| 2020-01-09 09:11:02 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS |
| | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| | |
| | 1- BORAL ROOF TILE NOA 18-0509.16 SUBMITTED DOESN'T |
| | LIST THE 3M FOAM NOA 15-1201.04 SUBMITTED. THERE IS NO |
| | WAY TO FIND THE UPLIFT RESISTANCE OF THE FOAM ADHESIVE |
| | SUBMITTED BECAUSE NEITHER THE ROOF TILE NOA NOR THE |
| | FOAM ADHESIVE NOA SUBMITTED SHOW THE UPLIFT RESISTANCE. |
| | . NEED THIS TO TO VERIFY COMPLIANCE WITH THE DESIGN |
| | PRESSURES OF SEC. R301.2.1 FBC-RESIDENTIAL. |
| | PROVIDE A ROOF TILE ADHESIVE PRODUCT APPROVAL THAT IS |
| | LISTED ON THE ROOF TILE PRODUCT APPROVAL SUBMITTED OR |
| | PROVIDE COMPLETE INFORMATION FROM 3M ADHESIVE |
| | MANUFACTURER FOR BUILDING OFFICIAL APPROVAL. |
| | SEC. 107.2.1 CITY AMENDMENTS AND FAC 61G20.3001. |
| | |
| | 2- ROOF TILE NOA AND ROOF TILE ADHESIVE NOA SUBMITTED: |
| | CLEARLY MARK ADHESIVE PADDY SIZE AS REQUIRED BY CITY |
| | POLICY FOR ALL ROOFING PERMITS TO VERIFY COMPLIANCE |
| | WITH THE DESIGN PRESSURES OF SEC R301.2.1 |
| | FBC-RESIDENTIAL. |
| | |
| | 3- POLYGLASS UNDERPAYMENT NOA 17-0614.22 SUBMITTED. |
| | CLEARLY SPECIFY WHICH OF THE UNDERLAYMENTS LISTED IN |
| | THE NOA IS GOING TO BE USED AS REQUIRED BY CITY POLICY |
| | FOR ALL ROOFING PERMITS TO VERIFY THAT PROPOSED |
| | UNDERLAYMENT IS OK TO BE USED ON FOAM ADHESIVE |
| | INSTALLATIONS. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | IN ORDER TO AVOID MULTIPLE SUBMITTALS, PLEASE FEEL FREE |
| | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| | COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |