| Plan Review Stops For Permit 20011283 |
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
2 |
Status |
P |
Date |
2020-08-22 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-08-22 |
Time |
07:34 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-08-20 |
Time |
11:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2020-01-31 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-01-31 |
Time |
16:21 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-01-31 |
Time |
16:21 |
Sent To |
|
|
| Notes |
| 2020-01-31 16:27:12 | WRITTEN NOTIFICATION TO THE HEALTH DEPARTMENT IS | | | REQUIRED FOR A RESIDENTIAL BUILDING HAVING 4 OR LESS | | | DWELLING UNITS IF IT HAS BEEN USED FOR COMMERCIAL | | | PURPOSES OR IT IS BEING DEMOLISHED AS PART OF A | | | COMMERCIAL OR PUBLIC PROJECT (WHICH INCLUDES | | | CITY-INITIATED DEMOLITION OF A SINGLE FAMILY | | | RESIDENCE). IF THIS PROJECT IS SUBJECT TO ASBESTOS | | | NOTIFICATION REQUIREMENTS, PROVIDE A SIGNED | | | ACKNOWLEDGMENT FROM THE CONTRACTOR STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF THE ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. IF THIS PROJECT IS NOT SUBJECT TO | | | ASBESTOS NOTIFICATION REQUIREMENTS, THE CONTRACTOR IS | | | TO PROVIDE A SIGNED STATEMENT ON LETTERHEAD EXPLAINING | | | WHY IT IS EXEMPT (FOR EXAMPLE, ?THIS PROJECT IS EXEMPT | | | BECAUSE IT IS A SINGLE FAMILY RESIDENCE AND IS NOT A | | | PART OF A COMMERCIAL OR PUBLIC PROJECT, AND IS NOT A | | | CITY-INITIATED DEMOLITION?). | | | | | | ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS | | | CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2020-09-16 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-09-16 |
Time |
13:06 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-09-16 |
Time |
07:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2020-08-24 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-08-22 |
Time |
08:32 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-08-20 |
Time |
11:42 |
Sent To |
|
|
| Notes |
| 2020-08-22 08:35:33 | ABO WAIVES SOILS REPORT REQUIREMENT. PROVIDE COMPACTION | | | TEST TO CITY INSPECTOR AT FOUNDATION INSPECTION, CT | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2020-06-23 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-06-23 |
Time |
09:40 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-06-22 |
Time |
11:37 |
Sent To |
|
|
| Notes |
| 2020-06-23 10:54:07 | PLAN REVIEW - BUILDING | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER BUILDING - PX3169 | | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. BUILDING DESIGN CRITERIA IS MISSING FROM COVER PAGE | | | A1.O. | | | 107.2 CONSTRUCTION DOCUMENTS. | | | | | | 2. MAX BUILDING HEIGHT IS STATED AS 40 FEET. THIS IS | | | INCORRECT. | | | 107.2 CONSTRUCTION DOCUMENTS. | | | | | | 3. ALL STRUCTURAL PLAN PAGES ARE MISSING FROM | | | SUBMITTAL. | | | 107.2 CONSTRUCTION DOCUMENTS. | | | | | | 4. PROVIDE A COMPREHENSIVE SCOPE OF WORK. | | | 107.2 CONSTRUCTION DOCUMENTS. | | | | | | 5. PROVIDE A SOILS REPORT. | | | FBC 1803.1 GENERAL.GEOTECHNICAL INVESTIGATIONS SHALL BE | | | CONDUCTED IN ACCORDANCE WITH SECTION 1803.2 AND | | | REPORTED IN ACCORDANCE WITH SECTION 1803.6. WHERE | | | REQUIRED BY THE BUILDING OFFICIAL OR WHERE GEOTECHNICAL | | | INVESTIGATIONS INVOLVE IN-SITU TESTING, LABORATORY | | | TESTING OR ENGINEERING CALCULATIONS, SUCH | | | INVESTIGATIONS SHALL BE CONDUCTED BY A REGISTERED | | | DESIGN PROFESSIONAL. | | | | | | 6. PROVIDE A DEMO PLAN. | | | 107.2 CONSTRUCTION DOCUMENTS. | | | | | | 7. PROVIDE AN EXISTING FLOOR PLAN. | | | 107.2 CONSTRUCTION DOCUMENTS. | | | | | | 8. PROVIDE AN ENERGY SUBMITTAL. | | | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. | | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 | | | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE | | | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE | | | COMPLIANCE BY SECTION 405. | | | | | | 9. PROVIDE A WINDOW SCHEDULE WITH ROUGH OPENINGS AND | | | DESIGN PRESSURES. YOU MAY ALSO PLACE THIS INFORMATION | | | ON THE PLANS NEXT TO EACH OPENING. | | | 107.2 CONSTRUCTION DOCUMENTS. | | | | | | 10. PROVIDE PRODUCT APPROVALS FOR PROPOSED WINDOWS AND | | | MULLIONS. | | | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE WINDOW SUBMITTALS. | | | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED. | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2020-08-22 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-08-22 |
Time |
07:42 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-08-20 |
Time |
15:33 |
Sent To |
|
|
| Notes |
| 2020-08-22 07:45:08 | NO NOTES |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2020-08-11 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-08-11 |
Time |
14:42 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-08-11 |
Time |
14:32 |
Sent To |
|
|
| Notes |
| 2020-08-11 14:45:19 | PLAN REVIEW - ELECTRICAL | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER BUILDING - PX3169 | | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | 2ND REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. WALL RECEPTACLE OUTLETS ARE MISSING IN THE TWO FRONT | | | BEDROOMS. CANNOT VERIFY SPACING PER E3901.2.1 SPACING. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2020-06-23 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-06-23 |
Time |
11:18 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-06-22 |
Time |
11:36 |
Sent To |
|
|
| Notes |
| 2020-06-23 11:19:55 | PLAN REVIEW - ELECTRICAL | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER BUILDING - PX3169 | | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PROVIDE AN EXISTING ELECTRICAL PLAN. | | | 107.2 CONSTRUCTION DOCUMENTS. | | | | | | 2. PROVIDE A NEW PANEL SCHEDULE. | | | PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED | | | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, | | | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY | | | WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5, | | | 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902 | | | | | | 3. PROVIDE A SERVICE RISER DIAGRAHM. | | | PROVIDE RISER DIAGRAM OF EXISTING SERVICE. NEC 215.5; | | | WPB FBC 107.2.1 | | | | | | 4. PROVIDE NEW LOAD CALCULATIONS. | | | PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING | | | AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS | | | ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2 | | | | | | 5. IDENTIFY LOCATION OF SERVICE AND PANEL BOARD ON | | | PLAN. | | | 107.2 CONSTRUCTION DOCUMENTS. | | | | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2020-09-16 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-09-16 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-09-16 |
Time |
07:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2020-08-22 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-08-22 |
Time |
07:13 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-08-20 |
Time |
15:33 |
Sent To |
|
|
| Notes |
| 2020-08-22 07:34:33 | PLAN REVIEW - FUEL GAS | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER BUILDING - PX3169 | | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | 2017 FBC RES-FUEL GAS CHPT. 24 | | | | | | 2ND REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS FROM 1ST REVIEW AND | | | RE-SUBMIT | | | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED. | | | PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED | | | SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN | | | PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER | | | PREVIOUS COMMENTS. | | | | | | 1ST REVIEW COMMENTS: | | | | | | 1) SHT. P-2 - THE GAS CALCULATION NOTES SHOW A BTU LOAD | | | OF 607,000 BTU'S BUT THE PLANS SHOW A TOTAL BTU LOAD OF | | | 207,000 BTU'S. CLARIFY. (GAS CALCULATIONS ON PLAN PAGE | | | P-2 INDICATE POOL HEATER AS EXISTING. PER NOTE BELOW, | | | THERE IS NO RECORD OF THE POOL HEATER BEING PERMITTED. | | | INCLUDE THE POOL HEATER ON ISO AND IDENTIFY LOCATION ON | | | GAS PLAN. SHOW PIPE TYPE, SIZE AND LENGTH. PROVIDE | | | MANUFACTURERES INSTALLATION INSTRUCTIONS) | | | | | | 2) LIST THE BTU LOAD OF EACH APPLIANCE ON THE SYSTEM. | | | REFER TO THE 2017 FBC-FUEL GAS SECS.401.8, 402.2, AND | | | TABLES 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC. | | | G2413.3, G2413.4 AND TABLES G2413.4 (1 ) THROUGH | | | G2413.4 (21). (SEE COMMENTS ABOVE) | | | | | | 3) SUBMIT MANUFACTURERS SPECIFICATION SHEETS / | | | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY | | | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND | | | FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017 | | | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED | | | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS | | | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF | | | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. | | | (MANUFACTURERS SPECIFICATIONS NOT SUBMITTED FOR REVIEW) | | | | | | NOTE: CITY RECORDS ONLY SHOW A GAS PERMIT FOR THE | | | TANKLESS WATER HEATER AND THE RANGE. ANY OTHER GAS | | | APPLIANCES THAT ARE CURRENTLY ON THIS SYSTEM MUST BE | | | PERMITTED. (POOL HEATER SHALL BE PERMITTED AND | | | INSPECTED. SEE COMMENTS ABOVE) | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2020-08-11 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2020-08-11 |
