Plan Review Details - Permit 20010838
Plan Review Stops For Permit 20010838
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-07-01 Cont ID  
Sent By jwitmer Date 2020-07-01 Time 08:25 Rev Time 0.00
Received By jwitmer Date 2020-07-01 Time 08:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-03-12 Cont ID  
Sent By jwitmer Date 2020-03-12 Time 15:15 Rev Time 0.00
Received By jwitmer Date 2020-03-12 Time 14:50 Sent To  
Notes
2020-03-12 15:14:582017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20010838
 ADD: 418 N SAPODILLA AVENUE
 CONT: TBD/ TO BE DETERMINED
 TEL: ????????
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
 2ND REVIEW
 DATE: THURS. MARCH 12/ 2020
 ACTION: BUILDING PROVISO
 1) BUILDING PROVISO: DEFERRED SUBMITTAL FOR THE WINDOW
 PRODUCT APPROVAL ASSURA WINDOWS, FIXED WINDOWS, SERIES
 200, FLORIDA APPROVAL: FL 21878.2. W. P. B. 107.3.4.1
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED
 BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
 SHEET A5-0 NOTE 3 STATES THE G. C. AND WINDOW MANUF. /
 INSTALLER TO PROVIDE DETAIL SHOP DRAWINGS OF ALL NEW
 WINDOW FOR ARCH. REVIEW AND APPROVAL PRIOR TO
 INSTALLATION.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-02-11 Cont ID  
Sent By jwitmer Date 2020-02-11 Time 13:27 Rev Time 0.00
Received By jwitmer Date 2020-02-11 Time 09:38 Sent To  
Notes
2020-02-11 13:27:332017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20010838
 ADD: 418 N SAPODILLA AVENUE
 CONT: TBD/ TO BE DETERMINED
 TEL: ????????
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. FEB. 11/ 2020
 ACTION: DENIED
  
 1) SHEET 006-A1-2 THE HANDICAP PARKING DETAIL # 2 HAS A
 DISCREPANCY WITHIN THE LOWER LEFT BUBBLED DETAIL. WHEN
 LOOKING AT THE OVERALL DETAIL THE PLANS SHOW A DOUBLE
 SPACED LINE, A 4 INCH PAINTED STRIPE AND 1 FOOT BETWEEN
 THE DOUBLE STRIPES. THIS IS A CORRECT PRESENTATION TO
 THE CITY OF WEST PALM BEACHES PARKING STANDARD, CITY OF
 W. P. B. MUNI CODE ARTICLE XV 94-485 PARKING PROVIDES A
 DOUBLE LINED DIMENSIONED PARKING STALL DETAIL.
 THE ISSUE IS IN THE BUBBLED DETAIL TO THE LEFT. THE
 BUBBLED DETAIL INDICATES 6 INCH WIDE STRIPES AND 1FOOT
 6 INCHES BETWEEN LINES. PLEASE CORRECT THE BUBBLED
 DETAIL. THANK YOU.
  
 2) BUILDING PROVISO: DEFERRED SUBMITTAL FOR THE WINDOW
 PRODUCT APPROVAL ASSURA WINDOWS, FIXED WINDOWS, SERIES
 200, FLORIDA APPROVAL: FL 21878.2. W. P. B. 107.3.4.1
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED
 BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
 SHEET A5-0 NOTE 3 STATES THE G. C. AND WINDOW MANUF./
 INSTALLER TO PROVIDE DETAIL SHOP DRAWINGS OF ALL NEW
 WINDOW FOR ARCH. REVIEW AND APPROVAL PRIOR TO
 INSTALLATION.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2020-07-08 Cont ID  
Sent By fgiaquin Date 2020-07-08 Time 08:51 Rev Time 0.00
Received By fgiaquin Date 2020-07-07 Time 20:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-04-21 Cont ID  
Sent By jpearson Date 2020-04-21 Time 09:53 Rev Time 0.00
Received By jpearson Date 2020-04-21 Time 09:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-03-24 Cont ID  
Sent By fgiaquin Date 2020-03-24 Time 08:06 Rev Time 0.00
Received By fgiaquin Date 2020-03-24 Time 06:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-02-15 Cont ID  
Sent By fgiaquin Date 2020-02-15 Time 22:05 Rev Time 0.00
Received By fgiaquin Date 2020-02-13 Time 10:33 Sent To  
Notes
2020-02-15 21:54:22ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVICE NOTE ON PLAN STATING A SEPARATE FIRE ALARM
 PERMIT IS REQUIRED. FBC 105.1, FBC 107.2.1
  
 2. PROVIDE NOTE ON PLAN STATING A SEPARATE SITE
 LIGHTING PERMIT IS REQUIRED. FBC 105.1, FBC 107.2.1
  
 3. PROVIDE ACCURATE DIAGRAMS OF EXISTING SERVICES. ON
 POWER PLAN, IT IS ONLY LABELED AS "METER AND EXISTING
 PANEL" FOR BOTH SERVICES. ON ONE-LINE DIAGRAMS NO
 SERVICE DISCONNECTING MEANS ARE SHOWN AND PANELS ARE
 SHOWN AS MLO PANELS. SHOW SERVICE DISCONNECTING MEANS
 AND OCP SIZE. FBC 107.2.1
 NEC 215.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2020-07-02 Cont ID  
Sent By abelisle Date 2020-07-02 Time 15:19 Rev Time 0.00
Received By abelisle Date 2020-07-02 Time 15:19 Sent To  
Notes
2020-07-02 15:21:457/2/2020 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 1- SEPERATE PERMIT REQUIRED FOR GAS
  
 ATELYO BELISLE
 PLUMBING PLAN EXAMINER
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2020-03-12 Cont ID  
Sent By fmittner Date 2020-03-12 Time 14:31 Rev Time 0.00
Received By fmittner Date 2020-03-12 Time 14:31 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2020-01-31 Cont ID  
Sent By fmittner Date 2020-01-31 Time 14:50 Rev Time 0.00
Received By fmittner Date 2020-01-31 Time 14:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2020-07-08 Cont ID  
Sent By lmarchan Date 2020-07-08 Time 10:27 Rev Time 0.00
Received By lmarchan Date 2020-06-29 Time 08:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2020-04-21 Time   Rev Time 0.00
Received By lmarchan Date 2020-04-15 Time 09:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-03-31 Cont ID  
Sent By lmarchan Date 2020-03-31 Time 11:18 Rev Time 0.00
Received By lmarchan Date 2020-03-31 Time 09:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-03-31 Cont ID  
Sent By lmarchan Date 2020-03-31 Time 07:52 Rev Time 0.00
Received By lmarchan Date 2020-03-09 Time 10:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-02-20 Cont ID  
Sent By lmarchan Date 2020-02-20 Time 07:47 Rev Time 0.00
Received By lmarchan Date 2020-01-23 Time 08:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2020-03-23 Cont ID  
Sent By ccole Date 2020-03-23 Time 16:20 Rev Time 0.00
Received By ccole Date 2020-03-23 Time 15:14 Sent To  
Notes
2020-03-23 16:21:39SEPARATE PERMIT AND PLANS REQUIRED FOR MECHANICAL
 ALTERATIONS.
 CCOLE- 3/23/20.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-02-10 Cont ID  
Sent By ccole Date 2020-02-10 Time 16:55 Rev Time 0.00
Received By ccole Date 2020-02-10 Time 14:53 Sent To  
Notes
2020-02-10 17:19:311ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20010838
 2/10/2020
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A2.1D & A2.1: PROVIDE A FRONT VIEW OF THE NEW
 COOKING LINE AND KITCHEN EXHAUST HOOD SHOWING THE
 REQUIRED CLEARANCES PER SECTION 507.4.1 FBC M:THE
 INSIDE LOWER EDGE OF CANOPY-TYPE TYPE I AND II
 COMMERCIAL HOODS SHALL OVERHANG OR EXTEND A HORIZONTAL
 DISTANCE OF NOT LESS THAN 6 INCHES (152 MM) BEYOND THE
 EDGE OF THE TOP HORIZONTAL SURFACE OF THE APPLIANCE ON
 ALL OPEN SIDES. THE VERTICAL DISTANCE BETWEEN THE FRONT
 LOWER LIP OF THE HOOD AND SUCH SURFACE SHALL NOT EXCEED
 4 FEET (1219 MM).
  
 2) A2.1D & A2.1: THE PHOTOS INDICATE THE HOOD DOES NOT
 HAVE THE REQUIRED 18" CLEARANCES TO THE COMBUSTIBLE
 DOOR TRIM AND THE ADJACENT DRYWALL. REFER TO SECTION
 507.2.6 FBC M: A TYPE I HOOD SHALL BE INSTALLED WITH A
 CLEARANCE TO COMBUSTIBLES OF NOT LESS THAN 18 INCHES
 (457 MM).
 EXCEPTION: CLEARANCE SHALL NOT BE REQUIRED FROM GYPSUM
 WALLBOARD OR 1/2-INCH (12.7 MM) OR THICKER CEMENTITIOUS
 WALLBOARD ATTACHED TO NONCOMBUSTIBLE STRUCTURES
 PROVIDED THAT A SMOOTH, CLEANABLE, NONABSORBENT AND
 NONCOMBUSTIBLE MATERIAL IS INSTALLED BETWEEN THE HOOD
 AND THE GYPSUM OR CEMENTITIOUS WALLBOARD OVER AN AREA
 EXTENDING NOT LESS THAN 18 INCHES (457 MM) IN ALL
 DIRECTIONS FROM THE HOOD.
  
 3) A2.1: INDICATE HOW MAKEUP AIR IS BEING PROVIDED TO
 THE HOOD- SECTION 508.1 FBC M.
  
 4) A2.1: INDICATE HOW COMBUSTION AIR WILL BE PROVIDED
 TO THE EXISTING GAS-FIRED 8 BURNER RANGE AND THE NEW
 GAS-FIRED FRYERS- SEE SECTION 304 FBC FG AND PROVIDE
 THE METHOD TO BE USED AND CALCULATIONS.
  
 5) A2.1: PROVIDE AN AIR BALANCE CALCULATION- SECTION
 508.1.2 FBC M.
  
 6) A2.1: NO MECHANICAL PLANS HAVE BEEN SUBMITTED
 HOWEVER THE CEILING IS GOING TO BE DEMOLISHED AND
 REPLACED. PLEASE SHOW ANY REQUIRED ALTERATIONS TO THE
 EXISTING DUCTWORK- SECTION 107.2.1 WPB.
  
 7) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW GAS
 FRYERS- SECTION 623.1 FBC FG.
  
 8) A SEPARATE PERMIT IS REQUIRED FOR MODIFICATIONS TO
 THE FIRE SUPPRESSION SYSTEM. PLEASE PLACE A NOTE ON THE
 PLAN ACCORDINGLY- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK "VOID" OR "OLD" ON THEM. PLEASE
 RETAIN THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS.
 THIS PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2020-07-02 Cont ID  
Sent By abelisle Date 2020-07-02 Time 15:45 Rev Time 0.00
Received By abelisle Date 2020-06-30 Time 15:44 Sent To  
Notes
2020-07-02 15:56:597/2/2020 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 1- SEPERATE PERMIT REQUIRED FOR PLUMBING, GAS,
 IRRIGATION, GREASE TRAP, BACKFLOW
  
 ATELYO BELISLE
 PLUMBING PLAN EXAMINER
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  

Review Stop P PLUMBING
Rev No 3 Status N Date 2020-03-31 Cont ID  
Sent By abelisle Date 2020-03-31 Time 09:33 Rev Time 0.00
Received By abelisle Date 2020-03-31 Time 09:33 Sent To  
Notes
2020-03-31 09:35:10SEPARATE PERMIT AND PLANS REQUIRED FOR ALL PLUMBING AND
 GAS ALTERATIONS.
 A. BELISLE - 3/31/20.

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-03-24 Cont ID  
Sent By abelisle Date 2020-03-24 Time 16:34 Rev Time 0.00
Received By abelisle Date 2020-03-18 Time 16:49 Sent To  
Notes
2020-03-24 16:46:363/24/2020 2ND PLUMBING REVIEW **DENIED** WITH COMMENTS
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 1) I HAVE RESEARCHED CITY RECORDS BACK TO 0000 AND
 THERE IS NO RECORD OF A PERMIT FOR THE INSTALLATION OF
 ANY GAS ON THIS PROPERTY. SINCE THERE IS NO RECORD OF
 GAS BEING PERMITED AT THIS ADDRESS PLEASE SUBMIT AN
 ISOMETRIC DRAWING THAT CLEARLY SHOWS THE LENGTH OF ALL
 CUT SECTIONS OF PIPE PER 2017 FBC FUEL GAS, SECS.
 402.4.1, 402.4.2. OR 2017 FBC FUEL GAS RES SECS.
 G2413.4.1, G2413.4.2. WPB AMENDMENTS TO THE FBC SEC.
 105.1.
  
