Plan Review Details - Permit 20010166
Plan Review Stops For Permit 20010166
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 4 Status P Date 2021-02-17 Cont ID  
Sent By rmcdouga Date 2021-02-17 Time 13:48 Rev Time 0.00
Received By rmcdouga Date 2021-02-17 Time 13:48 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status F Date 2021-02-08 Cont ID  
Sent By rmcdouga Date 2021-02-08 Time 11:35 Rev Time 0.00
Received By rmcdouga Date 2021-02-08 Time 11:35 Sent To  
Notes
2021-02-08 11:36:33FAILED PLAN REVIEW, COMMERCIAL:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE ADDRESS, PERMIT NUMBER AND "ASBESTOS" IN
 THE SUBJECT LINE.
  
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2020-09-22 Cont ID  
Sent By rmcdouga Date 2020-09-22 Time 10:12 Rev Time 0.00
Received By rmcdouga Date 2020-09-22 Time 10:12 Sent To  
Notes
2020-09-22 10:15:59FAILED PLAN REVIEW, COMMERCIAL:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE ADDRESS, PERMIT NUMBER AND ?ASBESTOS? IN
 THE SUBJECT LINE.
  
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-01-31 Cont ID  
Sent By rmcdouga Date 2020-01-31 Time 07:49 Rev Time 0.00
Received By rmcdouga Date 2020-01-30 Time 19:09 Sent To  
Notes
2020-01-31 07:49:31ASBESTOS NOTIFICATION REQUIREMENTS, PROVIDE A SIGNED
 ACKNOWLEDGMENT FROM THE CONTRACTOR STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF THE ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. IF THIS PROJECT IS NOT SUBJECT TO
 ASBESTOS NOTIFICATION REQUIREMENTS, THE CONTRACTOR IS
 TO PROVIDE A SIGNED STATEMENT ON LETTERHEAD EXPLAINING
 WHY IT IS EXEMPT (FOR EXAMPLE, "THIS PROJECT IS EXEMPT
 BECAUSE IT IS A SINGLE FAMILY RESIDENCE AND IS NOT A
 PART OF A COMMERCIAL OR PUBLIC PROJECT, AND IS NOT A
 CITY-INITIATED DEMOLITION").
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-02-08 Cont ID  
Sent By rmcdouga Date 2021-02-08 Time 10:14 Rev Time 0.00
Received By rmcdouga Date 2021-02-08 Time 10:14 Sent To  
Notes
2021-02-08 10:14:28PLAN
 REVIEW COMMENTS
 3RD REVIEW: FBC SIXTH EDITION (2017) EXISTING BUILDING
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NOTE #9 ON SHEET A-1, STATES THAT THE SPACE HAS AN
 EXISTING APPROVED AUTOMATIC SPRINKLER SYSTEM IN PLACE
 TO REMAIN AND THE BUILDING CONSTRUCTION TYPE STATES
 THAT IT IS A TYPE 2A UNSPRINKLERED BUILDING. PLEASE
 CLARIFY. FBC AMEND. 107.2.1
  
 2) THE TRAVEL DISTANCE IN THE BREAKROOM SHOULD BE FROM
 THE HAND SINK TO THE EXIT. THIS APPEARS TO BE THE MOST
 REMOTE POINT IN THE ROOM FROM THE EXIT. FBC 1017.3
  
 3) FBC ACCESSIBILITY SECTION 404.2.4 REQUIRES 18" CLEAR
 ON THE LATCH SIDE OF A DOOR ON THE PULL SIDE. PLEASE
 SHOW THAT THE NEW 2830 DOOR IN THE BREAKROOM COMPLIES.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-09-22 Cont ID  
Sent By rmcdouga Date 2020-09-22 Time 10:17 Rev Time 0.00
Received By rmcdouga Date 2020-09-22 Time 10:17 Sent To  
Notes
2020-09-22 09:55:32PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017) EXISTING BUILDING
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) COMPLIED. FBC 107.2.1 ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
  
