Plan Review Details - Permit 20011193
Plan Review Stops For Permit 20011193
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-02-18 Cont ID  
Sent By rmcphers Date 2020-02-18 Time 14:43 Rev Time 0.00
Received By rmcphers Date 2020-02-18 Time 14:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-02-06 Cont ID  
Sent By rmcphers Date 2020-02-06 Time 11:04 Rev Time 0.00
Received By rmcphers Date 2020-02-06 Time 07:37 Sent To  
Notes
2020-02-06 11:16:35FLOORING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED -
 1) THE BUILDING AT 1617 N FLAGLER HAS A 6" SLAB - I
 NEED AN "ACOUSTICAL LABORATORY TEST REPORT" THAT SHOWS
 THE TEST DESCRIPTION FOR A 6" THICK SLAB ( NO CEILING
 ). CONTACT THE UNDERLAYMENT MANUFACTURE OR THE STORE
 THAT YOU ARE GETTING THE UNDERLAYMENT (PROFLEX) FROMAND
 ASK FOR THE "ACOUSTICAL LABORATORY TEST REPORT". NEED
 AN IIC (ASTM E989-06) AND AN STC (ASTM E90) OF 50 OR
 HIGHER. IF PROFLEX DOESN'T HAVE THE TEST REPORT PLEASE
 TRY ANOTHER PRODUCT - - SEE FBC 1207
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-01-31 Cont ID  
Sent By rmcphers Date 2020-01-31 Time 14:14 Rev Time 0.00
Received By rmcphers Date 2020-01-31 Time 14:10 Sent To  
Notes
2020-01-31 14:50:21KITCHEN AND BATH REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED -
 1) PLEASE PROVIDE FLOORING UNDERLAYMENT ACOUSTICAL TEST
 REPORT TO SHOW THE REQUIRED "IIC" AND "STC" MINIMUM AT
 50 OR HIGHER PER FBC 1207
 FBC 1207.2 WALLS, PARTITIONS AND FLOOR/CEILING
 ASSEMBLIES SEPARATING DWELLING UNITS AND SLEEPING UNITS
 FROM EACH OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL
 HAVE A SOUND TRANSMISSION CLASS OF NOT LESS THAN 50, OR
 NOT LESS THAN 45 IF FIELD TESTED, FOR AIR-BORNE NOISE
 WHEN TESTED IN ACCORDANCE WITH ASTM E90.
 FBC 1207.3 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING
 UNITS AND SLEEPING UNITS OR BETWEEN A DWELLING UNIT OR
 SLEEPING UNIT AND A PUBLIC OR SERVICE AREA WITHIN THE
 STRUCTURE SHALL HAVE AN IMPACT INSULATION CLASS RATING
 OF NOT LESS THAN 50, OR NOT LESS THAN 45 IF FIELD
 TESTED, WHEN TESTED IN ACCORDANCE WITH ASTM E492.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-02-18 Cont ID  
Sent By rmcphers Date 2020-02-18 Time 14:43 Rev Time 0.00
Received By rmcphers Date 2020-02-11 Time 13:46 Sent To  
Notes
2020-02-18 14:44:03PLANS TAKEN TO PERMIT LIBRARY
2020-02-12 13:47:02RESUB ROUTED TO RMCPHERSON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-02-06 Cont ID  
Sent By rmcphers Date 2020-02-06 Time 11:16 Rev Time 0.00
Received By rmcphers Date 2020-02-04 Time 13:41 Sent To  
Notes
2020-02-06 11:17:46TAKEN TO PERMIT LIBRARY
2020-02-05 13:41:28RESUB ROUTED TO RMCPHERSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-01-31 Cont ID  
Sent By tklarge Date 2020-01-31 Time 14:33 Rev Time 0.00
Received By tklarge Date 2020-01-29 Time 14:16 Sent To  
Notes
2020-01-31 14:16:14PLANS TAKEN TO PERMIT LIBRARY
2020-01-30 14:16:56BLDG MISC 1

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-01-31 Cont ID  
Sent By tklarge Date 2020-01-31 Time 14:33 Rev Time 0.00
Received By tklarge Date 2020-01-31 Time 14:29 Sent To  
Notes
***NONE***