Plan Review Details - Permit 20010871
Plan Review Stops For Permit 20010871
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2020-02-05 Cont ID  
Sent By cpuell Date 2020-02-05 Time 17:05 Rev Time 0.00
Received By cpuell Date 2020-02-05 Time   Sent To  
Notes
2020-02-05 17:06:32NEW ADDRESS WILL BE 5145 WILLOW POND RD W - CONTACTED
 ALL AGENCIES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-03-10 Cont ID  
Sent By jgomez Date 2020-03-10 Time 10:21 Rev Time 0.00
Received By jgomez Date 2020-03-10 Time 10:12 Sent To  
Notes
2020-03-10 10:50:06BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- THERE IS A DISCREPANCY BETWEEN THE FOOTING SIZE
 RECOMMENDED BY THE SOIL TEST ENGINEER AND THE FOOTING
 SIZE SPECIFIED ON PLANS. DESIGNER OF RECORD TO REVIEW
 SOIL TEST REPORT RECOMMENDATIONS AND EITHER CHANGE THE
 FOOTING SIZE FOLLOWING THE ENGINEER'S RECOMMENDATIONS
 OR PROVIDE DOCUMENTATION SHOWING THAT THE PROPOSED
 FOOTING SIZE IS ADEQUATE. SEC. 107.2.1 CITY AMENDMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-02-04 Cont ID  
Sent By jgomez Date 2020-02-04 Time 10:26 Rev Time 0.00
Received By jgomez Date 2020-02-03 Time 17:35 Sent To  
Notes
2020-02-04 10:27:23NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
 ****IF PROVISO OPTION IS SELECTED, THEN NEED THE ENRGY
 CALCULATIONS SIGNED BY THE OWNER PRIOR TO PERMIT
 ISSUANCE.
  
  
  
 1- ENERGY CALCULATIONS SUBMITTED:
 A)THE ENERGY FORM SUBMITTED DOESN'T SEEM TO BE SIGNED
 BY THE OWNER OF THIS BUILDING. THE OWNER'S SIGNATURE
 SHOWN ON THE PERMIT APPLICATION AND THE SIGNATURE SHOWN
 ON THE ENERGY CALCULATIONS DON'T MATCH. CLARIFY WHY.
 NOTE: ONLY THE OWNER, ARCHITECT OR LEGAL AGENT IS
 AUTHORIZED TO SIGN THIS FORM AS REQUIRED BY SEC.
 R103.1.1.2 FBC-ENERGY CONSERVATION, 6TH EDITION (2017).
  
 B) PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM. PROVIDE CORRECT OWNER'S AND BUILDER'S NAME.
 PROVIDE COMPLETE ADDRESS OF THIS HOUSE. PROVIDE THE
 PERMIT OFFICE.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C) WALL INFORMATION ON ITEM 9 ON PAGE 1 OF 4 IS MISSING
 THE INFORMATION FOR THE ADJACENT WALL BY THE GARAGE
 AREA. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D) REVISE THE ATTIC VENT RATIO ON PAGE 2 OF 5. THE
 RATIO IS 1/150 NOT 1/300. SEC. R806.2 FBC-RESIDENTIAL.
 OR, PERSON PREPARING THE ENERGY CALCULATIONS TO PROVIDE
 COMPLETE DOCUMENTATION SHOWING COMPLIANCE WITH THE
 1/300 RATIO AS REQUIRED BY THE EXCEPTION ON SEC.
 R806.2.
  
 E) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 2- DRAWING C-1 (SITE/DRAINAGE PLAN):
 DRAWING SUBMITTED HAVE A COPY OF A DIGITAL SIGNATURE.
 PERMIT APPLICATION AND PLANS ARE NOT ELECTRONICALLY
 SUBMITTED. PLANS NEED TO HAVE THE ORIGINAL SEAL AND
 SIGNATURE OF THE ENGINEER OF RECORD AS REQUIRED BY SEC.
 61G15-23.003 FAC AND CHAPTER 471 F.S. WHEN SUBMITTING
 PLANS/DOCUMENTS FOR PUBLIC RECORDS.
  
 3- THERE IS A DISCREPANCY BETWEEN THE FOOTING SIZE
 RECOMMENDED BY THE SOIL TEST ENGINEER AND THE FOOTING
 SIZE SPECIFIED ON PLANS. DESIGNER OF RECORD TO REVIEW
 SOIL TEST REPORT RECOMMENDATIONS AND EITHER CHANGE THE
 FOOTING SIZE FOLLOWING THE ENGINEER'S RECOMMENDATIONS
 OR PROVIDE DOCUMENTATION SHOWING THAT THE PROPOSED
 FOOTING SIZE IS ADEQUATE. SEC. 107.2.1 CITY AMENDMENTS.
  
 4- SOIL TEST REPORT SUBMITTED HAVE A COPY OF THE
 ENGINEER'S SIGNATURE. PROVIDE REPORT WITH ENGINEER'S
 ORIGINAL SEAL AND SIGNATURE (2 COPIES) AS REQUIRED BY
 CHAPTER 471 F.S. WHEN SUBMITTING DOCUMENTS FOR PUBLIC
 RECORDS.
  
 5- REVISE ATTIC ACCESS DETAIL ON SHEET A-1. THE MIN.
 DIMENSION IS 22" AS REQUIRED BY SEC. R807.1
 FBC-RESIDENTIAL.
  
 6- REVISE SPECS FOR GARAGE DOOR LEADING TO THE
 RESIDENCE. IF THE DOOR IS NOT SOLID, THEN IT NEEDS TO
 BE HONEYCOMB CORE STEEL DOOR NOT METAL CLADD DOOR. OR
 20 MINUTE FIRE RATED DOOR. SEC. R302.5.1
 FBC-RESIDENTIAL. REVISE DOOR SCHEDULE SPECS ON SHEET
 A-1.
  
 7- REVISE THE SIZE OF THE STRUCTURAL BUCK SPECIFIED ON
 DETAIL C ON SHEET A-2. STRUCTURAL BUCK NEEDS TO PROVIDE
 FULL SUPPORT TO THE DOOR FRAME AND NEED TO EXTEND
 BEYOND THE INTERIOR FACE OF THE WINDOW OR DOOR FRAME AS
 REQUIRED BY SEC. R609.7.2.1 FBC-RESIDENTIAL. 2X4 BUCK
 IS SMALLER THAN THE DOOR FRAME. REVISE AS REQUIRED.
  
 8- WALL ENTRY SECTION #3 ON SHEET A-3:
 A) NEED TO SPECIFY 2 LAYERS OF WATER RESISTIVE BARRIERS
 AS REQUIRED BY SEC. R703.7.3 FBC-RESIDENTIAL ON THE
 WOOD FRAMED WALL.
  
 B) NEED TO SPECIFY THE 7/8" MIN. STUCCO THICKNESS AS
 REQUIRED BY TABLE R702.1(1) FBC-RESIDENTIAL.
  
 9- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW.
 VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S
 OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS
 REQUIRED BY SEC. 109.3 CITY AMENDMENTS. VALUATION WAS
 UPDATED TO $204,585. THE PERMIT FEE BALANCE IS $4718.42
 (INCLUDES PLAN REVIEW EXPEDITED FEE).
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. (NOTE: SUBMIT OLD DRAWINGS FOR REFERENCE). A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-01-28 Cont ID  
Sent By jpearson Date 2020-01-28 Time 14:55 Rev Time 0.00
Received By jpearson Date 2020-01-28 Time 14:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-03-25 Cont ID  
Sent By pvalenti Date 2020-03-25 Time 08:00 Rev Time 0.00
Received By pvalenti Date 2020-03-24 Time 13:36 Sent To  
Notes
2020-03-24 13:36:30RESUB ROUTED TO PVALENTI

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-03-10 Cont ID  
Sent By jgomez Date 2020-03-10 Time 11:34 Rev Time 0.00
Received By jgomez Date 2020-02-21 Time 10:32 Sent To I
Notes
2020-02-25 10:32:50R32

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-02-04 Cont ID  
Sent By jgomez Date 2020-02-04 Time 10:32 Rev Time 0.00
Received By jgomez Date 2020-01-22 Time 16:09 Sent To I
Notes
2020-01-23 16:10:17R12

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2020-03-04 Cont ID  
Sent By pvalenti Date 2020-03-04 Time 13:50 Rev Time 0.00
Received By pvalenti Date 2020-03-04 Time 13:50 Sent To  
Notes
2020-03-04 14:09:09PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 IMPACT REVIEW APPROVED:
  
 THE PERMIT SET WAS STAMPED BY THE COUNTY FOR IMPACT
 FEES.
  
 COUNTY NUMBER: MU-2020-004596-0000

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-02-04 Cont ID  
Sent By jgomez Date 2020-02-04 Time 10:29 Rev Time 0.00
Received By jgomez Date 2020-02-04 Time 10:29 Sent To  
Notes
2020-02-04 10:29:59IMPACT FEES -
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK
 OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW.
 PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT
 AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2020-03-26 Cont ID  
Sent By pvalenti Date 2020-03-26 Time 08:55 Rev Time 0.00
Received By pvalenti Date 2020-03-26 Time 08:55 Sent To  
Notes
2020-03-26 08:57:18PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 MECHANICAL REVIEW APPROVED
  
 NOTE: A MECHANICAL SUB PERMIT IS REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2020-03-25 Cont ID  
Sent By pvalenti Date 2020-03-25 Time 07:55 Rev Time 0.00
Received By pvalenti Date 2020-03-25 Time 07:55 Sent To  
Notes
2020-03-25 08:00:01***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561?805?6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 3RD MECHANICAL REVIEW DENIED:
  
 REFER TO SECTION M1602.3 BALANCED RETURN AIR. 2017
 RESIDENTIAL CODE.
 THE CFMS SHOWN ON THE PLANS COMPARED WITH THE CFMS
 FROM THE A/C UNIT, AS SHOWN ON THE ENERGY CALCULATIONS,
 ARE NOT BALANCED, THE SUBMITTED PLAN INDICATES A TOTAL
 OF 1,160 CFM OF SUPPLY AIR AND THE ENERGY CALCULATIONS
 INDICATE 750 CFM.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-03-04 Cont ID  
Sent By pvalenti Date 2020-03-04 Time 13:36 Rev Time 0.00
Received By pvalenti Date 2020-03-04 Time 11:16 Sent To  
Notes
2020-03-04 13:40:37***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 2ND MECHANICAL REVIEW DENIED:
  
  
 1) OK
  
 2) REFER TO SECTION M1602.3 BALANCED RETURN AIR. 2017
 RESIDENTIAL CODE.
 (THE CFMS SHOWN ON THE PLANS COMPARED WITH THE CFMS
 FROM THE A/C UNIT, AS SHOWN ON THE ENERGY CALCULATIONS,
 ARE NOT BALANCED.)
  
 3) ADDRESS ON PLAN AND APPLICATION DO NOT MATCH.
 (THE PLANS NEED TO HAVE THE SAME ADDRESS AS THE
 APPLICATION.)
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-01-29 Cont ID  
Sent By hmoser Date 2020-01-29 Time 10:14 Rev Time 0.00
Received By hmoser Date 2020-01-29 Time 09:46 Sent To  
Notes
2020-01-29 10:14:45PLAN DENIED
 1) PROVIDE CFM ON ALL SUPPLY DUCT. PER SECTION 107 FBC.
 2) REFER TO SECTION M1602.3 BALANCED RETURN AIR. 2017
 RESIDENTIAL CODE.
 3) ADDRESS ON PLAN AND APPLICATION DO NOT MATCH.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-01-24 Cont ID  
Sent By lcrespo Date 2020-01-24 Time 14:21 Rev Time 0.00
Received By lcrespo Date 2020-01-24 Time 14:06 Sent To  
Notes
2020-01-24 14:21:0601/24/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM
 [email protected]
 561-701-6437
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2020-02-04 Cont ID  
Sent By jgomez Date 2020-02-04 Time 10:30 Rev Time 0.00
Received By jgomez Date 2020-02-04 Time 10:29 Sent To  
Notes
2020-02-04 10:32:24SHINGLES NOA 17-0706.07
  
 SHINGLES HIP $ RIDGE. SHINGLES STARTER STRIP NOA
 19-0109.03

Review Stop Z ZONING
Rev No 1 Status P Date 2020-01-27 Cont ID  
Sent By rfalcone Date 2020-01-27 Time 16:22 Rev Time 0.00
Received By rfalcone Date 2020-01-27 Time 16:22 Sent To I
Notes
***NONE***