Plan Review Details - Permit 20010521
Plan Review Stops For Permit 20010521
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2020-02-12 Cont ID  
Sent By cpuell Date 2020-02-12 Time 09:30 Rev Time 0.00
Received By cpuell Date 2020-02-12 Time 09:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-02-08 Cont ID  
Sent By shill Date 2020-02-08 Time 16:49 Rev Time 0.00
Received By pvalenti Date 2020-02-08 Time 16:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-01-21 Cont ID  
Sent By shill Date 2020-01-21 Time 15:40 Rev Time 0.00
Received By shill Date 2020-01-21 Time 11:54 Sent To  
Notes
2020-01-21 15:40:28****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FBC 107, THIS APPEARS TO BE LANDLORD WORK IN
 PREPARATION FOR A TENANT BUILDOUT BUT I WAS UNABLE TO
 LOCATE THIS INFORMATION IN THE PLANS OR IN THE
 CONTRACTOR'S APPLICATION. REVISE PLAN TO INCLUDE THIS
 INFORMATION. IF THIS IS NOT THE CASE, SEE PLUMBING
 COMMENTS; THE TWO SPACES DO NOT APPEAR TO COMPLY WITH
 FBC 2017.
  
 2. FBC 107, REVISE PLAN TO PROVIDE SUITE NUMBERS TO
 EACH UNIT. TITLE BLOCK INDICATES THAT THIS IS NO LONGER
 100, THE TWO SPACES ARE SUITES 169 AND 181, BUT IT IS
 NOT CLEAR WHICH IS 169. PLEASE REVISE, AT A MINIMUM,
 SHEETS AD1.1 AND ALS1.1.
  
 3. A SEPARATE PERMIT AND SEPARATE SUB PERMITS ARE
 REQUIRED FOR THE 2ND TENANT SPACE, PLEASE SUBMIT
 APPLICATION AND LET ME KNOW VIA EMAIL WHEN IT IS
 SUBMITTED. REVIEWS WILL BE EXPEDITED. ALL AFFECTED
 PERMITS FOR THIS PROJECT ALSO NEED TO HAVE THE SUITE
 NUMBER CHANGED IN OUR SYSTEM.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-02-10 Cont ID  
Sent By jpearson Date 2020-02-10 Time 09:06 Rev Time 0.00
Received By jpearson Date 2020-02-10 Time 09:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-01-24 Cont ID  
Sent By jpearson Date 2020-01-24 Time 10:53 Rev Time 0.00
Received By jpearson Date 2020-01-24 Time 10:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-02-10 Cont ID  
Sent By pleduc Date 2020-02-10 Time   Rev Time 0.00
Received By pleduc Date 2020-02-10 Time 10:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-01-17 Cont ID  
Sent By pleduc Date 2020-01-17 Time   Rev Time 0.00
Received By pleduc Date 2020-01-17 Time 09:39 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2020-01-17 Cont ID  
Sent By jesmith Date 2020-01-17 Time 15:20 Rev Time 0.00
Received By jesmith Date 2020-01-17 Time 15:14 Sent To  
Notes
2020-01-17 15:20:01GAS COMMENTS: APPROVED W/PROVISO
 RE:PLAN SHEET P1.1.2, PLUMBING KEYNOTE 9; EXISTING 2
 INCH GAS MAIN PIPE ENTRANCE TO REMAIN SHALL BE VALVED
 AND CAPPED.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-03-06 Cont ID  
Sent By lmarchan Date 2020-03-06 Time 10:15 Rev Time 0.00
Received By lmarchan Date 2020-02-28 Time 16:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-02-19 Cont ID  
Sent By shill Date 2020-02-19 Time 08:17 Rev Time 0.00
Received By shill Date 2020-02-07 Time 13:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-01-24 Time   Rev Time 0.00
Received By lmarchan Date 2020-01-15 Time 10:18 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date   Cont ID  
Sent By ccole Date 2020-01-21 Time   Rev Time 0.00
Received By ccole Date 2020-01-21 Time 11:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-02-19 Cont ID  
Sent By thunt Date 2020-02-19 Time 08:16 Rev Time 0.00
Received By shill Date 2020-02-17 Time 17:13 Sent To  
Notes
2020-02-19 08:16:52REVIEWED REMOTELY BY TIM HUNT

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-01-21 Cont ID  
Sent By gjohnson Date 2020-01-21 Time 15:49 Rev Time 0.00
Received By jesmith Date 2020-01-21 Time 15:46 Sent To  
Notes
2020-01-21 15:49:06 
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
  
 PLUMBING COMMENTS: DENIED
 1. PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC
 CHAPTERS 3 AND 6 PROVIDE DETAILS INDICATING THE
 FOLLOWING:
 A. THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18
 INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION PER FBC
 ACC 604.2
 B. CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND
 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL PER FBC ACC 604.3.1
 C. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE
 REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR
 WALL PER FBC ACC 604.5.1
 D. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2
 E. FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC.
 HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309.
 FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE
 WATER CLOSET PER FBC ACC 604.6
 F. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC
 ACC 604.8.
 G. LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE
 FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC
 ACC 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE AS
 REQUIRED BY FBC ACC 306.2 AND 306.3
 H. UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED PER FBC ACC 602.2
 I. PROVIDE CLEAR FLOOR SPACES FOR ACCESSIBLE LAVATORIES
 COMPLYING WITH FBC ACC 305.
 J. PROVIDE TURNING SPACE FOR ACCESSIBLE WATER CLOSETS
 COMPLYING WITH FBC ACC 304.
 2. PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC PL
 403.5, PROVIDE ACCESSIBLE ROUTE TO NEAREST DRINKING
 FOUNTAIN INDICATING THE DISTANCE FROM THE TENANT SPACE
 TO SAID DRINKING FOUNTAIN.
 3. PER FBC PL 607.1S, HOT WATER SHALL BE SUPPLIED FOR
 CULINARY PURPOSES, CLEANSING, LAUNDRY OR BUILDING
 MAINTENANCE PURPOSES. WITH REMOVAL OF EXISTING WATER
 HEATER, HOW IS HOT WATER TO BE SUPPLIED?
 4. PER WPB FBC 107.2.1, INDICATE ON THE PLANS WHICH
 TENANT SPACE IS UNIT 169 AND WHICH IS 181.
  
  
  
  
 20010521 477 S ROSEMARY AVE # 100
  
 MASTER PERMIT 19060241
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-02-08 Cont ID  
Sent By pvalenti Date 2020-02-08 Time 17:04 Rev Time 0.00
Received By pvalenti Date 2020-02-08 Time 17:04 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-01-21 Cont ID  
Sent By shill Date 2020-01-21 Time 12:24 Rev Time 0.00
Received By shill Date 2020-01-21 Time 12:18 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2020-03-06 Cont ID  
Sent By eschneid Date 2020-03-06 Time 09:09 Rev Time 0.50
Received By eschneid Date 2020-03-06 Time 08:14 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2020-02-18 Cont ID  
Sent By eschneid Date 2020-02-18 Time 09:22 Rev Time 0.50
Received By eschneid Date 2020-02-18 Time 09:22 Sent To  
Notes
2020-02-18 09:29:48FAILED
  
 PROVIDE WRITTEN RESPONSE TO COMMENTS.
  
 1) THE RESUBMITTAL INFORMATION STATES THAT THIS IS A
 REVISION TO PERMIT 19060241, WHICH IS THE NORTHERN HALF
 OF THE BUILDING, YET THE DEMOLITION PLAN, SHEET AD1.1,
 SHOWS WORK ONLY FOR THE SOUTH HALF OF THE BUILDING AND
 STATES "NO WORK" IN THE NORTH HALF OF THE BUILDING.
 SUBMIT THE CORRECT DEMOLITION PLAN WITH THIS PERMIT.
  
 2) THE PLANS SUBMITTED INCLUDE BOTH THE NORTH AND THE
 SOUTH HALF OF THE BUILDING (FLOOR PLANS, ELECTRICAL
 PLANS, MECHANICAL PLANS, ETC.) PROVIDE ONLY PLANS THAT
 COVER THE AREA OF WORK UNDER THIS PERMIT AND REMOVE THE
 PLANS THAT DO NOT APPLY.
  
 3) THE BUILDING COMMENTS RESPONSE LETTER STATES THAT
 THE ROLL-UP DOOR IS FOR TEMPORARY FUTURE TENANT USE
 PRIOR TO OCCUPANCY. SINCE NO WORK IS TO OCCUR TO
 PREPARE THE SOUTHERN PORTION OF THE BUILDING FOR
 OCCUPANCY UNLESS THE WEST (ROSEMARY) ELEVATION IS
 BROUGHT INTO CONFORMANCE WITH THE MINIMUM GLAZING
 REQUIREMENTS, THE ROLL UP DOOR NEEDS TO BE SHOWN ON THE
 BAY BUILD-OUT PERMIT, NOT ON A PERMIT THAT DOES NOT
 CONTAIN THE FULL SCOPE OF WORK. THE REVISION TO PUT IN
 A LOADING DOOR OPENING IS MORE THAN WHAT IS REQUIRED TO
 MAINTAIN LIFE SAFETY REQUIREMENTS.
  
 4) ADDITIONALLY, WHAT IS THE TEMPORARY FUTURE TENANT
 USE PRIOR TO OCCUPANCY? THE TYPE OF USE MAY NOT BE
 PERMITTED BY THE ROSEMARY SQUARE USE ALLOWANCE, SUCH AS
 THE USE OF THE SPACE TO STORE BUILDING MATERIALS FOR
 THE 575 CONSTRUCTION, OR WOULD REQUIRE UPGRADES SUCH AS
 THE USE OF THE SPACE AS CONSTRUCTION OFFICES FOR THE
 575 CONSTRUCTION.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2020-01-22 Cont ID  
Sent By eschneid Date 2020-01-22 Time 17:31 Rev Time 0.50
Received By eschneid Date 2020-01-22 Time 17:31 Sent To  
Notes
2020-01-22 17:31:51FAILED
  
 PROVIDE WRITTEN RESPONSE TO COMMENTS.
  
 1) WHAT IS THE PURPOSE OF THE PROPOSED ROLL-UP DOOR?
 THE AREA IS CONSTRAINED TO USE AS LOADING BY THE
 EXISTING FPL TRANSFORMERS, THE LACK OF CURBING AND THE
 PROPOSED DEVELOPMENT, INCLUDING THE LANDSCAPING, FOR
 THE 575 SOUTH ROSEMARY (OLD MACY'S) SITE.
  
 2) NO WORK IS TO OCCUR TO PREPARE THE SOUTHERN PORTION
 OF THE BUILDING FOR OCCUPANCY UNLESS THE WEST
 (ROSEMARY) ELEVATION IS BROUGHT INTO CONFORMANCE WITH
 THE MINIMUM GLAZING REQUIREMENTS. THE REVISION TO PUT
 IN A LOADING DOOR OPENING IS MORE THAN WHAT IS REQUIRED
 TO MAINTAIN LIFE SAFETY REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]