| 2020-01-28 17:21:54 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. THE LETTER PROVIDED DOES NOT LIST THE CORRECT PERMIT |
| | NUMNER FOR THIS PROJECT. ADDITIONALLY, ANY CHANGES TO |
| | THE APPROVED PLAN REQUIRES SUBMISSION OF A REVISED PLAN |
| | TO BE REVIEWED. A LETTER ALONE IS NOT SUFFICIENT. A |
| | CHANGE FROM ONE METER TO TWO METERS WILL ALSO REQUIRE |
| | ZONING DEPARTMENT APPROVAL. FOR ELECTRICAL REVIEW, A |
| | SECOND METER MAY BE APPROVED, BUT IT MUST BE FED FROM |
| | ONLY ONE SERVICE. A SECOND SERVICE IS NOT PERMITTED PER |
| | CODE. PROVIDE CORRECTIONS. NEC 230.2; FBC RE E3601.2; |
| | WPB FBC 107.2.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| | |