| 2020-01-15 14:13:29 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THERE IS NO INDICATIONS OF COMPLAINCE WITH THE |
| | FLORIDA FIRE PREVENTION CODE, NFPA 101, CH MEANS OF |
| | EGRESS |
| | |
| | PER NFPA 101, CH 7 AS APPLICABLE |
| | |
| | 7.2.1.5.6 ELECTRICALLY CONTROLLED EGRESS DOOR |
| | ASSEMBLIES. DOOR ASSEMBLIES IN THE MEANS OF EGRESS |
| | SHALL BE PERMITTED TO BE ELECTRICALLY LOCKED IF |
| | EQUIPPED WITH APPROVED, LISTED HARDWARE, PROVIDED THAT |
| | ALL OF THE FOLLOWING CONDITIONS ARE MET: |
| | (1) THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS |
| | AFFIXED TO THE DOOR LEAF. |
| | (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION |
| | THAT IS READILY OPERATED IN THE DIRECTION OF EGRESS. |
| | (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE |
| | HAND IN THE DIRECTION OF EGRESS. |
| | (4) OPERATION OF THE HARDWARE INTERRUPTS THE POWER |
| | SUPPLY DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE |
| | DOOR ASSEMBLY IN THE DIRECTION OF EGRESS. |
| | (5)* LOSS OF POWER TO THE LISTED RELEASING HARDWARE |
| | AUTOMATICALLY UNLOCKS THE DOOR ASSEMBLY IN THE |
| | DIRECTION OF EGRESS. |
| | (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN |
| | ACCORDANCE WITH ANSI/UL 294, STANDARD FOR ACCESS |
| | CONTROL SYSTEM UNITS. |
| | |
| | 7.2.1.6.2* ACCESS-CONTROLLED EGRESS DOOR ASSEMBLIES. |
| | WHERE PERMITTED IN CHAPTERS 11 THROUGH 43, DOOR |
| | ASSEMBLIES IN THE MEANS OF EGRESS SHALL BE PERMITTED TO |
| | BE EQUIPPED WITH ELECTRICAL LOCK HARDWARE THAT PREVENTS |
| | EGRESS, PROVIDED THAT ALL OF THE FOLLOWING CRITERIA ARE |
| | MET: |
| | (1) A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE, |
| | ARRANGED TO UNLOCK THE DOOR LEAF IN THE DIRECTION OF |
| | EGRESS UPON DETECTION OF AN APPROACHING OCCUPANT. |
| | (2) DOOR LEAVES SHALL AUTOMATICALLY UNLOCK IN THE |
| | DIRECTION OF EGRESS UPON LOSS OF POWER TO THE SENSOR OR |
| | TO THE PART OF THE ACCESS CONTROL SYSTEM THAT LOCKS THE |
| | DOOR LEAVES. |
| | (3) DOOR LOCKS SHALL BE ARRANGED TO UNLOCK IN THE |
| | DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE |
| | COMPLYING WITH ALL OF THE FOLLOWING CRITERIA: |
| | (A) THE MANUAL RELEASE DEVICE SHALL BE LOCATED ON THE |
| | EGRESS SIDE, 40 IN. TO 48 IN. (1015 MM TO 1220 MM ) |
| | VERTICALLY ABOVE THE FLOOR, AND WITHIN 60 IN. (1525 MM) |
| | OF THE SECURED DOOR OPENINGS. |
| | (B) THE MANUAL RELEASE DEVICE SHALL BE READILY |
| | ACCESSIBLE AND CLEARLY IDENTIFIED BY A SIGN THAT READS |
| | AS FOLLOWS: PUSH TO EXIT. |
| | (C) WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL |
| | RESULT IN DIRECT INTERRUPTION OF POWER TO THE LOCK |
| | INDEPENDENT OF THE LOCKING SYSTEM ELECTRONICS .AND THE |
| | LOCK SHALL REMAIN UNLOCKED FOR NOT LESS THAN 30 |
| | SECONDS. |
| | (4) ACTIVATION OF THE BUILDING FIRE-PROTECTIVE |
| | SIGNALING SYSTEM, IF PROVIDED, SHALL AUTOMATICALLY |
| | UNLOCK THE DOOR LEAVES IN THE DIRECTION OF EGRESS, AND |
| | THE DOOR LEAVES SHALL REMAIN UNLOCKED UNTIL THE |
| | FIRE-PROTECTIVE SIGNALING SYSTEM HAS BEEN MANUALLY |
| | RESET. |
| | (5) THE ACTIVATION OF MANUAL FIRE ALARM BOXES THAT |
| | ACTIVATE THE BUILDING FIRE-PROTECTIVE SIGNALING SYSTEM |
| | SPECIFIED IN 7.2.1.6.2 (4) SHALL NOT BE REQUIRED TO |
| | UNLOCK THE DOOR LEAVES. |
| | (6) ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER OR |
| | FIRE DETECTION SYSTEM, IF PROVIDED, SHALL AUTOMATICALLY |
| | UNLOCK THE DOOR LEAVES IN THE DIRECTION OF EGRESS, AND |
| | THE DOOR LEAVES SHALL REMAIN UNLOCKED UNTIL THE |
| | FIRE-PROTECTIVE SIGNALING SYSTEM HAS BEEN MANUALLY |
| | RESET. |
| | (7) THE EGRESS SIDE OF ACCESS-CONTROLLED EGRESS DOORS, |
| | OTHER THAN EXISTING ACCESS-CONTROLLED EGRESS DOORS, |
| | SHALL BE PROVIDED WITH EMERGENCY LIGHTING IN ACCORDANCE |
| | WITH SECTION 7.9. |
| | |
| | PLEASE REVIEW AND ENSURE COMPLIANCE, PROVIDE AN |
| | APPLICABLE NOTE OF ACKNOWLEDGEMENT. |
| | |
| | |
| | |
| | 2) THE PLAN SHEETS INDICATING A FLOOR PLAN, THE FLOOR |
| | PLAN LINES ARE TOO LIGHT AND UNREADABLE. |
| | |
| | PLEASE REIVEW AND CORRECT. |
| | |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |