| 2020-04-09 09:19:14 | REVIEWED BY JERRY SMITH. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 20010978 505 S FLAGLER DR # 200 |
| | |
| | 2ND REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | PLEASE NOTE: PLAN SHEETS A1.2.1 AND A1.3.1 WHICH WERE |
| | REFERENCED IN THE RESPONSE LETTER DATED 4/2/2020, DO |
| | NOT PERTAIN TO PERMIT 20010978 WHICH IS FOR WORK TO BE |
| | DONE ON THE SECOND FLOOR. |
| | 1) PER WPB FBC 107.2.1, PROVIDE LOCATION OF THE |
| | REQUIRED BI-LEVEL DRINKING FOUNTAIN CALLED OUT IN |
| | PLUMBING FIXTURE SCHEDULE NOTED ON PLAN SHEET P0.1. |
| | ARCHITECT TO PROVIDE ADEQUATE SPACE FOR SAID DRINKING |
| | FOUNTAIN, WHICH SHALL BE CLEARLY SHOWN AS THE REQUIRED |
| | BI-LEVEL DRINKING FOUNTAIN ON ARCHITECTURAL PLAN SHEETS |
| | PERTAINING TO THE SECOND FLOOR RENOVATION FOR WHICH IS |
| | APPLICABLE TO PERMIT 20010978, THAT WILL COMPLY WITH |
| | THE REQUIREMENTS OF FBC ACC CHAPTERS 3 AND 6. |
| | ADDITIONALLY, THE DRINKING FOUNTAIN, WHICH SHALL BE |
| | CLEARLY SHOWN AS THE REQUIRED BI-LEVEL DRINKING |
| | FOUNTAIN ON PLAN SHEET P2.1. |
| | 2) PER WPB FBC 107.2.1, ARCHITECT TO PROVIDE ON |
| | ARCHITECTURAL PLAN SHEETS PERTAINING TO THE SECOND |
| | FLOOR RENOVATION FOR WHICH IS APPLICABLE TO PERMIT |
| | 20010978, CLEAR FLOOR SPACES, REACH RANGES, AND TURNING |
| | SPACES AS REQUIRED FOR SINK, ICE MAKERS, FRIDGE/ |
| | FREEZER, DRINKING FOUNTAIN. FBC-ACC 306, 306, 804. |
| | 3) PER WPB FBC 107.2.1, ARCHITECT TO NOTE ON |
| | ARCHITECTURAL PLAN SHEETS PERTAINING TO THE SECOND |
| | FLOOR RENOVATION FOR WHICH IS APPLICABLE TO PERMIT |
| | 20010978, THAT PER FBC ACC 606.3, THE SINK AND |
| | SUBSEQUENT COUNTER/WORKING SPACE SHALL BE INSTALLED |
| | WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER |
| | SURFACE 34 INCHES ABOVE THE FINISH FLOOR. |
| | 4) PER WPB FBC 107.2.1, ARCHITECT TO PROVIDE A DETAIL |
| | FOR THE DRINKING FOUNTAIN ON ARCHITECTURAL PLAN SHEETS |
| | PERTAINING TO THE SECOND FLOOR RENOVATION FOR WHICH IS |
| | APPLICABLE TO PERMIT 20010978, SHOWING COMPLIANCE WITH |
| | FBC ACC 307 AND 602. |
| | 5) RE: P0.1; THE FIXTURE PLUMBING SCHEDULE APPEARS TO |
| | APPLY TO OTHER RENOVATIONS IN ADDITION TO THE SECOND |
| | FLOOR RENOVATION. PER FBC 107.2.1, INDICATE ON THE |
| | PLUMBING FIXTURE SCHEDULE THAT S-1 AND NOT S-2 IS |
| | APPLICABLE TO THE SECOND FLOOR RENOVATION. |
| | 6) RE: P0.1; TYPICAL PLUMBING FIXTURE CONNECTION |
| | SCHEDULE. PLEASE COMPLY WITH THE FOLLOWING: |
| | A. COFFEE MAKER; PROVIDE BACKFLOW PREVENTOR FOR WATER |
| | CONNECTION |
| | B. FILTER; PROVIDE MANUFACTURER?S SPECIFICATION AND |
| | INSTALLATION MANUAL. |
| | 1. IF RO SYSTEM IS PROVIDED THEN A BACKFLOW PREVENTOR |
| | SHALL BE REQUIRED FOR THE WATER CONNECTION AND A |
| | TRAPPED AND VENTED ACCESSIBLE OPEN RECEPTACLE SHALL BE |
| | REQUIRED FOR THE DRAIN WHICH SHALL DISCHARGE TO THE |
| | OPEN RECEPTACLE THROUGH AN AIR GAP. THIS INFORMATION |
| | SHALL BE SHOWN IN PIPING ARRANGEMENT. |
| | 2. IF A REMOVABLE/REPLACEMENT TYPE FILTER IS PROVIDED, |
| | A BACKFLOW PREVENTER SHALL BE REQUIRED FOR THE WATER |
| | CONNECTION. |
| | C. REFRIGERATOR; PROVIDE BACKFLOW PREVENTOR FOR WATER |
| | CONNECTION |
| | 7) PER WPB FBC 107.2.1, PROVIDE WATER AND SANITARY |
| | RISER DIAGRAMS FOR THE PLUMBING WORK SHOWN IN PLAN |
| | VIEW. PLEASE NOTE THAT AN AAV SHALL NOT BE PERMITTED AS |
| | A FIXTURE VENT PER FBC PL 918.3.1 UNLESS THE HORIZONTAL |
| | BRANCH IS PROVIDED WITH A RELIEF VENT THAT CONNECTS TO |
| | THE VENT STACK. |
| | 8) IF DRINKING FOUNTAIN IS TO BE RELOCATED IN ORDER TO |
| | COMPLY WITH THE REQUIREMENTS OF FBC ACC 307 AND 602, |
| | THEN PER WPB FBC 107.2.1, PROVIDE PLAN VIEW AND RISER |
| | DIAGRAMS FOR THE REQUIRED PIPING |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE |
| | DESIGNER IN ACCORDANCE WITH FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-246-0882 MOBILE |
| | |
| | 20010978 505 S FLAGLER DR # 200 |
| | |
| | |