| 2020-01-30 10:47:58 | BUILDING REVIEW COMMENTS: |
| | |
| | W.P.B. PERMIT: 20011210 |
| | REVIEWED: JANUARY 30, 2020 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER PX4191 |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK |
| | BELOW) |
| | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ |
| | BUILDING-PERMIT-FORMS |
| | FBC[B] = FBC BUILDING |
| | FBC[EXISTING] = FBC EXISTING BUILDING |
| | FBC[A] = FBC ACCESSIBILITY |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | FBC[R] = FBC RESIDENTIAL |
| | |
| | 1) 105.15 FBC [AMENDED]OPENING PROTECTION. WHEN ANY |
| | ACTIVITY REQUIRING A BUILDING PERMIT THAT IS APPLIED |
| | FOR ON OR AFTER JULY 1, 2008, AND FOR WHICH THE |
| | ESTIMATED COST IS $50,000 OR MORE FOR A SITE BUILT |
| | SINGLE FAMILY DETACHED RESIDENTIAL STRUCTURES THAT IS |
| | LOCATED IN THE WIND BORNE DEBRIS REGION AS DEFINED IN |
| | THIS CODE AND THAT HAS AN INSURED VALUE OF $750,000 OR |
| | MORE, OR, IF THE SITE BUILT SINGLE FAMILY DETACHED |
| | RESIDENTIAL STRUCTURE IS UNINSURED OR FOR WHICH |
| | DOCUMENTATION OF INSURED VALUE IS NOT PRESENTED, HAS A |
| | JUST VALUATION FOR THE STRUCTURE FOR PURPOSES OF AD |
| | VALOREM TAXATION OF $750,000 OR MORE; OPENING |
| | PROTECTIONS AS REQUIRED WITHIN THIS CODE OR FLORIDA |
| | BUILDING CODE, RESIDENTIAL FOR NEW CONSTRUCTION SHALL |
| | BE PROVIDED. |
| | -PLEASE PROVIDE DOCUMENTATION THAT HOME HAS PERMITTED |
| | OPENING PROTECTION, OR SUPPLY DOCUMENTATION TO COMPLY |
| | WITH 105.15. |
| | |
| | 2) 908.8 FBC[R]IF HOME >300,000.00 VALUE THAN STRAPPING |
| | NEEDS TO BE UPGRADED. |
| | 908.8 FBC[R]WHEN A ROOF COVERING ON AN EXISTING |
| | SITE-BUILT-SINGLE FAMILY RESIDENTIAL STRUCTURE IS |
| | REMOVED AND REPLACED ON A BUILDING THAT IS LOCATED IN |
| | THE WIND BORNE DEBRIS REGION AS DEFINED IN THE FLORIDA |
| | BUILDING CODE, BUILDING AND THAT HAS AN INSURED VALUE |
| | OF $300,000 OR MORE OR, IF THE BUILDING IS UNINSURED OR |
| | FOR WHICH DOCUMENTATION OF INSURED VALUE IS NOT |
| | PRESENTED, HAS A JUST VALUATION FOR THE STRUCTURE FOR |
| | PURPOSES OF AD VALOREM TAXATION OF $300,000 OR MORE: |
| | (A) ROOF TO WALL CONNECTIONS SHALL BE IMPROVED AS |
| | REQUIRED BY SECTION R908.8.1 |
| | (B) MANDATED RETROFITS OF THE ROOF-TO-WALL CONNECTION |
| | SHALL NOT BE REQUIRED BEYOND A 15 PERCENT INCREASE IN |
| | THE COST OF RE-ROOFING. EXCEPTION: SINGLE-FAMILY |
| | RESIDENTIAL STRUCTURES PERMITTED SUBJECT TO THE FLORIDA |
| | BUILDING CODE ARE NOT REQUIRED TO COMPLY WITH THIS |
| | SECTION. |
| | -PLEASE PROVIDE DOCUMENTATION THAT THIS HAS BEEN DONE, |
| | OR SUPPLY DOCUMENTATION TO COMPLY WITH 908.8. |
| | |
| | 4) PROVIDE TWO COPIES OF PRODUCT APPROVAL FOR THE |
| | ATTACHMENT OF ROOFING TILE. |
| | |
| | 5) THE PRODUCT APPROVAL FOR FLAT ROOF IS ONLY THE COVER |
| | PAGES. WE ALSO NEED THE INSTALLATION INSTRUCTIONS WITH |
| | THE SYSTEM SELECTED THAT WILL BE INSTALLED (WE DON'T |
| | NEED ALL PAGES, JUST SHEETS 1-4 AND THE SHEET THAT |
| | CONTAINS YOUR SYSTEM). ALSO, REVIEW SHEET #3 TO SEE IF |
| | ENGINEERING IS NEEDED FOR MECHANICALLY ATTACHED |
| | COMPONENTS. |
| | |
| | 6) PROVIDE THE AMOUNT OF ROOF AREA FOR FLAT AND TILE |
| | WITH ROOF PITCHES AS WELL. |
| | |
| | 7) ALSO, THERE IS AN EXPIRED PERMIT ON THAT ADDRESS FOR |
| | MECHANICAL CHANGE OUT. PERMIT 13070195. PLEASE HAVE THE |
| | OWNER CONTACT THE BUILDING DEPARTMENT TO GET THIS |
| | PERMIT CLOSED OUT. |
| | 561-805-6700 (SPEAK TO THE PLAN REVIEWER ON-CALL) |
| | |
| | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| | [email protected] |
| | |
| | |
| | |