Plan Review Details - Permit 20010947
Plan Review Stops For Permit 20010947
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-03-13 Cont ID  
Sent By jgomez Date 2020-03-13 Time 09:07 Rev Time 0.00
Received By jgomez Date 2020-03-13 Time 08:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-03-02 Cont ID  
Sent By jgomez Date 2020-03-02 Time 16:48 Rev Time 0.00
Received By jgomez Date 2020-03-02 Time 16:30 Sent To  
Notes
2020-03-02 16:43:29RECEIVED E-MAIL FROM MILLET DEANGLES.
 CONSTRUCTION DRAWINGS FROM STEVEN BRUH (ARCH.) LOOK OK.
 PROVIDE COMPLETE INFORMATION REQUIRED ON ITEM #2. NEED
 TO SPECIFY THE CURRENT CODE (FBC-6TH EDITION, 2017),
 WIND EXPOSURE (C), WIND LOADS (170 PSF ULTIMATE WIND
 LOAD AND 132 PSF NOMINAL WIND LOAD) AS REQUIRED BY SEC.
 107.2.1, SEC. 107.3.5.3 CITY AMENDMENTS AND SEC. R301.1
 FBC-RESIDENTIAL.
  
  
  
 RESIDENTIAL (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- PROVIDE ENGINEERED CALCULATIONS SHOWING THAT THE
 PROPOSED PERGOLA INSTALLATION WILL BE ADEQUATE TO
 RESIST ALL WIND LOADS AND UPLIFT LOADS WITHOUT A
 FOUNDATION AS SHOWN ON DRAWINGS SUBMITTED. SEC.
 107.2.1.2 CITY AMENDMENTS. NOTE: BASED ON CITY
 ENGINEERING MAPS THIS AREA IS KNOWN TO HAVE
 QUESTIONABLE SOIL. ENGINEERING CALCULATIONS NEED TO
 TAKE THE SOIL CHARACTERISTICS INTO CONSIDERATION.
 CALCULATIONS TO BE PROPERLY SIGNED AND SEALED AS
 REQUIRED BY CHAPTER 471 F.S. OR CHAPTER 481 F.S.
  
 2- PROVIDE COMPLETE PLANS DRAWN TO SCALE SHOWING ALL
 DIMENSIONS (INCLUDING HEIGHT) AND SPECIFY THE CURRENT
 CODE (FBC-6TH EDITION, 2017), WIND EXPOSURE, WIND LOADS
 (ULTIMATE WIND LOAD AND NOMINAL WIND LOAD) AS REQUIRED
 BY SEC. 107.2.1, SEC. 107.3.5.3 CITY AMENDMENTS AND
 SEC. R301.1 FBC-RESIDENTIAL.
  
 3- PROVIDE THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. SEC. 107.2.1, SEC.
 107.3.5.3 CITY AMENDMENTS.
  
 4- PROVIDE COMPLETE SPECIFICATIONS FOR THE TYPE OF WOOD
 POSTS SHOWING COMPLIANCE WITH SEC. R407.1
 FBC-RESIDENTIAL. NEED PROTECTION AGAINST DECAY. NOTE:
 NEED SPECIFICATIONS FOR WOOD IN-GROUND INSTALLATION.
  
 5- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. UPDATE VALUATION OR PROVIDE COPY OF SIGNED
 CONTRACTS INCLUDING DESIGN PROFESSIONAL FEES.
  
