Plan Review Details - Permit 20010739
Plan Review Stops For Permit 20010739
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-02-15 Cont ID  
Sent By cthroop Date 2020-02-15 Time 10:49 Rev Time 0.00
Received By cthroop Date 2020-02-14 Time 08:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-01-31 Cont ID  
Sent By cthroop Date 2020-01-31 Time 11:37 Rev Time 0.00
Received By cthroop Date 2020-01-22 Time 13:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-02-15 Cont ID  
Sent By cthroop Date 2020-02-15 Time 10:54 Rev Time 0.00
Received By cthroop Date 2020-02-14 Time 08:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-01-31 Cont ID  
Sent By cthroop Date 2020-01-31 Time 10:12 Rev Time 0.00
Received By cthroop Date 2020-01-22 Time 13:53 Sent To  
Notes
2020-01-31 10:49:26PLAN REVIEW - ELECTRIC
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SMOKE ALARM AT BATH #3 APPEARS TOO CLOSE TO BATH.
 R314.3 LOCATION.
 SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
  
 SMOKE ALARMS SHALL BE INSTALLED NOT LESS THAN 3 FEET
 (914 MM) HORIZONTALLY FROM THE DOOR OR OPENING OF A
 BATHROOM THAT CONTAINS A BATHTUB OR SHOWER UNLESS THIS
 WOULD PREVENT PLACEMENT OF A SMOKE ALARM REQUIRED BY
 SECTION R314.3
  
 2. DISHWASHER OUTLET SHALL BE GFI PROTECTED.
  
 PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D);
 FBC RE E3902.10
  
 3. OUTLETS IN GARAGE SHALL BE GFI PROTECTED.
  
 GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE OUTLETS
 IN GARAGE. PROVIDE CORRECTION. NEC 210.8; FBC RE
 E3902.2
  
 4. PROVIDE NOTE ON PLAN - PROVIDE COMPLIANCE: A MINIMUM
 OF 75 PERCENT OF THE LAMPS IN PERMANENTLY INSTALLED
 LIGHTING FIXTURES SHALL BE HIGH-EFFICACY LAMPS OR A
 MINIMUM OF 75 PERCENT OF THE PERMANENTLY INSTALLED
 LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH EFFICACY
 LAMPS. A NOTE WILL SUFFICE. FBC EC C405.1, R404.1
  
 5. PROVIDE NOTE ON PLAN - AFCI PROTECTION. ALL BRANCH
 CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND
 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS,
 DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING, POWER
 OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH AFCI
 AND GFCI PROTECTION. PROVIDE CORRECTION. NEC 210.8,
 210.12; FBC RE E3902.16; FBC EX 607.1.1 OR 801.1,
 801.2, OR 901.2 AS APPLICABLE.
  
 6. PROVIDE INTERSYSTEM BONDING AT SERVICE.
  
 PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
  
 7. DISCONNECT IS REQUIRED AT EXTERIOR OF STRUCTURE -
 FEEDER CONDUCTORS EXCEED 8 FEET.
  
 NEC 230.70
  
 NOTICE: THE #1/0 THHN GROUNDED CONDUCTOR FROM
 DISCONNECT TO PANEL IS OVERSIZED. A #6 COPPER CONDUCTOR
 WOULD BE CODE COMPLIANT.
  
 TABLE 3908.12
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2020-02-15 Cont ID  
Sent By cthroop Date 2020-02-15 Time 11:06 Rev Time 0.00
Received By cthroop Date 2020-02-14 Time 08:31 Sent To  
Notes
2020-02-15 11:06:50SEPARATE GAS PERMIT AND ISO REQUIRED FOR GAS WH. CT

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-01-25 Cont ID  
Sent By cthroop Date 2020-01-25 Time 10:59 Rev Time 0.00
Received By cthroop Date 2020-01-25 Time 08:57 Sent To  
Notes
2020-01-25 11:01:55PLAN REVIEW - FUEL GAS
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 SUBMITTED PLAN INDICATES A GAS FIRED TANKLESS WATER
 HEATER SHALL BE INSTALLED.
  
 FUEL GAS PERMIT APPLICATION REQUIREMENTS
  
 GAS PLAN REVIEW
  
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-02-18 Cont ID  
Sent By lmarchan Date 2020-02-18 Time 07:52 Rev Time 0.00
Received By lmarchan Date 2020-02-07 Time 08:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-02-07 Cont ID  
Sent By lmarchan Date 2020-02-07 Time 11:47 Rev Time 0.00
Received By lmarchan Date 2020-01-21 Time 10:47 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2020-02-20 Cont ID  
Sent By lmarchan Date 2020-02-20 Time 07:31 Rev Time 0.00
Received By lmarchan Date 2020-02-07 Time 11:47 Sent To  
Notes
2020-02-18 09:51:29MU 2020-005136 - RECEIPT 2020-0218-315 - $1463.48 PAID
2020-02-07 11:47:512/7/20 EMAILED IMPACT FEE OFFICE. LEM

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2020-01-25 Cont ID  
Sent By cthroop Date 2020-01-25 Time 08:37 Rev Time 0.00
Received By cthroop Date 2020-01-22 Time 13:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-02-15 Cont ID  
Sent By cthroop Date 2020-02-15 Time 11:00 Rev Time 0.00
Received By cthroop Date 2020-02-14 Time 08:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-01-28 Cont ID  
Sent By cthroop Date 2020-01-28 Time 16:57 Rev Time 0.00
Received By cthroop Date 2020-01-22 Time 13:54 Sent To  
Notes
2020-01-28 17:54:07PLAN REVIEW - PLUMBING
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. IDENTIFY THE DISH WASHER ON SANITARY ISO.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. TUB AND SHOWER AT MASTER BATH GROUP SHALL BE
 INDEPENDENTLY CONNECTED TO WET VENT.
 P3108.1 HORIZONTAL WET VENT PERMITTED.
 EACH FIXTURE DRAIN SHALL CONNECT HORIZONTALLY TO THE
 HORIZONTAL BRANCH BEING WET VENTED OR SHALL HAVE A DRY
 VENT.
  
 3. HORIZONTAL WET VENT SHALL INCREASE IN SIZE TO 3
 INCHES AFTER INDEPENDENTLY CONNECTING SHOWER FROM
 M-BATH GROUP.
 TABLE P3801.3
  
 4. WASHING MACHINE MUST CONNECT TO THE HORIZONTAL WET
 VENT DOWNSTREAM OF THE WATER CLOSET FROM M-BATH GROUP.
 P3108.2.1 HORIZONTAL WET VENT.
  
  
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2020-01-25 Cont ID  
Sent By cthroop Date 2020-01-25 Time 08:57 Rev Time 0.00
Received By cthroop Date 2020-01-22 Time 13:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-02-15 Cont ID  
Sent By cthroop Date 2020-02-15 Time 10:54 Rev Time 0.00
Received By cthroop Date 2020-02-14 Time 08:31 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-01-25 Cont ID  
Sent By cthroop Date 2020-01-25 Time 08:37 Rev Time 0.00
Received By cthroop Date 2020-01-22 Time 13:53 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-02-07 Cont ID  
Sent By rfalcone Date 2020-02-07 Time 11:20 Rev Time 0.00
Received By rfalcone Date 2020-02-07 Time 11:20 Sent To I
Notes
***NONE***