Time |
05:28 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2020-08-11 |
Time |
05:20 |
Sent To |
|
|
| Notes |
| 2020-08-11 05:28:22 | 1) SHT. P-2 - THE GAS CALCULATION NOTES SHOW A BTU LOAD | | | OF 607,000 BTU'S BUT THE PLANS SHOW A TOTAL BTU LOAD OF | | | 207,000 BTU'S. CLARIFY. | | | 2) LIST THE BTU LOAD OF EACH APPLIANCE ON THE SYSTEM. | | | REFER TO THE 2017 FBC-FUEL GAS SECS.401.8, 402.2, AND | | | TABLES 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC. | | | G2413.3, G2413.4 AND TABLES G2413.4 (1 ) THROUGH | | | G2413.4 (21). | | | 3) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / | | | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY | | | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND | | | FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017 | | | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED | | | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS | | | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF | | | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. | | | NOTE: CITY RECORDS ONLY SHOW A GAS PERMIT FOR THE | | | TANKLESS WATER HEATER AND THE RANGE. ANY OTHER GAS | | | APPLIANCES THAT ARE CURRENTLY ON THIS SYSTEM MUST BE | | | PERMITTED. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2020-09-16 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-09-16 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-09-15 |
Time |
11:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2020-08-24 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2020-08-24 |
Time |
07:20 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-07-30 |
Time |
15:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-06-23 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-06-23 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-06-17 |
Time |
11:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2020-01-31 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-01-31 |
Time |
16:18 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-01-31 |
Time |
16:18 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2020-08-24 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2020-08-24 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2020-08-24 |
Time |
07:20 |
Sent To |
|
|
| Notes |
| 2020-08-24 09:53:54 | RECEIPT - MU-2020-32351 - $0.00 | | 2020-08-24 07:20:31 | 8/24/20 EMAILED IMPACT FEE OFFICE FOR REVIEW. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2020-01-31 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-01-31 |
Time |
16:21 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-01-31 |
Time |
16:21 |
Sent To |
|
|
| Notes |
| 2020-01-31 16:23:59 | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL | | | (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE | | | PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE | | | RETURNED STAMPED AND WITH A COPY OF THE PAID RECEIPT AS | | | APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE | | | QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE | | | FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD | | | MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2020-08-04 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2020-08-04 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2020-08-04 |
Time |
10:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2020-06-23 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-06-23 |
Time |
10:57 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-06-22 |
Time |
11:36 |
Sent To |
|
|
| Notes |
| 2020-06-23 11:00:05 | PLAN REVIEW - MECHANICAL | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER BUILDING - PX3169 | | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PROVIDE A MECHANICAL PLAN WITH DETAILED SCOPE OF | | | WORK. SHOW EXISTING AND PROPOSED WORK. | | | 107.2 CONSTRUCTION DOCUMENTS. | | | | | | 2. PROVIDE AN ENERGY SUBMITTAL. | | | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. | | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 | | | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE | | | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE | | | COMPLIANCE BY SECTION 405. | | | | | | 3. PROVIDE DETAIL FOR EQUIPMENT PAD. | | | 107.2 CONSTRUCTION DOCUMENTS. | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
7 |
Status |
N |
Date |
2020-09-16 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-09-16 |
Time |
12:58 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-09-16 |
Time |
07:24 |
Sent To |
|
|
| Notes |
| 2020-09-16 13:00:01 | ACTUAL CASH VALUE (ACV) APPRAISAL RECIEVED AND | | | APPROVED. COMPLIANCE WITH FEMA SUBSTANTIAL IMPROVEMENT | | | IS NOT REQUIRED. PAPER COPY OF APPRAISAL WITH ORIGINAL | | | SIGNATURE OF APPRAISER SENT TO SCANNING. CT | | | | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
6 |
Status |
F |
Date |
2020-08-20 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-08-20 |
Time |
11:44 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-08-20 |
Time |
08:19 |
Sent To |
|
|
| Notes |
| 2020-08-20 11:50:16 | PLAN REVIEW - NFIP | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER BUILDING - PX3169 | | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | 6TH REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | OVERVIEW: | | | | | | PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD AREA | | | (SFHA) WITH TWO AE ZONES. AE 6 AND AE 7. BASED ON THE | | | VALUE OF THIS SUBMITTAL WITH THE ADDITIONAL VALUE OF | | | WORK ON THE PROPERTY FOR THE LAST FIVE YEARS, THE WORK | | | ON THE PROPERTY IS CONSIDERED A SUBSTANTIAL IMPROVEMENT | | | PER FEMA P-758. THE OWNER HAS ELECTED TO PROVIDE A NEW | | | APPRTAISAL OF THE PROPERTY TO RAISE THE VALUE OF THE | | | SUBJECT IMPROVEMENTS ABOVE FEMA'S 50% RULE. | | | | | | NOTE: 6TH REVIEW | | | | | | A NEW APPRAISAL IS BEING SUBMITTED FOR REVIEW. THIS | | | APPRAISAL IS A MARKET VALUE APPRAISAL OF THE SUBJECT | | | PROPERTY BASED ON COMPARABLE SALES ANALYSIS. | | | | | | FEMA REQUIRES AN ACTUAL CASH VALUE APPRAISAL PER FEMA | | | DESK REFERENCE P-758 SECTION 4.5.3. AN ACTUAL CASH | | | VALUE APPRAISAL IS THE COST TO REPLACE A BUILDING ON | | | THE SAME PARCEL WITH A NEW BUILDING OF LIKE KIND AND | | | QUALITY, MINUS DEPRECIATION DUE TO AGE, USE AND | | | NEGLECT. | | | | | | PROVIDE A NFIP COMPLIANT APPRAISAL TO ADDRESS THE SI/SD | | | CLASSIFICATION OF THIS STRUCTURE. | | | | | | THE APPRAISAL SHALL: | | | | | | 1. BE NARRATIVE BASED. | | | 2. PROVIDE ACTUAL REPLACEMENT COST. | | | 3. PROVIDE DEPRECIATION. | | | 4. PROVIDE SOURCES SUPPORTING COST AND DEPRECIATION. | | | 5. STATE INTENDED USER - NFIP REQUIRES THE OWNER AND | | | THE FLOOD PLAIN MANAGER (ROBERT BROWN, BO, CITY OF WPB, | | | FL) TO BE LISTED AS USERS. | | | 6. STATE INTENDED USE - I.E. "TO SUPPORT A BUILDING | | | PERMIT APPLICATION SUBJECT TO SIGNIFICANT | | | IMPROVEMENTS/SIGNIFICANT DAMAGE (SI/SD) UNDER NFIP | | | REGULATIONS. | | | 7. CLEARLY DESCRIBE THE BUILDING. | | | 8. PROVIDE PHOTOGRAPHIC EVIDENCE. | | | 9. STATE METHODOLOGY USED TO DETERMINE DEPRECIATION. | | | 10. PROVIDE ADEQUATE DOCUMENTATION SUPPORTING THE | | | REPLACEMENT COST AND DEPRECIATION, ( I.E. | | | MARSHALL/SWIFT, ETC.) | | | | | | | | | NOTE: 5TH REVIEW | | | | | | THE APPRAISAL PROVIDED FOR THE 5TH NFIP REVIEW ONLY | | | NEEDED THE FOLLOWING CHANGES. | | | | | | 1. PROVIDE A COPY OF APPRAISAL WITH ORIGINAL SINATURE | | | OF APPRAISER. | | | | | | SEE COMMENTS BELOW FROM 3RD NFIP REVIEW. | | | | | | 1. APPRAISAL ESTABLISHES (ACV) ACTUAL COST VALUE | | | (REPLACEMENT COST MINUS DEPRECIATION) AT $317,000.00. | | | VALUE OF PROPOSED RES REMOD PERMIT 20011283 PLUS FIVE | | | YEAR TAIL EQUALS $140,078.00. PROPERTY IS NO LONGER | | | REQUIRED TO COMPLY WITH FEMA SUBSTANTIAL IMPROVEMENT | | | REQUIREMENTS. | | | NOTE: DATE OF ORIGINAL APPRAISAL IS 04/14/2019 (COVER | | | PAGE). APPRAISER DATED REVISED REPORT (SEE PG. 10 OF | | | 27) ON 03/11/2020. PLEASE UPDATE REPORT DATE TO | | | 03/11/2020 (COVER PAGE). APPRAISER TO PROVIDE APPRAISAL | | | WITH ORIGINAL SIGNATURE PRIOR TO PERMIT. CT | | | | | | | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
5 |
Status |
F |
Date |
2020-06-22 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-06-22 |
Time |
13:59 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-06-11 |
Time |
10:16 |
Sent To |
|
|
| Notes |
| 2020-06-22 13:45:02 | PLAN REVIEW - NFIP | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER BUILDING - PX3169 | | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | 5TH REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | OVERVIEW: PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD | | | AREA (SFHA) WITH TWO AE ZONES. AE 6 AND AE 7. BASED ON | | | THE VALUE OF THIS SUBMITTAL WITH THE ADDITIONAL VALUE | | | OF WORK ON THE PROPERTY FOR THE LAST FIVE YEARS, THE | | | WORK ON THE PROPERTY IS CONSIDERED A SUBSTANTIAL | | | IMPROVEMENT PER FEMA P-758. THE OWNER HAS ELECTED TO | | | PROVIDE A NEW APPRTAISAL OF THE PROPERTY TO RAISE THE | | | VALUE OF THE SUBJECT IMPROVEMENTS ABOVE FEMA'S 50% | | | RULE. | | | | | | 1. PROVIDE A COPY OF APPRAISAL WITH ORIGINAL SINATURE | | | OF APPRAISER. | | | | | | SEE COMMENTS BELOW FROM 3RD NFIP REVIEW. | | | | | | 1. APPRAISAL ESTABLISHES (ACV) ACTUAL COST VALUE | | | (REPLACEMENT COST MINUS DEPRECIATION) AT $317,000.00. | | | VALUE OF PROPOSED RES REMOD PERMIT 20011283 PLUS FIVE | | | YEAR TAIL EQUALS $140,078.00. PROPERTY IS NO LONGER | | | REQUIRED TO COMPLY WITH FEMA SUBSTANTIAL IMPROVEMENT | | | REQUIREMENTS. | | | NOTE: DATE OF ORIGINAL APPRAISAL IS 04/14/2019 (COVER | | | PAGE). APPRAISER DATED REVISED REPORT (SEE PG. 10 OF | | | 27) ON 03/11/2020. PLEASE UPDATE REPORT DATE TO | | | 03/11/2020 (COVER PAGE). APPRAISER TO PROVIDE APPRAISAL | | | WITH ORIGINAL SIGNATURE PRIOR TO PERMIT. CT |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
4 |
Status |
F |
Date |
2020-07-20 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-03-28 |
Time |
11:40 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-03-27 |
Time |
16:19 |
Sent To |
|
|
| Notes |
| 2020-03-28 11:51:59 | APPRAISAL ESTABLISHES (ACV) ACTUAL COST VALUE | | | (REPLACEMENT COST MINUS DEPRECIATION) AT $317,000.00. | | | VALUE OF PROPOSED RES REMOD PERMIT 20011283 PLUS FIVE | | | YEAR TAIL EQUALS $140,078.00. PROPERTY IS NO LONGER | | | REQUIRED TO COMPLY WITH FEMA SUBSTANTIAL IMPROVEMENT | | | REQUIREMENTS. | | | NOTE: DATE OF ORIGINAL APPRAISAL IS 04/14/2019 (COVER | | | PAGE). APPRAISER DATED REVISED REPORT (SEE PG. 10 OF | | | 27) ON 03/11/2020. PLEASE UPDATE REPORT DATE TO | | | 03/11/2020 (COVER PAGE). APPRAISER TO PROVIDE APPRAISAL | | | WITH ORIGINAL SIGNATURE PRIOR TO PERMIT. CT |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
3 |
Status |
F |
Date |
2020-03-25 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-03-25 |
Time |
06:57 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-03-25 |
Time |
06:17 |
Sent To |
|
|
| Notes |
| 2020-03-25 06:58:18 | RECIEVED 2ND APPRAISAL VIA E-MAIL - SEE 3RD NFIP REVIEW | | | FOR COMMENTS | | | | | | ADDRESS: 1007 N FLAGLER DR MASTER PERMIT: | | | 20011283 | | | | | | NFIP REVIEW - APPRAISAL FOR SI/SD DETERMINATION | | | | | | REQUIREMENT - NFIP COMPLIANT APPRAISAL | | | (MARKET VALUE OF THE STRUCTURE MINUS DEPRECIATION) | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | FBC RE = FLORIDA RESIDENTIAL CODE 6TH EDITION 2017 | | | CITY OF WEST PALM BEACH ORDINANCE NO. 4729-17 | | | USPAP = UNIFORM STANDARDS OF PROFESSIONAL APPRAISAL | | | PRACTICE | | | FEMA P-758 = SI/SD DESK REFERENCE | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 2ND REVIEW OF APPRAISAL | | | | | | RESULTS: DENIED | | | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED. | | | PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED | | | SATISFACTORILY HAVE ADDITIONAL COMMENTS IN PARENTHESES. | | | ANY NEW COMMENT WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | | | | | | TYPE OF APPRAISAL: UNIFORM RESIDENTIAL APPRAISAL | | | REPORT | | | | | | METHODOLOGY: CONVENTIONAL MARKET VALUE APPRAISAL | | | (RE-SUB INCLUDES COST APPROACH METHODOLOGY TO ESTABLISH | | | FEMA MARKET VALUE - REPLACEMENT COST MINUS DEPRECIATION | | | - ACTUAL CASH VALUE - ACV) CORRECTED | | | (ANALYSIS OF COMPARABLE SALES) (COST APPROACH) | | | CORRECTED | | | | | | | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. USPAP SR 2-2 (A) (I) REQUIRES APPRAISERS TO REPORT | | | THE APPRAISALS INTENDED USERS. CORRECTED | | | | | | 2. USPAP SR 2-2 (A) (II) REQUIRES APPRAISERS TO REPORT | | | THE APPRAISALS INTENDED USE. CORRECTED | | | | | | 3. USPAP SR 2-2 (A) (V) REQUIRES APPRAISERS TO STATE | | | THE TYPE AND DEFINITION OF VALUE. VALUE STATED IS | | | MARKET VALUE BASED ON AN ANALYSIS OF COMPARABLE SALES. | | | CORRECTED (COST APPROACH SUBMITTED FOR REVIEW) (TOTAL | | | COST NEW OBTAINED USING RS MEANS) | | | | | | 4. USPAP SR 2-2(A) (X) (I) STANDARD 1 - PROVIDE A NFIP | | | COMPLIANT REPLACEMENT COST ESTIMATE WITH DEPRECIATION | | | (ACTUAL CASH VALUE - ACV) FROM A RECOGNIZED COST | | | ESTIMATING SERVICE SUPPORTED BY ADEQUATE DOCUMENTATION. | | | (SEE NEW COMMENTS BELOW) | | | | | | 5. PROVIDE A COST BREAKDOWN OF PROPOSED WORK. CORRECTED | | | FEMA P-758 DESK REFERENCE SECTION 4.4 | | | | | | NEW COMMENTS | | | | | | 4A. REPLACEMENT COST ESTIMATE ESTABLISHED USING RS | | | MEANS - CORRECTED | | | | | | 4B.USPAP SR 2-2 (A) (X) (I) DEPRECIATION - STANDARD 1 - | | | REQUIRES APPRAISERS TO USE AN ANALYTICAL PROCESS IN | | | REACHING THEIR CONCLUSIONS. | | | PLEASE REFERENCE - APPRAISAL / COST APPROACH / | | | CALCULATIONS / PHYSICAL DETERIORATION FOR THE | | | FOLLOWING: | | | ECONOMIC LIFE WAS ESTABLISHED AT 70 YEARS | | | EFFECTIVE LIFE WAS ESTABLISHED AT 10 YEARS | | | 10/70=14.29% | | | STRUCTURE WAS BUILT IN 1953 - THIS WOULD ESTABLISH A | | | REMAINING HISTORICAL LIFE OF 4 YEARS (70-66) | | | | | | PROVIDE A RATIONAL ANALYSIS FOR THE INCREASE FROM A | | | REMAINING HISTORICAL LIFE OF 4 YEARS TO AN EFFECTIVE | | | LIFE OF 10 YEARS. | | | | | | 6. PLEASE REFERENCE - APPRAISAL - COST APPROACH - | | | ANALYSIS/COMMENTS SECTION - RECONCILIATION : | | | $411,000.00 IS THE DEPRECIATED COST OF THE MAIN | | | BUILDING, EXCLUDING LAND VALUE, THE REAR BUILDING AND | | | SITE IMPROVEMENTS. | | | | | | DEPRECIATED VALUE (ACV) OF THE BUILDING WAS ESTABLISHED | | | AT $317,188 IN THE CALCULATIONS AND SUMMARY OF COST | | | SECTIONS, PROVIDE CLARIFICATION FOR THIS RECONCILIATION | | | STATEMENT OF $411.000.00. | | | | | | | | | | | | | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
2 |
Status |
F |
Date |
2020-02-11 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-02-11 |
Time |
11:35 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-02-10 |
Time |
16:55 |
Sent To |
|
|
| Notes |
| 2020-02-11 12:09:55 | ADDRESS: 1007 N FLAGLER DR MASTER PERMIT: | | | 20011283 | | | | | | NFIP REVIEW - APPRAISAL FOR SI/SD DETERMINATION | | | | | | REQUIREMENT - NFIP COMPLIANT APPRAISAL | | | (MARKET VALUE OF THE STRUCTURE MINUS DEPRECIATION) | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | FBC RE = FLORIDA RESIDENTIAL CODE 6TH EDITION 2017 | | | CITY OF WEST PALM BEACH ORDINANCE NO. 4729-17 | | | USPAP = UNIFORM STANDARDS OF PROFESSIONAL APPRAISAL | | | PRACTICE | | | FEMA P-758 = SI/SD DESK REFERENCE | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | BUILDING PLANS EXAMINER, PX3169 | | | 1&2 FAMILY PLANS EXAMINER, SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | | | | TYPE OF APPRAISAL: UNIFORM RESIDENTIAL APPRAISAL | | | REPORT | | | | | | METHODOLOGY: CONVENTIONAL MARKET VALUE APPRAISAL | | | (ANALYSIS OF COMPARABLE SALES) | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. USPAP SR 2-2 (A) (I) REQUIRES APPRAISERS TO REPORT | | | THE APPRAISALS INTENDED USERS. THE INTENDED USER ON THE | | | SUBMITTED APPRAISAL IS THE CLIENT. NFIP REQUIRES THE | | | CLIENT AND FLOODPLAIN MANAGER TO BE LISTED AS INTENDED | | | USERS. | | | | | | 2. USPAP SR 2-2 (A) (II) REQUIRES APPRAISERS TO REPORT | | | THE APPRAISALS INTENDED USE. THE INTENDED USE OF THE | | | SUBMITTED APPRAISAL IS TO ESTABLISH MARKET VALUE FOR A | | | RESIDENTIAL MORTGAGE. NFIP REQUIRES APPRAISALS TO | | | SUPPORT A BUILDING PERMIT APPLICATION SUBJECT TO | | | SIGNIFICANT IMPROVEMENT/SIGNIFICANT DAMAGE | | | DETERMINATION UNDER NFIP REGULATIONS. | | | | | | 3. USPAP SR 2-2 (A) (V) REQUIRES APPRAISERS TO STATE | | | THE TYPE AND DEFINITION OF VALUE. VALUE STATED IS | | | MARKET VALUE BASED ON AN ANALYSIS OF COMPARABLE SALES. | | | NFIP REQUIRES THE ACTUAL CASH VALUE OF THE BUILDING | | | MINUS DEPRECIATION. | | | | | | 4. PROVIDE A NFIP COMPLIANT REPLACEMENT COST ESTIMATE | | | (ACV) WITH DEPRECIATION FROM A RECOGNIZED COST | | | ESTIMATING SERVICE SUPPORTED BY ADEQUATE DOCUMENTATION. | | | | | | 5. PROVIDE A COST BREAKDOWN OF PROPOSED WORK. | | | FEMA P-758 DESK REFERENCE SECTION 4.4 | | | | | | | | | | | | | | | | | | | | | | | 2020-02-10 16:55:52 | RECIEVED APPRAISAL FOR REVIEW. CT |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
1 |
Status |
F |
Date |
2020-01-31 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2020-01-31 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2020-01-31 |
Time |
15:09 |
Sent To |
|
|
| Notes |
| 2020-01-31 16:17:54 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | THIS STRUCTURE IS LOCATED IN A SPECIAL FLOOD HAZARD | | | AREA (AE, BFE 7). THE PAPA IMPROVEMENT VALUE FOR THE | | | PROPERTY IS $213,326.00. THERE ARE TWO STRUCTURES | | | LOCATED ON THE PROPERTY. THE MAIN BUILDING HAS A TOTAL | | | OF 1661 SQFT AND THE OTHER BUILDING IS A TOTAL OF 444 | | | SQFT. THE SQFT VALUE IS APPROXIMATELY $101.34. BASED ON | | | THIS THE VALUE OF THE MAIN HOUSE IS $168,325.74. THE | | | COST OF THE PROPOSED IMPROVEMENTS PLUS ANY OTHER | | | IMPROVEMENTS TO THE BUILDING FOR THE LAST FIVE YEARS | | | CAN NOT EXCEED 50 PERCENT OF THE VALUE OF THE BUILDING | | | ($ 84,162.87). THE PROPOSED WORK HAS A VALUATION OF | | | $100,000.00 AND THE VALUE OF THE IMPROVEMENTS FOR THE | | | PAST FIVE YEARS IS $58,036.00. THE TOTAL IS $158,036.00 | | | WHICH IS MORE THAN THE SUBSTANTIAL IMPROVEMENT | | | THRESHOLD OF $84,162.87. THEREFORE, THIS WILL BE A | | | SUBSTANTIAL IMPROVEMENT AND THE STRUCTURE WILL BE | | | REQUIRED TO COMPLY WITH THE CITY OF WEST PALM BEACH'S | | | FLOOD ORDINANCE FOR RESIDENTIAL CONSTRUCTION (INCLUDING | | | THE TWO FOOT FREEBOARD REQUIREMENT). NO FURTHER REVIEWS | | | WILL BE COMPLETED UNTIL THIS ISSUE HAS BEEN RESOLVED. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2020-09-16 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-09-16 |
Time |
13:10 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-09-16 |
Time |
07:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2020-08-22 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-08-22 |
Time |
07:39 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-08-20 |
Time |
15:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2020-08-11 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2020-08-11 |
Time |
05:20 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2020-08-10 |
Time |
13:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2020-06-23 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-06-23 |
Time |
11:14 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-06-22 |
Time |
11:36 |
Sent To |
|
|
| Notes |
| 2020-06-23 11:18:25 | PLAN REVIEW - PLUMBING | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER BUILDING - PX3169 | | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PROVIDE A PLUMBING PLAN WITH DETAILED SCOPE OF WORK. | | | SHOW EXISTING AND PROPOSED WORK. | | | 107.2 CONSTRUCTION DOCUMENTS. | | | | | | 2. PROVIDE A SANITARY RISER DIAGRAHM. | | | PLUMBING RISER - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FLORIDA BUILDING CODE, CHAPTER 1 ADMINISTRATION SECTION | | | 107.3.5.3 (12) | | | | | | 3. PROVIDE A WATER DISTRIBUTION RISER DIAGRAHM. | | | P2903.1WATER SUPPLY SYSTEM DESIGN CRITERIA. THE WATER | | | SERVICE AND WATER DISTRIBUTION SYSTEMS SHALL BE | | | DESIGNED, AND PIPE SIZES SHALL BE SELECTED SUCH THAT | | | UNDER CONDITIONS OF PEAK DEMAND, THE CAPACITIES AT THE | | | POINT OF OUTLET DISCHARGE SHALL NOT BE LESS THAN SHOWN | | | IN TABLE P2903.1. | | | | | | 4. PROVIDE SPECIFICATIONS FOR WATER CONTROL VALVES. | | | 607.2 HOT OR TEMPERED WATER SUPPLY TO FIXTURES. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
N |
Date |
2020-09-15 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-09-15 |
Time |
15:04 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-09-15 |
Time |
15:04 |
Sent To |
|
|
| Notes |
| 2020-09-15 15:04:58 | SEPERATE ROOFING PERMIT REQUIRED. CT |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2020-08-22 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-08-22 |
Time |
08:14 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-08-20 |
Time |
11:42 |
Sent To |
|
|
| Notes |
