| 2020-02-14 06:18:35 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. ELECTRICAL DESIGNS OVER 240VOLTS OR $125,000 MUST BE |
| | DESIGNED AND SIGNED SEALED BY A DESIGN PROFESSIONAL. |
| | ELECTRONICALLY SUBMITTED DOCUMENTS MUST BE DIGIALLY |
| | SIGNED. |
| | |
| | 471.003?QUALIFICATIONS FOR PRACTICE; EXEMPTIONS. |
| | |
| | (H)?ANY ELECTRICAL, PLUMBING, AIR-CONDITIONING, OR |
| | MECHANICAL CONTRACTOR WHOSE PRACTICE INCLUDES THE |
| | DESIGN AND FABRICATION OF ELECTRICAL, PLUMBING, |
| | AIR-CONDITIONING, OR MECHANICAL SYSTEMS, RESPECTIVELY, |
| | WHICH SHE OR HE INSTALLS BY VIRTUE OF A LICENSE ISSUED |
| | UNDER CHAPTER 489, UNDER PART I OF CHAPTER 553, OR |
| | UNDER ANY SPECIAL ACT OR ORDINANCE WHEN WORKING ON ANY |
| | CONSTRUCTION PROJECT WHICH: |
| | |
| | 1. REQUIRES AN ELECTRICAL OR PLUMBING OR |
| | AIR-CONDITIONING AND REFRIGERATION SYSTEM WITH A VALUE |
| | OF $125,000 OR LESS; AND |
| | 2. REQUIRES AN AGGREGATE SERVICE CAPACITY OF 600 |
| | AMPERES (240 VOLTS) OR LESS ON A RESIDENTIAL ELECTRICAL |
| | SYSTEM OR 800 AMPERES (240 VOLTS) OR LESS ON A |
| | COMMERCIAL OR INDUSTRIAL ELECTRICAL SYSTEM. |
| | |
| | |
| | |
| | 2.PROVIDE NOTE ON PLAN STATING LOW VOLTAGE SHOWN WILL |
| | REQUIRE A SEPARATE LOW VOLTAGE PERMIT. FBC 105.1 |
| | |
| | 3. PROVIDE RISER DIAGRAM OF EXISTING SERVICE. NEC |
| | 215.5; WPB FBC 107.2.1 |
| | |
| | 4.PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 |
| | |
| | 5.PROVIDE NOTE THAT THE SERVICE EQUIPMENT SHALL BE |
| | MARKED WITH THE MAXIMUM AVAILABLE SHORT CIRCUIT CURRENT |
| | AVAILABLE PER NEC 110.24. |
| | |
| | 6.CONDUCTOR SIZES FOR 30KVA TRANSFORMER SHOWN ON PLANS |
| | ARE INCORRECT. MUST BE #6 CU FOR PRIMARY AND #1/0 |
| | SECONDARY. PROVIDE CORRECTION. NEC 110.14(C)(1)(A)(2), |
| | 215.2(A)(1)(A), 310.15(B)(16) 240.21(C) |
| | |
| | 7.PLAN SHOWS HIGH AND LOW VOLTAGE CONDUCTORS IN SAME |
| | CONDUIT FROM LCP TO FOUNTAIN. CANNOT MIX HIGH AND LOW |
| | VOLTAGE. PROVIDE CORRECTION. NEC 725.136B |
| | |
| | 8.LCP IS FED WITH #12 WIRE BUT HAS A BRANCH CIRCUIT OF |
| | #8'S??? PROVIDE CORRECTION/CLARIFICATION. FBC 1`07.2.1 |
| | |
| | 9.NO PANEL SCHEDULE SHOWN FOR LCP. PROVIDE CORRECTION. |
| | FBC 107.2.1 |
| | |
| | 10. PLAN SHOWS "LCP TYPICAL OF 2" BUT ONLY SHOWS ONE |
| | LCP PANEL. PROVIDE CORRECTION/CLARIFICATION FBC 107.2.1 |
| | |
| | 11. 30KVA TRANSFORMER MUST HAVE GROUNDING ELECTRODE |
| | CONDUCTOR FROM A GROUNDING ELECTRODE SPECIFIED IN |
| | 250.30A4 (1) OR (2) WHEN AVAILABLE. IF NOT AVAILABLE |
| | THEN ANOTHER SUPPLEMENTAL ELECTRODE WILL BE REQUIRED |
| | FOR TRANSFORMER. THE ONE GROUND ROD SHOWN DOES NOT |
| | SUFFICE. NEC 250.53A2 |
| | |
| | 12. PROVIDE CUT SHEETS OF ALL MATERIALS AND EQUIPMENT |
| | FOR PRODUCT APPROVAL. NEC 90.7, 110.2, 110.3B FBC |
| | 107.2.1 |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |