODES
 ABOVE)
 3. NOTES UNDER PANEL SCHEDULES (2 LOCATIONS) STATE THAT
 LIGHTING IN CLOSETS SHALL COMPLY WITH NEC 410.8 . THIS
 CODE SECTION DOES NOT APPLY TO CLOSET LIGHTING. PROVIDE
 CORRECTION OR NOTE OR COMPLIANCE. NEC 410.16; FBC RE
 E4003.12
 4. NOTES UNDER PANEL SCHEDULES (2 LOCATIONS) STATE THAT
 RECEPTACLES SHALL BE TAMPER RESISTANT PER NEC 406.11.
 THIS CODE SECTION DOES NOT APPLY TO TAMPER RESISTANT
 RECEPTACLES. PROVIDE CORRECTION. NEC 406.12; FBC RE
 E4002.14
 5. SMOKE ALARMS MUST BE INSTALLED AT LEAST 3 FEET FROM
 BATHROOM DOOR, 3 FEET FROM CEILING FANS, AND 3 FEET
 FROM ANY MECHANICAL DUCT. PROVIDE CORRECTIONS. FBC RE
 R314.3(4), NFPA 72:29.8.3.4
 6. ALL RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS
 SHALL HAVE GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8(A)(9); FBC RE E3902.9
 7. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR RECEPTACLE OUTLETS. RECEPTACLES SHALL
 BE INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6
 FEET FROM A RECEPTACLE OUTLET. THE WALL SPACING
 REQUIREMENTS FOR KITCHEN COUNTER SPACE STATE THAT
 RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT NO POINT
 ALONG THE WALL LINE IS MORE THAN 24 INCHES MEASURED
 HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT SPACE.
 THE PLAN PROVIDED DOES NOT MEET THIS CODE IN SOME
 AREAS. PROVIDE CORRECTION. NEC 210.52(C)(1); FBC RE
 E3901
 8.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2020-02-05 Cont ID  
Sent By lcrespo Date 2020-02-05 Time 15:28 Rev Time 0.00
Received By lcrespo Date 2020-02-05 Time 15:28 Sent To  
Notes
2020-02-05 15:29:01GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN
 THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN
 PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND PLANS
 WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE
 RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT
 REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE PER
 THE WPB AMENDMENTS TO FBC SEC. 107.2.1.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-06-05 Cont ID  
Sent By cpuell Date 2020-06-05 Time 15:23 Rev Time 0.00
Received By cpuell Date 2020-06-05 Time 12:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-03-01 Time   Rev Time 0.00
Received By lmarchan Date 2020-02-03 Time 13:40 Sent To  
Notes
2020-02-04 13:40:56R33

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-02-06 Cont ID  
Sent By pvalenti Date 2020-02-06 Time 07:55 Rev Time 0.00
Received By pvalenti Date 2020-02-06 Time 06:58 Sent To  
Notes
2020-02-06 07:56:49***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 IMPACT FEES - PAPER SUBMITTALS
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-02-06 Cont ID  
Sent By pvalenti Date 2020-02-06 Time 13:28 Rev Time 0.00
Received By pvalenti Date 2020-02-06 Time 06:58 Sent To  
Notes
2020-02-06 13:37:49***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 MECHANICAL REVIEW DENIED:
  
 1. FBC R M 1305.1.4/1401.4, PROVIDE ENGINEER'S
 CONNECTION DETAILS FOR EXTERIOR CONDENSING UNITS TO
 PADS.
 2. FBC BN 107.1, PLEASE PROVIDE (2) COMPLETED AND
 SIGNED ORIGINALS OF ENERGY AND A/C CALCULATIONS.

Review Stop P PLUMBING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-02-05 Cont ID  
Sent By lcrespo Date 2020-02-05 Time 15:29 Rev Time 0.00
Received By lcrespo Date 2020-02-05 Time 07:20 Sent To  
Notes
2020-02-05 15:32:0602/05/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ISOMETRIC DOES NOT MATCH THE LAYOUT ON P1.01 AS
 THESE PLANS BECOME PART OF CITY ARCHIVES FOR DIRECTION
 AND LOCATION FOR FUTURE REMODELING OF PLUMBING
 FIXTURES, PLEASE TRY TO MATCH AS CLOSE AS POSSIBLE PER
 THE WPB AMENDMENT TO FBC SEC. 107.2.1.3 QUALITY OF
 BUILDING PLANS.
  
 2. THERE ARE 2 WET VENTS ON WASHING MACHINES STACK NEED
 TO BE DOWNSTREAM OF THE INTERCONNECTION FROM BATHROOM
 GROUP PER THE 2017 FBC SEC. R 3107.2.
  
 3. PLEASE AND CLEAN OUT WHERE REQUIRED WITH 10' FROM
 ENTRY TO THE BUILDING PER THE 2017 FBC SEC. R 3005.2.3
  
 4. IN GUESS ROOM 1 (122) ON THE WASHING MACHINE
 STACKABLE THE VALVES SHALL BE ACCESSIBLE PER THE 2017
 FBC SEC. R 2903.9.3.
  
 5. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 6. A SUB GAS PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2020-02-06 Cont ID  
Sent By pvalenti Date 2020-02-06 Time 14:30 Rev Time 0.00
Received By pvalenti Date 2020-02-06 Time 06:58 Sent To  
Notes
2020-02-06 14:46:26***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 ROOFING REVIEW DENIED:
  
 FBC B 107.2.1 PROVIDE ROOFING MATERIAL PRODUCT
 APPROVALS/SPECIFICATIONS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-02-12 Cont ID  
Sent By rfalcone Date 2020-02-12 Time 15:49 Rev Time 0.00
Received By rfalcone Date 2020-02-12 Time 15:49 Sent To I
Notes
2020-02-12 15:50:002/12/20 FAILED.
  
 PLEASE PROVIDE A SURVEY OF THE SUBJECT SITE WITH THE
 ADDITIONS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 RACHEL FALCONE, ASSOCIATE PLANNER
 DEVELOPMENT SERVICES DEPARTMENT
 E-MAIL: [email protected]
 TEL: (561) 822-1442
  