| 2020-02-04 06:04:39 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. FROM CUT SHEETS PROVIDED SEVERAL PRODUCTS ARE NOT UL |
| | OR OTHER NRTL (NATIONALLY RECOGNIZED TESTING |
| | LABORATORY) LISTED. |
| | |
| | UAP-AC-M-PRO NOT LISTED |
| | |
| | MXE-200 NOT LISTED |
| | |
| | NO LISTING'S PROVIDED FOR WIRELESS ACCESS POINTS (WAP). |
| | |
| | PROVIDE LISTINGS FOR ALL MATERIALS AND EQUIPMENT |
| | (INCLUDE LV CABLE) NEC 90.7, 110.2, 110.3B FBC 107.2.1 |
| | |
| | 2. DESIGNS OVER $125,000 MUST BE DESIGNED AND |
| | SIGNED/SEALED BY A DESIGN PROFESSIONAL (ENGINEER). F.S. |
| | 471.003(2)(H)1 |
| | |
| | 3. PROVIDE LOAD CALCULATION, PANEL SCHEDULE, AND |
| | ANNOTATE ON PLAN THE CIRCUIT NUMBERS FOR NEW OR |
| | EXISITNG CIRCUITS USED TO POWER NEW PARKING GUIDANCE |
| | SYSTEM/ LIGHING/ AND RECEPTACLES. FBC 107.2.1 NEC 220 |
| | |
| | INFORMATIONAL NOTE: L.E.D. LIGHTING LOADS ARE |
| | CALCULATED BY AMPS DRAWN, NOT WATTS. PER NEC 220.18.B |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN |
| | PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE |
| | 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A |
| | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |