Plan Review Details - Permit 20010698
Plan Review Stops For Permit 20010698
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-03-18 Cont ID  
Sent By jleahy Date 2020-03-18 Time 11:59 Rev Time 0.00
Received By jleahy Date 2020-03-17 Time 12:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-02-04 Cont ID  
Sent By fgiaquin Date 2020-02-04 Time 06:18 Rev Time 0.00
Received By fgiaquin Date 2020-02-04 Time 05:49 Sent To I
Notes
2020-02-04 06:04:39ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. FROM CUT SHEETS PROVIDED SEVERAL PRODUCTS ARE NOT UL
 OR OTHER NRTL (NATIONALLY RECOGNIZED TESTING
 LABORATORY) LISTED.
  
 UAP-AC-M-PRO NOT LISTED
  
 MXE-200 NOT LISTED
  
 NO LISTING'S PROVIDED FOR WIRELESS ACCESS POINTS (WAP).
  
 PROVIDE LISTINGS FOR ALL MATERIALS AND EQUIPMENT
 (INCLUDE LV CABLE) NEC 90.7, 110.2, 110.3B FBC 107.2.1
  
 2. DESIGNS OVER $125,000 MUST BE DESIGNED AND
 SIGNED/SEALED BY A DESIGN PROFESSIONAL (ENGINEER). F.S.
 471.003(2)(H)1
  
 3. PROVIDE LOAD CALCULATION, PANEL SCHEDULE, AND
 ANNOTATE ON PLAN THE CIRCUIT NUMBERS FOR NEW OR
 EXISITNG CIRCUITS USED TO POWER NEW PARKING GUIDANCE
 SYSTEM/ LIGHING/ AND RECEPTACLES. FBC 107.2.1 NEC 220
  
 INFORMATIONAL NOTE: L.E.D. LIGHTING LOADS ARE
 CALCULATED BY AMPS DRAWN, NOT WATTS. PER NEC 220.18.B
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 IF THE RESUBMITTAL IS NOT PREPARED BY A DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER), AND THE PAGES ARE
 11X17 OR SMALLER, YOU MAY RESUBMIT, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-03-18 Cont ID  
Sent By jleahy Date 2020-03-18 Time 11:59 Rev Time 0.00
Received By jleahy Date 2020-03-06 Time 14:19 Sent To  
Notes
2020-03-09 14:20:22RESUB ROUTED TO FGIAQUINTO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-02-04 Cont ID  
Sent By fgiaquin Date 2020-02-04 Time 06:18 Rev Time 0.00
Received By fgiaquin Date 2020-01-17 Time 16:40 Sent To E
Notes
***NONE***