Plan Review Details - Permit 20010807
Plan Review Stops For Permit 20010807
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-01-27 Cont ID  
Sent By jbrooks Date 2020-01-27 Time 13:24 Rev Time 0.00
Received By jbrooks Date 2020-01-27 Time 13:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-02-13 Cont ID  
Sent By jleahy Date 2020-02-13 Time 14:24 Rev Time 0.00
Received By jleahy Date 2020-02-13 Time 14:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-02-04 Cont ID  
Sent By fgiaquin Date 2020-02-04 Time 06:54 Rev Time 0.00
Received By fgiaquin Date 2020-02-04 Time 06:21 Sent To I
Notes
2020-02-04 06:50:57ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. VALUE LOW FOR AMOUNT OF WORK SHOWN. PROVIDE ACCURATE
 VALUE OR VALUE WILL BE SET BY BUILDING OFFICIAL. FBC
 109.3
  
 2. PROVIDE WIRING DIAGRAM FOR LIGHTED SIGN (SIGN F).
 FBC 107.2.1
  
 3. SEPARATE ELECTRICAL PERMIT REQUIRED FOR PRIMARY
 VOLTAGE CIRCUIT TO NEW ILLUMINATED SIGN BY LICENSED
 ELECTRICIAN. REFERENCE PERMIT NUMBER OF
 APPLICATION/PERMIT WHEN RESUBMITTING THESE PLANS SO IT
 CAN BE VERIFIED. FBC 105.1 107.2.1
  
 SIGN CONTRACTORS F.S. 489.505 (#19) AND F.A.C.
 61G6-7.001 SPECIALTY ELECTRICAL CONTRACTORS (#2 SIGN
 SPECIALTY CONTRACTOR)
  
 THE SCOPE OF CERTIFICATION INCLUDES THE STRUCTURAL
 FABRICATION INCLUDING CONCRETE FOUNDATION, ERECTION,
 INSTALLATION, ALTERATION, REPAIR, SERVICE AND WIRING OF
 ELECTRICAL SIGNS AND OUTLINE LIGHTING. THE SCOPE OF
 CERTIFICATION SHALL NOT INCLUDE THE PROVISION OF, OR
 ANY ELECTRICAL WORK BEYOND, THE LAST DISCONNECT MEAN OR
 TERMINAL POINTS. HOWEVER, A CONTRACTOR CERTIFIED UNDER
 THIS SECTION MAY PROVIDE THE ELECTRICAL ENTRANCE
 REQUIREMENTS FOR METERING AND MAIN DISCONNECT OF REMOTE
 BILLBOARDS OR SIGNS WHICH ARE INDEPENDENT OF ANY
 STRUCTURE OR BUILDING AND WHICH REQUIRE NO MORE THAN
 TWENTY-FIVE (25) KILOWATTS AT TWO HUNDRED FIFTY (250)
 VOLTS MAXIMUM.
  
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-02-04 Cont ID  
Sent By fgiaquin Date 2020-02-04 Time 06:54 Rev Time 0.00
Received By fgiaquin Date 2020-01-21 Time 16:08 Sent To  
Notes
2020-01-28 11:18:08ROUTED TO ELECTRICAL BOX
2020-01-25 08:45:01ROUTED TO MISC 2

Review Stop Z ZONING
Rev No 1 Status P Date 2020-01-24 Cont ID  
Sent By jbrooks Date 2020-01-27 Time 13:24 Rev Time 0.00
Received By rfalcone Date 2020-01-24 Time 13:54 Sent To I
Notes
***NONE***