 6- RECORDED NOTICE OF COMMENCEMENT WILL BE REQUIRED.
 SEC. 713 F.S.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. (NOTE: SUBMIT OLD DRAWINGS FOR REFERENCE). A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-02-07 Cont ID  
Sent By jgomez Date 2020-02-07 Time 09:39 Rev Time 0.00
Received By jgomez Date 2020-02-07 Time 08:15 Sent To  
Notes
2020-02-07 08:57:47RESIDENTIAL (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- PROVIDE ENGINEERED CALCULATIONS SHOWING THAT THE
 PROPOSED PERGOLA INSTALLATION WILL BE ADEQUATE TO
 RESIST ALL WIND LOADS AND UPLIFT LOADS WITHOUT A
 FOUNDATION AS SHOWN ON DRAWINGS SUBMITTED. SEC.
 107.2.1.2 CITY AMENDMENTS. NOTE: BASED ON CITY
 ENGINEERING MAPS THIS AREA IS KNOWN TO HAVE
 QUESTIONABLE SOIL. ENGINEERING CALCULATIONS NEED TO
 TAKE THE SOIL CHARACTERISTICS INTO CONSIDERATION.
 CALCULATIONS TO BE PROPERLY SIGNED AND SEALED AS
 REQUIRED BY CHAPTER 471 F.S. OR CHAPTER 481 F.S.
  
 2- PROVIDE COMPLETE PLANS DRAWN TO SCALE SHOWING ALL
 DIMENSIONS (INCLUDING HEIGHT) AND SPECIFY THE CURRENT
 CODE (FBC-6TH EDITION, 2017), WIND EXPOSURE, WIND LOADS
 (ULTIMATE WIND LOAD AND NOMINAL WIND LOAD) AS REQUIRED
 BY SEC. 107.2.1, SEC. 107.3.5.3 CITY AMENDMENTS AND
 SEC. R301.1 FBC-RESIDENTIAL.
  
 3- PROVIDE THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. SEC. 107.2.1, SEC.
 107.3.5.3 CITY AMENDMENTS.
  
 4- PROVIDE COMPLETE SPECIFICATIONS FOR THE TYPE OF WOOD
 POSTS SHOWING COMPLIANCE WITH SEC. R407.1
 FBC-RESIDENTIAL. NEED PROTECTION AGAINST DECAY. NOTE:
 NEED SPECIFICATIONS FOR WOOD IN-GROUND INSTALLATION.
  
 5- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. UPDATE VALUATION OR PROVIDE COPY OF SIGNED
 CONTRACTS INCLUDING DESIGN PROFESSIONAL FEES.
  
 6- RECORDED NOTICE OF COMMENCEMENT WILL BE REQUIRED.
 SEC. 713 F.S.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. (NOTE: SUBMIT OLD DRAWINGS FOR REFERENCE). A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2020-03-12 Cont ID  
Sent By fmittner Date 2020-03-12 Time 10:23 Rev Time 0.00
Received By fmittner Date 2020-03-12 Time 10:23 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2020-01-30 Cont ID  
Sent By fmittner Date 2020-01-30 Time 11:07 Rev Time 0.00
Received By fmittner Date 2020-01-30 Time 11:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-03-13 Cont ID  
Sent By jgomez Date 2020-03-13 Time 09:07 Rev Time 0.00
Received By jgomez Date 2020-03-05 Time 09:09 Sent To I
Notes
2020-03-12 15:15:553/12 ROUTED TO JGOMEZ
2020-03-09 09:09:52RESUB ROUTED TO HISTORIC INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-03-02 Cont ID  
Sent By jgomez Date 2020-03-02 Time 16:49 Rev Time 0.00
Received By jgomez Date 2020-03-02 Time 16:30 Sent To  
Notes
2020-03-02 16:32:19RECEIVED E-MAIL FROM MILLET DEANGLES.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-02-07 Cont ID  
Sent By jgomez Date 2020-02-07 Time 09:39 Rev Time 0.00
Received By jgomez Date 2020-01-23 Time 13:36 Sent To I
Notes
2020-01-30 16:48:19ROUTED TO MISC 2
2020-01-27 13:36:56ROUTED TO HISTORIC INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2020-03-12 Cont ID  
Sent By fmittner Date 2020-03-12 Time 10:23 Rev Time 0.00
Received By fmittner Date 2020-03-12 Time 10:23 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-01-30 Cont ID  
Sent By fmittner Date 2020-01-30 Time 11:07 Rev Time 0.00
Received By fmittner Date 2020-01-30 Time 11:07 Sent To  
Notes
***NONE***