Plan Review Details - Permit 20010565
Plan Review Stops For Permit 20010565
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-02-07 Cont ID  
Sent By jleahy Date 2020-02-07 Time 11:14 Rev Time 0.00
Received By jleahy Date 2020-02-07 Time 11:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-01-16 Cont ID  
Sent By jleahy Date 2020-01-16 Time 15:00 Rev Time 0.00
Received By jleahy Date 2020-01-16 Time 15:00 Sent To  
Notes
2020-01-16 15:03:33FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 IS THIS A NEW SERVICE OR A REAIR.
  
 IF THIS IS NEW WHERE IS THE SERVICE THAT WAS JUST
 INSTALLED IN REFERENCE TO THIS NEW SERVICE??
  
 WE DON'T GIVE ADDITIONAL SERVICES TO A PROPERTY UNLESS
 THEY CAN MEET ONE OF THE REQUIREMENTS FROM 230.2
  
 230.2 NUMBER OF SERVICES
 A BUILDING OR OTHER STRUCTURE SERVED SHALL BE SUPPLIED
 BY ONLY
 ONE SER VICE UNLESS PERMITTED IN 230.2(A) THROUGH (D).

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-01-16 Cont ID  
Sent By jleahy Date 2020-01-16 Time 15:04 Rev Time 0.00
Received By jleahy Date 2020-01-15 Time 10:55 Sent To  
Notes
2020-01-16 10:55:28ELEC <5K