Plan Review Details - Permit 20010867
Plan Review Stops For Permit 20010867
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-09-03 Cont ID  
Sent By fgiaquin Date 2020-09-03 Time 20:42 Rev Time 0.00
Received By fgiaquin Date 2020-09-03 Time 20:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-08-10 Cont ID  
Sent By fgiaquin Date 2020-08-10 Time 20:46 Rev Time 0.00
Received By fgiaquin Date 2020-08-10 Time 19:46 Sent To  
Notes
2020-08-10 19:57:47ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PERMIT APPLICATION IS NOT COMPLETE. THERE IS NO
 CONTRACTOR OR OWNER BUILDER DESIGNATION AND THE PERMIT
 APPLICATION IS NOT SIGNED. PLEASE PROVIDE CORRECTIONS.
 FBC 107.2.1
  
 2. THERE IS A NEW 200AMP FUSED 2P SWITCH SHOWN ON PLAN.
 PROVIDE RISER DIAGRAM OF EXISTING SERVICE AND TO SHOW
 NEW PROPOSED WORK. PROVIDE CONDUIT SIZE, WIRE SIZE, OCP
 ECT. FBC 107.2.1 NEC 220
  
 3. PROVIDE LOAD CALCULATION SHOWING ALL LOADS BOTH NEW
 AND EXISTING. NEC 220
  
 4. EXTERIOR LIGHTING MUST COMPLY WITH FBC EC 405.2.5
 AND MUST BE CONTROLLED BY A TIMER SWITCH CAPABLE OF
 RETAINING THE HOME TIME SETTING IN THE EVENT OF UP TO A
 10 HR POWER LOSS.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-09-03 Cont ID  
Sent By fgiaquin Date 2020-09-03 Time 20:42 Rev Time 0.00
Received By fgiaquin Date 2020-08-24 Time 09:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-08-10 Cont ID  
Sent By fgiaquin Date 2020-08-10 Time 20:46 Rev Time 0.00
Received By fgiaquin Date 2020-07-20 Time 16:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-09-03 Cont ID  
Sent By fgiaquin Date 2020-09-03 Time 20:42 Rev Time 0.00
Received By fgiaquin Date 2020-09-03 Time 20:42 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-08-10 Cont ID  
Sent By fgiaquin Date 2020-08-10 Time 20:46 Rev Time 0.00
Received By fgiaquin Date 2020-08-10 Time 20:46 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-09-02 Cont ID  
Sent By elevesqu Date 2020-09-02 Time 10:48 Rev Time 0.00
Received By elevesqu Date 2020-09-02 Time 10:48 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-07-22 Cont ID  
Sent By elevesqu Date 2020-07-22 Time 13:04 Rev Time 0.00
Received By elevesqu Date 2020-07-22 Time 13:04 Sent To  
Notes
2020-07-22 13:04:23PLEASE PROVIDE PHOTOMETRIC FOR ALL BUIDLING ENTRANCES
 AND FOR FRONT ASPHALT AREA (OFF SAPODILLA) BETWEEN CURB
 AND COURTYARD- CAN USE EXTERNAL EXISTING SOURCES
 SECTIONS OF COURTYARD THAT AREA AT 0.0 NEED TO BE
 MINIMUM 0.6
  
 PLEASE PROVIDE PHOTOMETRIC FOR DUMPSTER ENCLOSURE AREA-
 MUST BE MINIMUM 0.6
  
 SECTION 94-113 (B):
 EXTERIOR LIGHTING. ALL BUILDINGS SHALL PROVIDE EXTERIOR
 LIGHTING EVERY NIGHT FROM DUSK TO DAWN TO ILLUMINATE
 BUILDING ENTRANCES, ADJACENT SIDEWALKS, AND PATHS, AT A
 MINIMUM OF 0.6 FOOTCANDLES AS MEASURED AT THE BACK EDGE
 OF THE CURB AND ONE FOOT ABOVE THE SIDEWALK. THIS
 MEASUREMENT SHALL INCLUDE LIGHT EMANATING FROM PUBLIC
 AND PRIVATE SOURCES. UNSHIELDED LIGHT FIXTURES SHALL BE
 PROHIBITED.
  