Plan Review Details - Permit 20010856
Plan Review Stops For Permit 20010856
Review Stop E ELECTRICAL
Rev No 3 Status N Date 2020-05-20 Cont ID  
Sent By lmarchan Date 2020-05-20 Time 07:38 Rev Time 0.00
Received By lmarchan Date 2020-05-20 Time 07:38 Sent To  
Notes
2020-05-20 07:39:10SEE REVIEWS UNDER 20041110.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-05-15 Cont ID  
Sent By jpearson Date 2020-05-15 Time 07:51 Rev Time 0.00
Received By jpearson Date 2020-05-15 Time 07:51 Sent To  
Notes
2020-05-15 07:32:26ELECTRICAL RE-WIRING DONE WITHOUT PERMIT PER EMAIL FROM
 CONTRACTOR.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR
 THE DESIGN. PROVIDE CORRECTION. FS 481.229; WPB FBC
 107.1, 107.2.1, 107.3.5.1.2 (NOT PROVIDED.)
 2. QUALITY OF BUILDING PLANS. BUILDING PLANS SHALL BE
 DRAWN TO A MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL
 PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. THE BUILDING
 OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY,
 OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, IN ORDER
 TO PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE
 WITH THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES. WPB
 FBC 107.2.1.3 (NOT PROVIDED.)
 3. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3 (NOT PROVIDED.)
 4. CORRECTED.
 5. CORRECTED.
 6. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902 (NOT
 PROVIDED.)
 7. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902;
 FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2 AS APPLICABLE.
 (NOT PROVIDED.)
 8. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR RECEPTACLE OUTLETS. RECEPTACLES SHALL
 BE INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6
 FEET FROM A RECEPTACLE OUTLET. THE WALL SPACING
 REQUIREMENTS FOR KITCHEN COUNTER SPACE STATE THAT
 RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT NO POINT
 ALONG THE WALL LINE IS MORE THAN 24 INCHES MEASURED
 HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT SPACE.
 THE PLAN PROVIDED DOES NOT SHOW COMPLIANCE. PROVIDE
 CORRECTION. NEC 210.52(C)(1); FBC RE E3901 (NOT
 PROVIDED.)
 9. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING
 ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS
 NEW INSTALLATIONS, OR PROVIDE A NOTE REQUIRING
 COMPLIANCE. FBC RE R314.3, R315.1; WPB FBC 107.2.1 (NOT
 PROVIDED.)
 10. AS THE PLAN PROVIDED IS SEVERELY LACKING IN
 REQUIRED INFORMATION, IT IS POSSIBLE THAT ADDITIONAL
 COMMENTS MAY BE NECESSARY THAT ARE NOT ADDRESSED IN
 THIS REVIEW. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-01-23 Cont ID  
Sent By jpearson Date 2020-01-23 Time 09:55 Rev Time 0.00
Received By jpearson Date 2020-01-23 Time 09:54 Sent To I
Notes
2020-01-23 09:47:23ELECTRICAL RE-WIRING DONE WITHOUT PERMIT PER EMAIL FROM
 CONTRACTOR.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR
 THE DESIGN. PROVIDE CORRECTION. FS 481.229; WPB FBC
 107.1, 107.2.1, 107.3.5.1.2
 2. QUALITY OF BUILDING PLANS. BUILDING PLANS SHALL BE
 DRAWN TO A MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL
 PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. THE BUILDING
 OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL POLICY,
 OTHER STANDARDS FOR PLANS AND SPECIFICATIONS, IN ORDER
 TO PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE
 WITH THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES. WPB
 FBC 107.2.1.3
 3. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
 4. PROVIDE RISER DIAGRAM OF EXISTING SERVICE. NEC
 215.5; WPB FBC 107.2.1
 5. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE
 E3602.2
 6. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
 7. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902;
 FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2 AS APPLICABLE.
 8. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING
 REQUIREMENTS FOR RECEPTACLE OUTLETS. RECEPTACLES SHALL
 BE INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6
 FEET FROM A RECEPTACLE OUTLET. THE WALL SPACING
 REQUIREMENTS FOR KITCHEN COUNTER SPACE STATE THAT
 RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT NO POINT
 ALONG THE WALL LINE IS MORE THAN 24 INCHES MEASURED
 HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT SPACE.
 THE PLAN PROVIDED DOES NOT SHOW COMPLIANCE. PROVIDE
 CORRECTION. NEC 210.52(C)(1); FBC RE E3901
 9. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING
 ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS
 NEW INSTALLATIONS, OR PROVIDE A NOTE REQUIRING
 COMPLIANCE. FBC RE R314.3, R315.1; WPB FBC 107.2.1
 10. AS THE PLAN PROVIDED IS SEVERELY LACKING IN
 REQUIRED INFORMATION, IT IS POSSIBLE THAT ADDITIONAL
 COMMENTS MAY BE NECESSARY THAT ARE NOT ADDRESSED IN
 THIS REVIEW. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-05-20 Cont ID  
Sent By lmarchan Date 2020-05-20 Time 07:38 Rev Time 0.00
Received By lmarchan Date 2020-05-19 Time 09:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-05-15 Time   Rev Time 0.00
Received By lmarchan Date 2020-05-04 Time 08:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-01-23 Cont ID  
Sent By jpearson Date 2020-01-23 Time 09:55 Rev Time 0.00
Received By jpearson Date 2020-01-23 Time 09:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-05-15 Cont ID  
Sent By jpearson Date 2020-05-15 Time 07:51 Rev Time 0.00
Received By jpearson Date 2020-05-15 Time 07:51 Sent To  
Notes
2020-05-15 07:51:00PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED (AND SEALED IF APPLICABLE) BY
 THE PERSON RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN
 REQUIRES A DIGITAL SIGNATURE WITH THE PROPER THIRD
 PARTY VERIFICATION. PROVIDE CORRECTION. ALTERNATIVELY,
 A SIGNED/SEALED PAPER SET MAY BE SUPPLIED TO THE
 BUILDING DEPARTMENT WHEN ALL TRADES ARE APPROVED. WPB
 FBC 107.1; FS 471/481