| 2020-08-22 08:19:09 | PLAN REVIEW - ROOFING | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER BUILDING - PX3169 | | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | 2ND REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED. | | | PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED | | | SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN | | | PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER | | | PREVIOUS COMMENTS. | | | | | | | | | 1. A ROOFING PERMIT IS REQUIRED. (NOTICE ONLY) | | | PERMITS - 105.1 REQUIRED. | | | | | | 2. PROVIDE PRODUCT APPROVALS FOR PROPOSED ROOFING | | | SYSTEM COMPONENTS. (NOT ADDRESSED. APPLICANT MAY SUBMIT | | | A STAND ALONE ROOFING PERMIT. PLEASE ADVISE) | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE ROOFING SUBMITTALS. | | | | | | 3. PROVIDE A ROOF FRAMING PLAN. (CORRECTED) | | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2020-06-23 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-06-23 |
Time |
10:54 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-06-22 |
Time |
14:00 |
Sent To |
|
|
| Notes |
| 2020-06-23 10:57:05 | PLAN REVIEW - ROOFING | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER BUILDING - PX3169 | | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. A ROOFING PERMIT IS REQUIRED. | | | PERMITS - 105.1 REQUIRED. | | | | | | 2. PROVIDE PRODUCT APPROVALS FOR PROPOSED ROOFING | | | SYSTEM COMPONENTS. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE ROOFING SUBMITTALS. | | | | | | 3. PROVIDE A ROOF FRAMING PLAN. | | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | | | | | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2020-09-16 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-09-16 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-09-16 |
Time |
07:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2020-08-22 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2020-08-22 |
Time |
07:34 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2020-08-20 |
Time |
13:41 |
Sent To |
|
|
| Notes |
| 2020-08-22 07:37:59 | PLAN REVIEW - SIGNATURE | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER BUILDING - PX3169 | | | PLANS EXAMINER 1&2 FAMILY - SFP306 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CODES IN EFFECT: | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | NOTE: ALL NEW PLAN SHEETS UPLOADED FOR REVIEW. PREVIOUS | | | SIGNATURE REVIEW NOT APPLICABLE. | | | | | | DESIGN PROFESSIONALS | | | | | | 1. DIGITAL SIGNATURES/SEALS ARE NOT IN ACCORDANCE WITH | | | FS 471, FS 481 AS NOTED. NEW SHEETS SUBMITTED IN THE | | | NEXT REVIEW CYCLE REQUIRE REVIEW. | | | | | | 2. UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL | | | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE | | | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT. | | | | | | OPTION | | | | | | YOU MAY ELECT TO PROVIDE A HARD COPY OF PLANS WITH WET | | | SEAL AND SIGNATURE OF DESIGN PROFESSIONAL PRIOR TO | | | PERMIT. A DROP BOX HAS BEEN INSTALLED OUTSIDE CITY HALL | | | FOR THIS PURPOSE. CONTACT THE OFFICE OF DEVELOPMENT | | | SERVICES @ 561-805-8700 OR [email protected] TO STATE YOUR | | | INTENTIONS. CITY STAFF WILL REVIEW YOUR DOCUMENTS AND | | | IF APPROVED YOU WILL RECIEVE AN E-MAIL INSTRUCTING YOU | | | TO DOWNLOAD AND PRINT YOUR PERMIT AND PLANS. | | | | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2020-06-17 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-06-17 |
Time |
13:48 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-06-17 |
Time |
13:48 |
Sent To |
|
|
| Notes |
| 2020-06-17 13:50:10 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | SIGNATURE REVIEW APPROVED BY ORIGINAL (PAPER) | | | SIGNATURES/SEALS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2020-08-06 |
|
|
Cont ID |
|
| Sent By |
elevesqu |
Date |
2020-08-06 |
Time |
09:35 |
Rev Time |
0.00 |
| Received By |
elevesqu |
Date |
2020-08-06 |
Time |
09:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2020-06-22 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2020-06-22 |
Time |
11:37 |
Rev Time |
0.00 |
| Received By |
elevesqu |
Date |
2020-06-22 |
Time |
11:37 |
Sent To |
|
|
| Notes |
| 2020-06-22 11:37:26 | COVER SHEET SITE PLAN SHEET 1.01 IS MISSING SF | | | INFORMATION FOR ADDITIONAL AND TOTAL - PLEASE INCLUDE | | | | | | NEW ROOF ON EXISTING STRUCTURE MOST LIKELY REQUIRES | | | SEPARATE PERMIT - CHECK WITH BUILDING PERMIT INTAKE | | | | | | LIZ LEVESQUE, URBAN DESIGN PLANNER | | | [email protected] | | | 561 822 1426 | | | | | | | | | |
|
|