 2)SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW GAS
 FRYER AND RANGE -FBC 2017 FG. SECTION 623.1
  
 3) SEPERATE PERMITS WILL BE REQUIRED FOR GREASE
 INTERCEPTOR, BACKLOW DEVICE, IRRIGATION, GENERAL
 PLUMBING, AND GAS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-02-13 Cont ID  
Sent By shill Date 2020-02-13 Time 16:57 Rev Time 0.00
Received By shill Date 2020-02-11 Time 17:58 Sent To  
Notes
2020-02-13 16:57:33REVIEWED REMOTELY BY TIM HUNT
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status P Date 2020-07-01 Cont ID  
Sent By abelisle Date 2020-07-01 Time 15:42 Rev Time 0.00
Received By abelisle Date 2020-07-01 Time 15:41 Sent To  
Notes
2020-07-01 15:42:39SEPERATE PERMIT REQUIRED FOR GREASE TRAP

Review Stop P-IRRIGATE IRRIGATION REVIEW
Rev No 1 Status P Date 2020-07-01 Cont ID  
Sent By abelisle Date 2020-07-01 Time 15:46 Rev Time 0.00
Received By abelisle Date 2020-07-01 Time 15:42 Sent To  
Notes
2020-07-01 15:45:577/1/2020 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 1-SEPERATE PERMIT REQUIRED FOR BACKFLOW PREVENTER AND
 IRRIGATION
  
 ATELYO BELISLE
 PLUMBING PLAN EXAMINER
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  
  

Review Stop PW PUBLIC WORKS
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2020-03-20 Time   Rev Time 0.00
Received By   Date 2020-03-20 Time   Sent To  
Notes
2020-03-20 15:43:53NO FURTHER COMMENTS FROM PUBLIC WORKS.

Review Stop PW PUBLIC WORKS
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2020-02-20 Time   Rev Time 0.00
Received By   Date 2020-02-20 Time   Sent To  
Notes
2020-02-20 07:36:26PLEASE PROVIDE THE FOLLOWINGS:
  
 1- WHERE VISIBLE TO THE PUBLIC, COMMERCIAL CONTAINERS
 SHALL BE STORED IN A CITY APPROVED ENCLOSURE
 OBSTRUCTING THE CONTAINERS VIEW FROM PERSONS USING THE
 SIDEWALK, STREET, OR THE COMMERCIAL ESTABLISHMENT'S
 FACILITIES, EXCEPT WHEN ENCLOSURES ARE PROHIBITED, SUCH
 AS IN DOWNTOWN ALLEYS, OR OTHERWISE APPROVED BY THE
 CITY. THIS REQUIREMENT INDICATED IN THE CODE OF
 ORDINANCES, SECTION 74-34-A-2-D. FOR A FREESTANDING
 SITE DUMPSTER ENCLOSURE, THE ENCLOSURE SHALL COMPLY
 WITH THE LATEST REVISION OF CITY OF WEST PALM BEACH
 GENERAL CONSTRUCTION-GARBAGE ENCLOSURE STANDARD, CG-8.
 THE ENCLOSURE DETAILS SHOWN ON SHEET A5.3 DOES NOT
 COMPLY WITH OUR LATEST ENCLOSURE SPEC.
 2- AUTO TURN FOR THE SANITATION SERVICE, FRONT LOADER
 TRUCK WITH THE FOLLOWING SPECS:
 - TRUCK LENGTH: 35 FT
 - TRUCK WIDTH: 11 FT
 - TURNING RADIUS:
 - SAE TURNING RADIUS: 32.5 FT
 - CURB-TO-CURB DIAMETER: 74 FT
 - WALL-TO-WALL DIAMETER: 86.3 FT
  
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 561-822-2045
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-07-08 Cont ID  
Sent By medwards Date 2020-07-08 Time 09:53 Rev Time 0.00
Received By medwards Date 2020-07-08 Time 09:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-04-21 Cont ID  
Sent By jpearson Date 2020-04-21 Time 09:53 Rev Time 0.00
Received By jpearson Date 2020-04-21 Time 09:53 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-03-31 Cont ID  
Sent By jpearson Date 2020-03-31 Time 11:16 Rev Time 0.00
Received By jpearson Date 2020-03-31 Time 11:16 Sent To  
Notes
2020-03-31 11:10:53PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN REQUIRES A
 DIGITAL SIGNATURE WITH THE PROPER THIRD PARTY
 VERIFICATION. SHEET E4.01 SHOWS AN INVALID SIGNATURE.
 FOR SHEET P3.02, THE ENGINEER SELF-CERTIFIED THE
 SIGNATURE. SELF-CERTIFICATION IS NOT ACCEPTABLE FOR
 ENGINEERS. PROVIDE CORRECTION. WPB FBC 107.1; FS
 471/481

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-02-26 Cont ID  
Sent By medwards Date 2020-02-26 Time 14:43 Rev Time 0.00
Received By medwards Date 2020-02-26 Time 14:42 Sent To  
Notes
2020-02-26 14:47:29ALL SHEETS OK FOR FIRST REVIEW.
 ANY ADDITIONAL SHEETS SUBMITTED TO BE DIGITALLY SIGNED.

Review Stop Z ZONING
Rev No 2 Status P Date 2020-03-18 Cont ID  
Sent By elevesqu Date 2020-03-18 Time 15:32 Rev Time 0.00
Received By elevesqu Date 2020-03-18 Time 15:32 Sent To  
Notes
2020-03-18 15:32:13 
  
  
 CONDITIONS OF APPROVAL:
 DUMPSTER ENCLOSURE SHALL BE SHIFTED 5 FEET WEST TO MEET
 MINIMUM 5 FOOT INTERIOR SETBACK
 THE NO PARKING AREA IN FRONT OF MECHANICAL EQUIPMENT
 AREAS HALL BE STRIPED TO DESIGNATE NO PARKING AREA
 ALL FENCES SHALL REQUIRE SEPARATE PERMIT
 ALL SIGNAGE TO REQUIRE SEPARATE PERMIT
 APPLICANT SHALL REMOVE JOGGING SIDEWALK PORTION FOR
 PEDESTIRAN GATE AND HAVE PEDESTRIAN GATE DIRECTLY FROM
 EXISTING SIDEWALK (SET BACK SO ONLY 18" OF GATE SWINGS
 ONTO SIDEWALK, OR INWARD SWINGING GATE). THIS IS TO
 REDUCE CONCRETE AREA AND RETAIN SOD AREA.
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2020-02-18 Cont ID  
Sent By elevesqu Date 2020-02-18 Time 15:24 Rev Time 0.00
Received By elevesqu Date 2020-02-18 Time 15:24 Sent To  
Notes
2020-02-18 15:24:25NEW FENCES SHALL REQUIRE SEPARATE PERMIT. FENCE GATES
 CANNOT SWING OUTWARD INTO PUBLIC SIDEWALK - PROVIDE
 INWARD SWINING GATE OR ROLLING GATE OR SETBACK FENCE TO
 ACCOMODATE NO MORE THAN 18" SWING INTO THE SIDEWALK
 (ALONG 4TH STREET)
 GATES FOR VEHICULAR ENTRY MUST BE SETBAK A MINIMUM OF
 20 FEET FROM PROPERTY LINE FOR VEHICULAR STACKING
 (94-111)
  
 LANDSCAPE TO BE REVIEWED THROUGH SEPARATE PERMIT -
 PLEASE REMOVE FROM PERMIT SET
  
 REMOVE EXISTING CHAIN LINK FENCE THAT IS STATE OF
 DISREPAIR AND REPLACE WITH OTHER FENCCE, OR INCLUDE
 LANDSCAPE HEDGE ALONG OUTSIDE IF REMAINING - ANY
 PROPOSED NEW FENCE CANNOT EXCEED FOUR FEET WITHIN FRONT
 SETBACK. CHAIN LINK CAN BE USED BUT REQUIRES A
 LANDSCAPE HEDGE BUFFER ON THE OUTSIDE PER HISTORIC
 REGULATIONS. ALUMINUM DOES NOT REQUIRE LANDSCAPE HEDGE
  
 PLEASE REMOVE CONCRETE SIDEWALK CONNECTING TO EXISTING
 COVERED WALKWAY THAT DOES NOT CONNECT TO SAPODILLA
 AVENUE SIDEWALK AND INCLUDE NEW SIDEWWALK CONNECTION
 THAT MEETS SIDEWALK ALONG SAPODILLA
  
 PARKING SPACES CANNOT BACK DIRECTLY INTO A ROW:
 REMOVE PARKING FROM SAPODILLA AVENUE AND CONNECT
 COURTYARD TO STREETSCAPE THROUGH PAVERS AND LANDSCAPE
 AREA (MAINTAINING CLEAR ADA ACCESS TO RAMP FROM
 SIDEWALK)
 REMOVE CURB CUT FROM SAPODIALL AVENUE. ADDITIONAL
 OPTION - LOOK INTO REQUIRED DIMENSIONS TO DETERMINE IF
 ADA SPACE ON SAPODILLA CAN BE A PARALLEL PARKING SPACE
 - NEED TO MEET SIDEWALK REQUIREMENTS (5 FEET) TO NOT
 IMPACT PEDESTRIAN TRAVEL
  
