Plan Review Details - Permit 20010717
Plan Review Stops For Permit 20010717
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-02-06 Cont ID  
Sent By rmcphers Date 2020-02-06 Time 14:42 Rev Time 0.00
Received By rmcphers Date 2020-02-06 Time 14:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-02-26 Cont ID  
Sent By jleahy Date 2020-02-26 Time 12:24 Rev Time 0.00
Received By jleahy Date 2020-02-26 Time 12:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-01-31 Cont ID  
Sent By rmcphers Date 2020-02-06 Time 14:42 Rev Time 0.00
Received By fgiaquin Date 2020-01-31 Time 07:13 Sent To I
Notes
2020-01-31 07:16:34ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SATISFY ZONING COMMENTS
  
 2. VALUE LOW FOR AMOUNT OF WORK SHOWN, PROVIDE ACCURATE
 VALUE OR VALUE WILL BE SET BY BUILDING OFFICIAL. FBC
 109.3
  
 3. ELECTRICAL PERMIT REQUIRED BY LICENSED ELECTRICIAN
 TO INSTALL 120V DISCONNECT WITHIN SIGHT OF SIGN PER
 600.6A1 NEC AND BRANCH CIRCUIT FOR SIGN. FBC 105.1
  
 PLEASE READ SCOPE OF WORK FOR ES SIGN SPECIALTY LICENSE
 BELOW:
  
 SIGN CONTRACTORS F.S. 489.505 (#19) AND F.A.C.
 61G6-7.001 SPECIALTY ELECTRICAL CONTRACTORS (#2 SIGN
 SPECIALTY CONTRACTOR)
  
 THE SCOPE OF CERTIFICATION INCLUDES THE STRUCTURAL
 FABRICATION INCLUDING CONCRETE FOUNDATION, ERECTION,
 INSTALLATION, ALTERATION, REPAIR, SERVICE AND WIRING OF
 ELECTRICAL SIGNS AND OUTLINE LIGHTING. THE SCOPE OF
 CERTIFICATION SHALL NOT INCLUDE THE PROVISION OF, OR
 ANY ELECTRICAL WORK BEYOND, THE LAST DISCONNECT MEAN OR
 TERMINAL POINTS. HOWEVER, A CONTRACTOR CERTIFIED UNDER
 THIS SECTION MAY PROVIDE THE ELECTRICAL ENTRANCE
 REQUIREMENTS FOR METERING AND MAIN DISCONNECT OF REMOTE
 BILLBOARDS OR SIGNS WHICH ARE INDEPENDENT OF ANY
 STRUCTURE OR BUILDING AND WHICH REQUIRE NO MORE THAN
 TWENTY-FIVE (25) KILOWATTS AT TWO HUNDRED FIFTY (250)
 VOLTS MAXIMUM.
  
 4. PROVIDE ELECTRICAL PLANS TO INDICATE COMPLIANCE WITH
 THE NEC ARTICLE 600 AND THE FBC EC CHAPTER 4 SECTION
 405.2.5.
  
 EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR FEEDER
 CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR OUT-LINE
 LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN EXTERNALLY
 OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL OPEN ALL
 UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN NEC
 600.6(A)(1)
  
 ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 405.1 SHALL
 HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR WHEN
 NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & TIME
 CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES
 SHALL BE CAPABLE OF RETAINING PROGRAMING DURING A LOSS
 OF POWER FOR A MINIMUM OF 10 HOURS. FBC-EC 405.2.5
  
 5. PROVIDE WIRING DIAGRAM FOR SIGN. FBC 107.2.1
  
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-02-06 Cont ID  
Sent By rmcphers Date 2020-02-06 Time 14:42 Rev Time 0.00
Received By rmcphers Date 2020-01-17 Time 16:04 Sent To E
Notes
2020-02-06 14:43:01PLANS TO PERMIT LIBRARY
2020-02-03 08:32:48M2
2020-01-22 16:35:54ROUTED TO ELEC 5K LESS

Review Stop Z ZONING
Rev No 2 Status P Date 2020-02-10 Cont ID  
Sent By rfalcone Date 2020-02-10 Time 08:53 Rev Time 0.00
Received By rfalcone Date 2020-02-10 Time 08:53 Sent To I
Notes
2020-02-10 08:54:11MISSED INFORMATION IN FIRST REVIEW. RF

Review Stop Z ZONING
Rev No 1 Status F Date 2020-01-21 Cont ID  
Sent By rfalcone Date 2020-01-21 Time 15:34 Rev Time 0.00
Received By rfalcone Date 2020-01-21 Time 15:34 Sent To I
Notes
2020-01-21 15:37:221/21/2020 FAILED.
  
 PLEASE PROVIDE THE MEASUREMENTS OF THE FRONT FACADE TO
 DETERMINE THE ALLOWED PERCENTAGE OF SIGN AREA
 PERMITTED.
  
 SEC. 94-408(A)(1)WALL-MOUNTED SIGNS. THE REQUIREMENTS
 FOR WALL MOUNTED SIGNS SHALL BE AS FOLLOWS:
 A.CONTENT: THE NAME, LOGO AND ADDRESS OF THE BUILDING
 AND BUILDING OCCUPANTS TO WHICH THE SIGN IS ACCESSORY,
 AND OTHER RELATED INFORMATION. IN ADDITION, SIGNS
 PERMITTED PURSUANT TO THIS SECTION MAY CONTAIN ANY
 NONCOMMERCIAL MESSAGE WHICH HAS NOT BEEN DECLARED BY A
 COURT OF COMPETENT JURISDICTION TO BE OBSCENE,
 DEFAMATORY OR OTHERWISE CONTRARY TO LAW.
 B.MAXIMUM SUM TOTAL AREA OF ALL SIGNS MOUNTED ON THE
 FRONT FACADE OF A BUILDING: 75 PERCENT OF THE AREA
 PERMITTED BY SECTION 94-409.
 C.MAXIMUM SUM TOTAL AREA OF ALL SIGNS MOUNTED ON A
 FACADE OTHER THAN THE FRONT FACADE: 75 PERCENT OF THE
 AREA PERMITTED BY SECTION 94-409.
 D.MAXIMUM NUMBER ON EACH BUILDING: ONE SIGN FOR EACH
 INDIVIDUAL BUSINESS OCCUPANT OF THE BUILDING, PLUS TWO
 ADDITIONAL SIGNS.
 E.MAXIMUM HEIGHT: NO HIGHER THAN THE BUILDING WALL ON
 WHICH IT IS MOUNTED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 RACHEL FALCONE, ASSOCIATE PLANNER
 DEVELOPMENT SERVICES DEPARTMENT
 E-MAIL: [email protected]
 TEL: (561) 822-1442
  