Plan Review Details - Permit 20010288
Plan Review Stops For Permit 20010288
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2020-06-21 Cont ID  
Sent By jwitmer Date 2020-06-21 Time 12:40 Rev Time 0.00
Received By jwitmer Date 2020-06-21 Time 12:40 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-03-16 Cont ID  
Sent By jwitmer Date 2020-03-16 Time 10:46 Rev Time 0.00
Received By jwitmer Date 2020-03-16 Time 10:44 Sent To  
Notes
2020-03-16 10:45:08ASBESTOS COMMERCIAL. PLEASE PROVIDE A SIGNED
 ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD,
 STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF
 ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF
 HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT
 NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL
 INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE
 FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-02-04 Cont ID  
Sent By jwitmer Date 2020-02-04 Time 06:26 Rev Time  
Received By jwitmer Date 2020-02-04 Time   Sent To  
Notes
2020-02-04 06:26:23ASBESTOS COMMERCIAL. PLEASE PROVIDE A SIGNED
 ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON LETTERHEAD,
 STATING THAT THE INSTRUCTIONS ON THE WEBSITE OF
 ASBESTOS PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF
 HEALTH PALM BEACH COUNTY WILL BE FOLLOWED AND THAT
 NOTIFICATION WILL BE GIVEN TIMELY. ADDITIONAL
 INFORMATION REGARDING ASBESTOS REQUIREMENTS CAN BE
 FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-06-21 Cont ID  
Sent By jwitmer Date 2020-06-21 Time 12:54 Rev Time 0.00
Received By jwitmer Date 2020-06-21 Time 12:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-03-16 Cont ID  
Sent By jwitmer Date 2020-03-16 Time 10:59 Rev Time 0.00
Received By jwitmer Date 2020-03-16 Time 10:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-02-04 Cont ID  
Sent By jwitmer Date 2020-02-04 Time 06:25 Rev Time 0.00
Received By jwitmer Date 2020-02-03 Time 14:08 Sent To  
Notes
2020-02-04 06:25:242017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20010288
 ADD: 901 45TH ST. ST. MARY?S MEDICAL CENTER
 CONT: TBD/ TO BE DETERMINED
 TEL: ???????????????
 E-MAIL: [email protected] CONTACT: JENNIFER
 PINSKY
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. FEB. 03/2020
 ACTION: DENIED
  
 1) THE PERMIT VALUE IS EXTREMELY LOW THE COST OF THE
 PLANS WOULD BE MORE THAN STATED ON THE PERMIT
 APPLICATION!!!
 108.3* BUILDING PERMIT VALUATION. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE UNDER
 ESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL,
 PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD
 AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION
 REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
  
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
  
 2) THE TITLE SHEET LIST THE OCCUPANCY TYPE AS AN
 MERCANTILE OCCUPANCY. IN MOST CASES I WOULD BELIEVE YOU
 WERE RIGHT. IN THIS CASE THIS PHARMACY IS PROVIDING
 MORE OF A SERVICE SUCH AS A PRINT SHOP OR POST OFFICE
 WHICH ARE CONSIDERED A BUSINESS OCCUPANCY. SEE 2017
 FBC-B 304.1 FOR BUSINESS OCCUPANCIES.
  
 3) THERE IS AN EGRESS PLAN ON G-004 BUT NEITHER G-004
 OR SHEET A-111 PROVIDE THE COMMON PATH OF TRAVEL FROM
 THE MOST REMOTE POINT IN THE TENANT SPACE AND
 COMPLIANCE WITH SECTION/ TABLE 1006.2.1 OF THE 2017
 FBC-B.
  
 4) SHEET A-111 THE CONSULT ROOM IT APPEARS THERE ARE 2
 WALLS THAT BACK UP AGAINST ONE ANOTHER, THE SAME WALL
 TYPE IS ON THE FRONT OF THE CONSULT ROOM. ARE THESE
 WALLS GLASS WALLS OR COULD THEY BE CUBICLE HEIGHT
 WALLS? THERE ARE NO WALL TAGS IDENTIFYING THESE WALLS?
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 5) SHEET A-111 JUST TOP OF THE PHARMACY OFFICE THERE
 APPEARS TO BE A SHAFT ENCLOSURE THE WALL TYPE IS NOT
 GIVEN. ON SHEET G-004 THIS SAME AREA IS SHOWN WITH A
 BLACK HEAVY LINE THAT IN THE LIFE SAFETY LEGEND COULD
 BE A 1 HOUR RATED WALL TO 4HR. FIRE/ SMOKE COMPARTMENT
 WALL? PLEASE IDENTIFY THE HOUR RATING ON THIS SHAFT/
 CHASE? 2017 FBC-B SECTION 703.2 FIRE RESISTANCE
 RATINGS. THE FIRE RESISTANCE RATING OF BUILDING
 ELEMENTS, COMPONENTS OR ASSEMBLIES SHALL BE DETERMINED.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-03-18 Cont ID  
Sent By jleahy Date 2020-03-18 Time 16:43 Rev Time 0.00
Received By jleahy Date 2020-03-18 Time 16:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-01-29 Cont ID  
Sent By jleahy Date 2020-01-29 Time 14:37 Rev Time 0.00
Received By jleahy Date 2020-01-29 Time 14:33 Sent To  
Notes
2020-01-29 14:38:32FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) VALUE FOR WORK SHOWN TOO LOW, PLEASE SUBMIT SIGNED
 CONTRACT WORK.
  
 2) SEPARATE PERMIT REQUIRED FOR LOW VOLTAGE WORK.
  
 3) SEPARATE PERMIT REQUIRED FOR FIRE ALARM

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-03-12 Cont ID  
Sent By pleduc Date 2020-03-12 Time   Rev Time 0.00
Received By pleduc Date 2020-03-12 Time 16:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2020-01-21 Cont ID  
Sent By pleduc Date 2020-01-21 Time   Rev Time 0.00
Received By pleduc Date 2020-01-21 Time 16:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2020-06-21 Time 12:54 Rev Time 0.00
Received By lmarchan Date 2020-06-16 Time 10:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-03-24 Cont ID  
Sent By shill Date 2020-03-24 Time 14:09 Rev Time 0.00
Received By shill Date 2020-03-11 Time 11:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-02-04 Time   Rev Time 0.00
Received By lmarchan Date 2020-01-15 Time 10:55 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2020-02-04 Cont ID  
Sent By jwitmer Date 2020-02-04 Time 06:26 Rev Time  
Received By jwitmer Date 2020-02-04 Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-03-24 Cont ID  
Sent By ccole Date 2020-03-24 Time 13:02 Rev Time 0.00
Received By ccole Date 2020-03-24 Time 12:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-02-03 Cont ID  
Sent By ccole Date 2020-02-03 Time 15:24 Rev Time 0.00
Received By ccole Date 2020-02-03 Time 15:24 Sent To  
Notes
2020-02-03 15:34:301ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20010288
 2/3/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M100: PROVIDE SUPPLY CFMS AT EACH DIFFUSER
 LOCATION- SECTION 603 FBC M.
  
 2) M100: REFER TO TABLE 7-1 ASHRAE 170-2013 AN PROVIDE
 THE OUTDOOR AIR CHANGES, AND THE TOTAL AIR CHANGES FOR
 THE NEW PHARMACY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK ?VOID? OR "OLD" ON THEM. PLEASE
 RETAIN THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS.
 THIS PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-03-24 Cont ID  
Sent By jesmith Date 2020-03-24 Time 14:07 Rev Time 0.00
Received By shill Date 2020-03-24 Time 10:30 Sent To  
Notes
2020-03-24 14:07:5220010288 901 45TH ST
  
 1ST REVIEW
 PLUMBING COMMENTS: APPROVED W/PROVISO
 1. PER FBC ACC 212.3, WHERE SINKS ARE PROVIDED, AT
 LEAST 5 PERCENT, BUT NO FEWER THAN ONE, OF EACH TYPE
 PROVIDED IN EACH ACCESSIBLE ROOM OR SPACE AND SHALL
 COMPLY WITH FBC ACC 606 WHICH REQUIRES ACCESSIBLE SINKS
 TO HAVE A CLEAR FLOOR SPACE COMPLYING WITH 305,
 POSITIONED FOR A FORWARD APPROACH, AND KNEE AND TOE
 CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED (606.2)
 AS WELL AS SAID SINK SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND
 (606.3). PER WPB FBC 107.2.1, PROVIDE PLAN REVISION
 PROVIDING FOR THE SAME OR PROVIDE AN AFFIDAVIT STATING
 THAT A STAFF MEMBER WHO WOULD USE THE FACILITY IS
 DISABLED THAT THE FACILITY WILL MAKE THE REQUIRED
 CHANGES TO ACCOMMODATE SAID STAFF MEMBER. SAID
 AFFIDAVIT SHALL BE SUBMITTED AND IN PLACE PRIOR TO
 FIRST INSPECTION. A PLAN REVISION IF REQUIRED, SHALL BE
 IN PLACE PRIOR TO FINAL INSPECTION.
 2. REGARDING RO SYSTEM BY OWNER:
 1) A SEPARATE PERMIT IS REQUIRED.
 2) PER FBC PL 608.3, PROVIDE A BACKFLOW PREVENTOR13.1
 AT THE COLD WATER SUPPLY FOR THE RO SYSTEM.
 3) PROVIDE A TRAPPED AND VENTED DRAIN WITH OPEN
 RECEPTACLE FOR THE RO DRAIN. RO DRAIN AND BACKFLOW
 PREVENTOR VENT DRAIN SHALL DISCHARGE INTO THE OPEN
 RECEPTACLE THROUGH AN AIR GAP IN ACCORDANCE WITH FBC PL
 608.13.1.
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 20010288 901 45TH ST
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-01-29 Cont ID  
Sent By gjohnson Date 2020-01-29 Time 11:41 Rev Time 0.00
Received By gjohnson Date 2020-01-28 Time 17:26 Sent To  
Notes
2020-01-29 11:41:401ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1.PROVIDE A PLUMBING FLOOR PLAN AND ISOMETRIC WATER AND
 SANITARY THE SHEET LABEL P200 HAS SHEET E100 UPLOADED
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-03-24 Cont ID  
Sent By shill Date 2020-03-24 Time 10:33 Rev Time 0.00
Received By shill Date 2020-03-24 Time 10:32 Sent To  
Notes
2020-03-16 11:00:36ARCHRITECURAL SHEETS CHECKED FOR SIGNATURE 2ND REVIEW.
 3/16/2020 OK. JW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-02-10 Cont ID  
Sent By shill Date 2020-02-10 Time 08:17 Rev Time 0.00
Received By shill Date 2020-02-10 Time 08:16 Sent To  
Notes
2020-02-04 06:31:08ARCHITECTURAL SHEETS CHECKED FOR ELECTRONIC SIGNATURES.
 02/04.2020, OK. JW