 2) COMPLIED. PROVIDE (2) SETS OF A COMPLETE FLOOR PLAN
 OF THE BUILDING AND SHOW THE LOCATION OF THE PROPOSED
 WORK. FBC 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED
 AND DRAWN UPON SUITABLE MATERIAL. ELECTRONIC MEDIA
 DOCUMENTS SHALL BE SUBMITTED WHEN APPROVED BY THE
 BUILDING OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 3) COMPLIED. PROVIDE (2) SETS OF A FLOOR PLAN THAT
 SHOWS THE EXISTING CABINET CONFIGURATION. FBC 107.2.1
  
 4) SECOND REQUEST. SPECIFY THE BUILDING OCCUPANCY GROUP
 AND USE ON THE PLANS. FBC 107.3.5 AND 302.1
  
 5) SECOND REQUEST. SPECIFY THE BUILDING'S CONSTRUCTION
 TYPE AND IF IT IS SPRINKLERED. FBC 107.3.5 AND 503
  
 6) SECOND REQUEST. THE CITY DOES NOT HAVE ANY RECORDS
 THAT SHOW AN EXISTING RANGE OR HOOD. THEREFORE, THE
 RANGE AND HOOD WILL BE REVIEWED AS NEW INSTALLATIONS.
 INDICATE THE INTENDED USED OF THE COOKING EQUIPMENT. IS
 IT TO BE USED TO PREPARE MEALS FOR THE STUDENTS AND/OR
 FACULTY, IF SO HOW MANY PEOPLE? PROVIDE THE
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 REQUIREMENTS. FBC 107.2.1.2
  
 7) SECOND REQUEST. A THOROUGH AND COMPLETE PLAN REVIEW
 CANNOT BE COMPLETED AT THIS TIME DUE TO LACK OF
 INFORMATION ON THE SUBMITTED PLANS. ADDITIONAL PLAN
 REVIEW COMMENTS MAY BE GENERATED WHEN MORE INFORMATION
 IS PROVIDED.
  
 8) SECOND REQUEST. WHEN RESUBMITTING, IT IS HELPFUL TO
 PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG
 WITH THE CITY RE-SUBMITTAL FORM.
  
 NEW COMMENTS.
  
 9) PLAN SHEET A-1 AND E-1 HAVE A DIFFERENT FLOOR PLAN
 CONFIGURATION AT THE PROPOSED BREAKROOM AREA. PLEASE
 COORDINATE. FBC 107.2.1
  
 10) THE PROPOSED PLANS INDICATE THAT WALLS ARE BEING
 ADDED AND SPACES RECONFIGURED WHICH MAKES THIS IS A
 LEVEL 2 ALTERATION TO AN EXISTING BUILDING. PLEASE NOTE
 THIS ON THE PLANS. FBC EXISTING BUILDING SECTION 501
  
 11) SUBMIT A LIFE SAFETY AND EXITING PLAN.
 THE LIFE SAFETY PLAN NEEDS TO SHOW THE FOLLOWING:
 A) NUMBER OF OCCUPANTS IN EACH AREA FBC 1004.1
 B) CUMULATIVE OCCUPANT LOADS FBC 1004.1.1
 C) EXIT SEPARATION DISTANCE FBC 1015.2.1
 D) COMMON PATH OF EGRESS TRAVEL DISTANCE FBC 1014.3
 E) EXIT ACCESS TRAVEL DISTANCE FBC 1016.3
 F) CLEAR WIDTH OF THE EXIT OR EXIT ACCESS DOORS FBC
 1008.1.1
 G) CAPACITY OF EGRESS DOORS, OCCUPANT LOAD SERVED AND
 MEANS OF EGRESS FACTOR FBC1005.3.2
 H) DISTRIBUTION OF EGRESS CAPACITY FBC1005.5
  
 12) PROVIDE ELEVATIONS OF THE NEW CABINETS IN THE BREAK
 ROOM. DEPENDING ON THE USE OF THE PROPOSED KITCHEN,
 THERE ARE ACCESSIBILITY REQUIREMENTS THAT WILL NEED TO
 BE ADDRESSED. FBC ACCESSIBILITY
  
 13) ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO
 HAVE THE ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO
 HAVE THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS
 REQUIRED TO BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER
 FACSIMILES OF THE SIGNATURE ARE ACCEPTABLE. FS 471 &
 61G15
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-01-31 Cont ID  
Sent By rmcdouga Date 2020-01-31 Time 09:30 Rev Time 0.00
Received By rmcdouga Date 2020-01-30 Time 19:09 Sent To  
Notes
2020-01-31 08:02:32PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017) EXISTING BUILDING
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.2.1 ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
  
 2) PROVIDE (2) SETS OF A COMPLETE FLOOR PLAN OF THE
 BUILDING AND SHOW THE LOCATION OF THE PROPOSED WORK.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 3) PROVIDE (2) SETS OF A FLOOR PLAN THAT SHOWS THE
 EXISTING CABINET CONFIGURATION. FBC 107.2.1
  
 4) SPECIFY THE BUILDING OCCUPANCY GROUP AND USE ON THE
 PLANS. FBC 107.3.5 AND 302.1
  
 5) SPECIFY THE BUILDING'S CONSTRUCTION TYPE AND IF IT
 IS SPRINKLERED. FBC 107.3.5 AND 503
  
 6) THE CITY DOES NOT HAVE ANY RECORDS THAT SHOW AN
 EXISTING RANGE OR HOOD. THEREFORE, THE RANGE AND HOOD
 WILL BE REVIEWED AS NEW INSTALLATIONS. INDICATE THE
 INTENDED USED OF THE COOKING EQUIPMENT. IS IT TO BE
 USED TO PREPARE MEALS FOR THE STUDENTS AND/OR FACULTY,
 IF SO HOW MANY PEOPLE? PROVIDE THE MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION REQUIREMENTS. FBC
 107.2.1.2
  
 7) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE
 COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION ON
 THE SUBMITTED PLANS. ADDITIONAL PLAN REVIEW COMMENTS
 MAY BE GENERATED WHEN MORE INFORMATION IS PROVIDED.
  
 8) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
 9) RE-SUBMITTAL PROCEDURE YOU ARE REQUIRED TO FILL OUT
 A RE-SUBMITTAL FORM TO BE SUBMITTED WITH THE CORRECTED
 PLANS AND/OR OTHER DOCUMENTS. THE PERMIT CLERK WILL
 RETRIEVE THE DENIED APPLICATION, PLANS AND OTHER
 DOCUMENTS FOR YOU. YOU ARE REQUIRED TO REMOVE THE OLD
 PLAN SHEETS THAT HAVE BEEN CORRECTED AND REPLACE THEM
 WITH THE NEW ONES. THE CLERK WILL PROVIDE YOU WITH A
 STAPLE REMOVER AND A STAPLER. ONE SET OF THE OLD PLAN
 SHEETS THAT HAVE BEEN REMOVED SHALL BE MARKED AS VOIDED
 AND RESUBMITTED ALONG WITH THE TWO (OR MORE) SETS THAT
 CONTAIN THE CORRECTED SHEETS. IF THERE ARE ANY SHEETS
 THAT HAVE BEEN STAMPED FOR COUNTY IMPACT FEES, HOA
 APPROVAL STAMPS OR OTHERS, RESUBMIT THOSE SHEETS.
 IF ALL OF THE PLAN SHEETS HAVE BEEN CORRECTED, THEN TWO
 (OR MORE) SETS OF THE NEW PLANS AND ANY OTHER DOCUMENTS
 SHALL BE SUBMITTED.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-01-29 Cont ID  
Sent By jleahy Date 2021-01-29 Time 09:54 Rev Time 0.00
Received By jleahy Date 2021-01-29 Time 09:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-09-22 Cont ID  
Sent By jleahy Date 2020-09-22 Time 10:41 Rev Time 0.00
Received By jleahy Date 2020-09-22 Time 10:37 Sent To  
Notes
2020-09-22 10:45:25ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
  
 KITCHEN RECEPTACLES. 125-VOLT, SINGLE-PHASE, 15- AND
 20-AMPERE RECEPTACLES SHALL HAVE GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL. INCLUDING
 REFIGERATOR, RANGE HOOD ECT. ECT. 210.8(B) (2)

