Plan Review Details - Permit 20011142
Plan Review Stops For Permit 20011142
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-03-30 Cont ID  
Sent By rmcphers Date 2020-03-30 Time 14:54 Rev Time 0.00
Received By rmcphers Date 2020-03-30 Time 14:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-03-16 Cont ID  
Sent By rmcphers Date 2020-03-16 Time 10:39 Rev Time 0.00
Received By rmcphers Date 2020-03-16 Time 10:35 Sent To  
Notes
2020-03-16 10:40:53SIGN
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED -
 1) ENGINEERED CALCULATIONS NEED TO BE ELECTRONICALLY
 SIGNED BY THE ENGINEER FOR USE IN ELECTRONIC PLAN
 REVIEW. ORIGINAL SIGNED AND SEALED DRAWINGS MAY BE
 BROUGHT IN TO THE FRONT COUNTER TO BE ADDED TO THE
 PERMIT PACKAGE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-02-11 Cont ID  
Sent By rmcphers Date 2020-02-11 Time 08:43 Rev Time 0.00
Received By rmcphers Date 2020-02-11 Time 08:32 Sent To  
Notes
2020-02-11 08:49:10SIGN
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED -
 1) ENGINEERED SIGNED AND SEALED DRAWINGS AND
 CALCULATIONS NEED TO BE ELECTRONICALLY SIGNED BY THE
 ENGINEER FOR USE IN ELECTRONIC PLAN REVIEW. ORIGINAL
 SIGNED AND SEALED DRAWINGS MAY BE BROUGHT IN TO THE
 FRONT COUNTER TO BE ADDED TO THE PERMIT PACKAGE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-03-21 Cont ID  
Sent By fgiaquin Date 2020-03-21 Time 13:20 Rev Time 0.00
Received By fgiaquin Date 2020-03-21 Time 13:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-02-10 Cont ID  
Sent By fgiaquin Date 2020-02-10 Time 07:00 Rev Time 0.00
Received By fgiaquin Date 2020-02-06 Time 06:06 Sent To  
Notes
2020-02-10 06:13:10ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PAGES OF PLAN ARE CUT OFF AND ARE NOT FULL PAGES.
 FBC 107.2.1
  
 2. DIGITALLY SUBMITTED PLANS MUST BE DIGTIALLY SIGNED
 BY DESIGN PROFESSIONAL. PLEASE SEE REQUIREMENTS BELOW
 FOR SIGNS/SEALS.
  
 PRINTED COPIES OF DIGITALLY SIGNED PLANS ARE NOT
 CONSIDERED TO BE SIGNED AND SEALED PER FLORIDA
 STATUTES. PLEASE SEE REQUIREMENTS BELOW FOR SIGNATURE
 AND SEALS.
  
 PHYSICALLY TRANSMITTED DOCUMENTS REQUIRE THAT THE
 LICENSEE CREATE BY HAND AN ORIGINAL OF THE LICENSEE?S
 SIGNATURE. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE IS NOT ALLOWED
 ON PHYSICALLY TRANSMITTED DOCUMENTS.
 CHAPTER 61G15-23.003(1), F.A.C., THE LICENSEE SHALL
 SIGN BY HAND AN ORIGINAL OF THE LICENSEE?S SIGNATURE ON
 EACH PAGE REQUIRED TO BE SEALED. A SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S
 SIGNATURE SHALL NOT BE USED.
  
 AS FOR CREATING THE SEAL, PHYSICALLY TRANSMITTED
 DOCUMENTS ARE ALLOWED TO BE EMBOSSED, SEALED USING A
 WET STAMP, OR CONTAIN A DIGITALLY CREATED SEAL (AS PART
 OF THE BORDER). IN EACH OF THESE CASES THE SEAL IS TO
 PARTIALLY OVERLAP THE LICENSEE?S SIGNATURE SUCH THAT
 THE SIGNATURE IS NOT MADE ILLEGIBLE.
 CHAPTER 61G15-23.003(2), F.A.C., THE LICENSEE MUST THEN
 USE A WET SEAL, A DIGITALLY CREATED SEAL, OR AN
 EMBOSSING SEAL PLACED PARTIALLY OVERLAPPING THE
 LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. THE PLACEMENT OF THE SEAL SHALL NOT RENDER THE
 SIGNATURE ILLEGIBLE.
  
 3. DISCONNECT MUST COMPLY WITH 600.6A1 NEC AND MUST BE
 WITHIN SIGHT OF SIGN.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-03-30 Cont ID  
Sent By rmcphers Date 2020-03-30 Time 14:56 Rev Time 0.00
Received By rmcphers Date 2020-03-23 Time 14:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-03-23 Cont ID  
Sent By lmarchan Date 2020-03-23 Time 09:27 Rev Time 0.00
Received By lmarchan Date 2020-03-11 Time 07:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-02-28 Cont ID  
Sent By lmarchan Date 2020-02-28 Time 11:57 Rev Time 0.00
Received By lmarchan Date 2020-01-28 Time 08:25 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-03-30 Cont ID  
Sent By rmcphers Date 2020-03-30 Time 14:55 Rev Time 0.00
Received By rmcphers Date 2020-03-30 Time 14:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-03-16 Cont ID  
Sent By rmcphers Date 2020-03-16 Time 10:41 Rev Time 0.00
Received By rmcphers Date 2020-03-16 Time 10:41 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-02-11 Cont ID  
Sent By rmcphers Date 2020-02-11 Time 08:49 Rev Time 0.00
Received By rmcphers Date 2020-02-11 Time 08:49 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-03-19 Cont ID  
Sent By eschneid Date 2020-03-19 Time 15:42 Rev Time 0.25
Received By eschneid Date 2020-03-19 Time 15:34 Sent To  
Notes
2020-03-19 15:45:24PERMITTED: 35.4 SF
 PROPOSED: 35 SF

Review Stop Z ZONING
Rev No 1 Status F Date 2020-02-28 Cont ID  
Sent By eschneid Date 2020-02-28 Time 11:21 Rev Time 0.25
Received By eschneid Date 2020-02-28 Time 11:21 Sent To  
Notes
2020-02-28 11:53:02FAILED
  
 1) PLEASE PROVIDE ONE DIMENSION SHOWING THE FULL HEIGHT
 OF THE BAY. STAFF IS UNABLE TO VERIFY HOW YOU ARRIVED
 AT THE 384 SQUARE FOOT STOREFRONT AREA WITH THE 32 FOOT
 WIDTH AND THE 108 INCH/30 INCH DIMENSIONS SHOWN FOR THE
 HEIGHT.
  
 2) THE PROPOSED SIGN AREA IS LISTED AS 52.3 SF, YET
 WHEN STAFF CALCULATES THE PROPOSED 185 INCH X 30 INCH
 SIGN IT RESULTS IN A 38.54 SF SIGN. PLEASE VERIFY YOUR
 DIMENSIONS AND CALCULATIONS ON THE PLANS.
  
 3) THE MAXIMUM SIGN AREA PERMITTED FOR A FACADE BETWEEN
 300 AND 400 SF IS 35.4 SF, WHICH IS LESS THAN BOTH THE
 STATED PROPOSED SIGN AREA AND THE STAFF CALCULATED SIGN
 AREA.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]