 PARKING LOT TO MEET CURRENT REQUIREMENTS FOR PARKING
 LOTS - SECTION 94-111 AND 94-113 (F)
 PLEASE INCLUDE DIMENSIONS FOR PARKING SPACES, OVERHANG
 AREA, AISLE WIDTH, CURB CUT WIDTH, ADA PATHWAY, ETC.
 MINIMUM 24' AISLE WIDTH REQUIRED AND 8.6'X18 PARKING
 SPACES FOR STANDARD SPACE
 SHOW DOUBLE STRIPING ON PLAN PER REQUIRED PARKING LOT
 DETAIL
  
  
 A MINIMUM THREE-FOOT BACK UP AREA SHALL BE PROVIDED AT
 THE TERMINUS OF ANY DEAD-END DRIVE AISLE TO ALLOW FOR
 VEHICLES TO SAFELY PULL OUT OF THE END PARKING SPACES.
 IN ADDITION, THE EQUIVALENT OF ONE PARKING SPACE AT THE
 TERMINUS OF A DEAD-END AISLE SHALL BE STRIPED AS A
 DEDICATED PULL-IN AREA FOR TURNING AROUND.. PROPOSED
 DUMPSTER ENCLOSURE GATES IS DIRECTLY BEHIND END PARKING
 SPACE - CANNOT INTERFERE WITH REQUIRED 24' AISLE WIDTH
 BEHIND PARKING SPACE
  
 LIGHT POLE AND GATE FOR MECHANICAL ENCLOSURES CANNOT BE
 LOCATED WITHIN 2 FEET OVERHANG FOR PARKING SPACES -
 PLEASE ENSURE TWO FOOT CLEARANCE AND RELOCATE AS
 NECESSARY . INCLUDE DIMENSION
  
 94-113(F) LANDSCAPE REQUIREMENTS (AS AMENDED THROUGH
 CODE REVISION CASE 19-08- NOT YET UPDATED IN MUNICODE):
 (1)SETBACKS AND LANDSCAPE BUFFER . SURFACE PARKING LOTS
 SHALL MEET THE MINIMUM GROUND FLOOR SETBACK
 REQUIREMENTS AS PROVIDED IN THE SUBDISTRICT BUILDING
 REQUIREMENTS TABLE. A FIVE-FOOT LANDSCAPE BUFFER SHALL
 BE PROVIDED IN ADDITION TO THE GROUND FLOOR SETBACK TO
 VISUALLY SCREEN PARKING AREAS. THE LANDSCAPE BUFFER
 SHALL BE COMPRISED OF A HEDGE PLANTED AT TWO-FOOT TO
 THREE-FOOT INTERVALS AND MAINTAINED AT A MAXIMUM HEIGHT
 OF 36 INCHES AT MATURITY. SHADE TREES SHALL BE PLANTED
 AT 30-FOOT INTERVALS. A FIVE-FOOT LANDSCAPE BUFFER
 SHALL ALSO BE PROVIDED MEETING THESE REQUIREMENTS FOR
 THE ENTIRE PERIMETER OF THE SURFACE LOT.
  
 (2)TERMINAL ISLANDS, INTERIOR ISLANDS, AND DIVIDER
 MEDIANS. ALL OTHER PARKING AREA LANDSCAPING SHALL MEET
 THE REQUIREMENTS OF CHAPTER XIV (LANDSCAPE SECTION)
  
  
 OVERFLOW PARKING: CLOSE EXISTING ENTRANCE AND REMOVE
 PAVEMENT AREA- CAN BE ACCESSED FROM OTHER PARKING LOT
 ENTRANCE (ONLY ONE ENTRANCE PERMITTED PER ROW)
 CONTINUE LANDSCAPE HEDGE ALONG THIS FRONTAGE TO SCREEN
 OVERFLOW PARKING AREA
  
  
 DUMPSTER ENCLOSURE TO MEET CITY REQUIREMENTS AND
 SUBJECT TO PUBLIC WORKS REVIEW FOR TRASH PICKUP (SEE
 PUBLIC WORKS REVIEW STOP COMMENTS)
 PROVIDE DUMPSTER ENCLOSURE DETAIL - CONCRETE PAD
 REQUIRED. ADD DIMENSIONS
  
 PROPOSED SIGN REQUIRES SEPARATE PERMIT - REQUIREMENT IN
 SECTION 94-110
  
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 [email protected]
 561 822 1426
  
  
  
  
  
  
  
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved