Plan Review Details - Permit 20011057
Plan Review Stops For Permit 20011057
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-02-21 Cont ID  
Sent By jpearson Date 2020-02-21 Time 10:37 Rev Time 0.00
Received By jpearson Date 2020-02-21 Time 10:37 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-01-28 Cont ID  
Sent By jpearson Date 2020-01-28 Time 17:21 Rev Time 0.00
Received By jpearson Date 2020-01-28 Time 17:21 Sent To I
Notes
2020-01-28 17:21:54CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE LETTER PROVIDED DOES NOT LIST THE CORRECT PERMIT
 NUMNER FOR THIS PROJECT. ADDITIONALLY, ANY CHANGES TO
 THE APPROVED PLAN REQUIRES SUBMISSION OF A REVISED PLAN
 TO BE REVIEWED. A LETTER ALONE IS NOT SUFFICIENT. A
 CHANGE FROM ONE METER TO TWO METERS WILL ALSO REQUIRE
 ZONING DEPARTMENT APPROVAL. FOR ELECTRICAL REVIEW, A
 SECOND METER MAY BE APPROVED, BUT IT MUST BE FED FROM
 ONLY ONE SERVICE. A SECOND SERVICE IS NOT PERMITTED PER
 CODE. PROVIDE CORRECTIONS. NEC 230.2; FBC RE E3601.2;
 WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-02-21 Time   Rev Time 0.00
Received By lmarchan Date 2020-02-14 Time 13:41 Sent To  
Notes
2020-02-18 13:41:56RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-01-28 Time   Rev Time 0.00
Received By lmarchan Date 2020-01-27 Time 13:45 Sent To  
Notes
2020-01-28 13:45:10REVISION ROUTED TO JPEARSON