Plan Review Details - Permit 20010892
Plan Review Stops For Permit 20010892
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-01-31 Cont ID  
Sent By rmcdouga Date 2020-01-31 Time 08:05 Rev Time 0.00
Received By rmcphers Date 2020-01-31 Time 07:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-03-19 Cont ID  
Sent By fgiaquin Date 2020-03-19 Time 22:08 Rev Time 0.00
Received By fgiaquin Date 2020-03-19 Time 19:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-02-14 Cont ID  
Sent By fgiaquin Date 2020-02-14 Time 06:19 Rev Time 0.00
Received By fgiaquin Date 2020-02-13 Time 10:32 Sent To  
Notes
2020-02-14 06:18:35ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL DESIGNS OVER 240VOLTS OR $125,000 MUST BE
 DESIGNED AND SIGNED SEALED BY A DESIGN PROFESSIONAL.
 ELECTRONICALLY SUBMITTED DOCUMENTS MUST BE DIGIALLY
 SIGNED.
  
 471.003?QUALIFICATIONS FOR PRACTICE; EXEMPTIONS.
  
 (H)?ANY ELECTRICAL, PLUMBING, AIR-CONDITIONING, OR
 MECHANICAL CONTRACTOR WHOSE PRACTICE INCLUDES THE
 DESIGN AND FABRICATION OF ELECTRICAL, PLUMBING,
 AIR-CONDITIONING, OR MECHANICAL SYSTEMS, RESPECTIVELY,
 WHICH SHE OR HE INSTALLS BY VIRTUE OF A LICENSE ISSUED
 UNDER CHAPTER 489, UNDER PART I OF CHAPTER 553, OR
 UNDER ANY SPECIAL ACT OR ORDINANCE WHEN WORKING ON ANY
 CONSTRUCTION PROJECT WHICH:
  
 1. REQUIRES AN ELECTRICAL OR PLUMBING OR
 AIR-CONDITIONING AND REFRIGERATION SYSTEM WITH A VALUE
 OF $125,000 OR LESS; AND
 2. REQUIRES AN AGGREGATE SERVICE CAPACITY OF 600
 AMPERES (240 VOLTS) OR LESS ON A RESIDENTIAL ELECTRICAL
 SYSTEM OR 800 AMPERES (240 VOLTS) OR LESS ON A
 COMMERCIAL OR INDUSTRIAL ELECTRICAL SYSTEM.
  
  
  
 2.PROVIDE NOTE ON PLAN STATING LOW VOLTAGE SHOWN WILL
 REQUIRE A SEPARATE LOW VOLTAGE PERMIT. FBC 105.1
  
 3. PROVIDE RISER DIAGRAM OF EXISTING SERVICE. NEC
 215.5; WPB FBC 107.2.1
  
 4.PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
  
 5.PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE
 MARKED WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT
 AVAILABLE PER NEC 110.24.
  
 6.CONDUCTOR SIZES FOR 30KVA TRANSFORMER SHOWN ON PLANS
 ARE INCORRECT. MUST BE #6 CU FOR PRIMARY AND #1/0
 SECONDARY. PROVIDE CORRECTION. NEC 110.14(C)(1)(A)(2),
 215.2(A)(1)(A), 310.15(B)(16) 240.21(C)
  
 7.PLAN SHOWS HIGH AND LOW VOLTAGE CONDUCTORS IN SAME
 CONDUIT FROM LCP TO FOUNTAIN. CANNOT MIX HIGH AND LOW
 VOLTAGE. PROVIDE CORRECTION. NEC 725.136B
  
 8.LCP IS FED WITH #12 WIRE BUT HAS A BRANCH CIRCUIT OF
 #8'S??? PROVIDE CORRECTION/CLARIFICATION. FBC 1`07.2.1
  
 9.NO PANEL SCHEDULE SHOWN FOR LCP. PROVIDE CORRECTION.
 FBC 107.2.1
  
 10. PLAN SHOWS "LCP TYPICAL OF 2" BUT ONLY SHOWS ONE
 LCP PANEL. PROVIDE CORRECTION/CLARIFICATION FBC 107.2.1
  
 11. 30KVA TRANSFORMER MUST HAVE GROUNDING ELECTRODE
 CONDUCTOR FROM A GROUNDING ELECTRODE SPECIFIED IN
 250.30A4 (1) OR (2) WHEN AVAILABLE. IF NOT AVAILABLE
 THEN ANOTHER SUPPLEMENTAL ELECTRODE WILL BE REQUIRED
 FOR TRANSFORMER. THE ONE GROUND ROD SHOWN DOES NOT
 SUFFICE. NEC 250.53A2
  
 12. PROVIDE CUT SHEETS OF ALL MATERIALS AND EQUIPMENT
 FOR PRODUCT APPROVAL. NEC 90.7, 110.2, 110.3B FBC
 107.2.1
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-03-19 Cont ID  
Sent By fgiaquin Date 2020-03-19 Time 22:08 Rev Time 0.00
Received By fgiaquin Date 2020-03-16 Time 10:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-02-20 Cont ID  
Sent By lmarchan Date 2020-02-20 Time 09:51 Rev Time 0.00
Received By lmarchan Date 2020-01-22 Time 07:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-03-19 Cont ID  
Sent By medwards Date 2020-03-19 Time 16:29 Rev Time 0.00
Received By medwards Date 2020-03-19 Time 16:29 Sent To  
Notes
2020-03-19 16:30:00PREVIOUS REVIEWERS COMMENTS WERE ADDRESSED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-02-11 Cont ID  
Sent By ccole Date 2020-02-11 Time 12:28 Rev Time 0.00
Received By ccole Date 2020-02-11 Time 12:18 Sent To  
Notes
2020-02-11 12:29:511ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20010892
 2/11/2020
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS F3.2 & F3.3: PROVIDE AN EXHAUST VENTILATION
 CALCULATION FOR THE EQUIPMENT ROOM TO INDICATE HOW THE
 FANS WERE SIZED- SECTION 107.2.1 WPB.
  
 2) F3.2 & F3.3: PROVIDE THE SEQUENCE OF OPERATION FOR
 THE FANS- SECTION 107.2.1 WPB.
  
 3) F3.2 & F3.3: PROVIDE A PRODUCT DATA SHEET FOR THE
 EXHAUST FANS THAT INCLUDES THE UL LISTING AND LABELING
 NUMBER. THE SUBMITTAL SHALL BEAR THE SHOP DRAWING
 APPROVAL STAMP AND SIGNATURE BY THE ENGINEER OF RECORD-
 SECTION 107.2.1 WPB.
  
 4) F3.2: PROVIDE A HAZARDOUS MATERIALS REPORT IN
 ACCORDANCE WITH SECTION 414.1.3 FBC B. INFORMATION
 REQUIRED.
 A REPORT SHALL BE SUBMITTED TO THE BUILDING OFFICIAL
 IDENTIFYING THE MAXIMUM EXPECTED QUANTITIES OF
 HAZARDOUS MATERIALS TO BE STORED, USED IN A CLOSED
 SYSTEM AND USED IN AN OPEN SYSTEM, AND SUBDIVIDED TO
 SEPARATELY ADDRESS HAZARDOUS MATERIAL CLASSIFICATION
 CATEGORIES BASED ON TABLES 307.1(1) AND 307.1(2). THE
 METHODS OF PROTECTION FROM SUCH HAZARDS, INCLUDING BUT
 NOT LIMITED TO CONTROL AREAS, FIRE PROTECTION SYSTEMS
 AND GROUP H OCCUPANCIES SHALL BE INDICATED IN THE
 REPORT AND ON THE CONSTRUCTION DOCUMENTS. THE OPINION
 AND REPORT SHALL BE PREPARED BY A QUALIFIED PERSON,
 FIRM OR CORPORATION APPROVED BY THE BUILDING OFFICIAL
 AND PROVIDED WITHOUT CHARGE TO THE ENFORCING AGENCY.
  
 5) F3.2: PROVIDE CONSTRUCTION DETAILS AND DIMENSIONED
 SECTION VIEWS FOR THE ACCESS LADDER AND SHIP'S LADDER-
 SEE SECTIONS 1011.15, 1011.16 FBC B, AND 306.5 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK "VOID" OR "OLD" ON THEM. PLEASE
 RETAIN THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS.
 THIS PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-02-10 Cont ID  
Sent By gjohnson Date 2020-02-10 Time 13:41 Rev Time 0.00
Received By gjohnson Date 2020-02-10 Time 09:23 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-03-19 Cont ID  
Sent By fgiaquin Date 2020-03-19 Time 22:08 Rev Time 0.00
Received By fgiaquin Date 2020-03-19 Time 22:08 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-02-25 Cont ID  
Sent By medwards Date 2020-02-25 Time 16:49 Rev Time 0.00
Received By medwards Date 2020-02-25 Time 16:49 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-02-18 Cont ID  
Sent By aaponte Date 2020-02-18 Time 11:00 Rev Time 0.00
Received By aaponte Date 2020-02-18 Time 11:00 Sent To  
Notes
***NONE***