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-01-31 Cont ID  
Sent By jpearson Date 2020-01-31 Time 14:54 Rev Time 0.00
Received By jpearson Date 2020-01-31 Time 14:20 Sent To I
Notes
2020-01-31 14:24:31CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM OF EXISTING SERVICE. NEC
 215.5; WPB FBC 107.2.1
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5
 3. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30
 4. SEVERAL ITEMS ON PLAN ARE ILLEGIBLE. PROVIDE LEGIBLE
 PLAN FOR REVIEW, SIGNED AND SEALED BY A DESIGN
 PROFESSIONAL, OR SIGNED BY THE ELECTRICAL CONTRACTOR
 QUALIFIER. FS 471.003(2)(H); 471.025; WPB FBC 107.2.1,
 107.3.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-09-22 Cont ID  
Sent By pleduc Date 2020-09-22 Time   Rev Time 0.00
Received By pleduc Date 2020-09-22 Time 09:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-01-09 Cont ID  
Sent By pleduc Date 2020-01-09 Time   Rev Time 0.00
Received By pleduc Date 2020-01-09 Time 14:28 Sent To  
Notes
2020-01-09 14:36:06THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS RANGE AND HOOD INDICATED.
  
 IS THIS A NEW RANGE AND NEW HOOD AS THERE IS NO
 PREVIOUS RECORD OF THIS INSTALLATION?
  
 PLEASE PROVIDE DETAILS
  
  
  
 2) COOKING SHALL COMPLY WITH THE REQUIRMENTS OF NFPA
 101, CH 15 EXISTING EDUCATIONAL OCCUPANCIES.
  
 15.3.2.2 COOKING FACILITIES SHALL BE PROTECTED IN
 ACCORDANCE WITH
 9.2.3. OPENINGS SHALL NOT BE REQUIRED TO BE PROTECTED
 BETWEEN
 FOOD PREPARATION AREAS AND DINING AREAS.
  
 9.2.3 COMMERCIAL COOKING OPERATIONS. WHERE REQUIRED BY
 ANOTHER
 SECTION OF THIS CODE, COMMERCIAL COOKING OPERATIONS
 SHALL BE PROTECTED
 IN ACCORDANCE WITH NFPA 96, STANDARD FOR VENTILATION
 CONTROL AND
 FIRE PROTECTION OF COMMERCIAL COOKING OPERATIONS,
 UNLESS SUCH
 INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS,
 WHICH SHALL BE
 PERMITTED TO BE CONTINUED IN SERVICE.
  
 A RESIDENTIAL HOOD DOES NOT COMPLY WITH THE ABOVE.
  
 PLEASE PROVIDE DETAILS AND A NOTE OF ACKNOWLEDGEMENT TO
 COMPLY BY PROVIDING FOR A NFPA 96 COMPLIANT HOOD AND
 SUPPROESSION SYSTEM
  
  
  
  
 3) DOES THE OCCUPANCIES HAVE FIRE SPRINKLER PROTECTION?
  
 PLEASE PROVIDE AND APPLICABLE NOTE, IF SO THE FIRE
 SPRINKLER MAY REQUIRE MODIFICATION FOR CODE COMPLIANT
 COVERAGE.
  
 ALL FIRE SPRINKLER WORK SHALL BE SUBMITTED UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-02-08 Cont ID  
Sent By rmcdouga Date 2021-02-08 Time 10:16 Rev Time 0.00
Received By rmcdouga Date 2021-01-20 Time 21:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-09-22 Cont ID  
Sent By lcrespo Date 2020-09-22 Time 14:23 Rev Time 0.00
Received By lcrespo Date 2020-08-26 Time 07:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2020-01-31 Time   Rev Time 0.00
Received By lmarchan Date 2020-01-07 Time 10:54 Sent To  
Notes
2020-01-08 10:55:04B01

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2021-01-22 Cont ID  
Sent By medwards Date 2021-01-22 Time 07:26 Rev Time 0.00
Received By medwards Date 2021-01-21 Time 14:11 Sent To  
Notes
2021-01-22 07:36:373RD REVIEW FBC-2020 MECHANICAL
 PERMIT-20010166
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2020
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 PREVIOUS COMMENTS STILL HAVE NOT BEEN ADDRESSED.
  
 1) PLEASE PROVIDE A MENU TO VERIFY HOW THIS RESIDENTIAL
 COOKING APPLIANCE IS TO BE USED. THIS WILL DETERMINE
 WHICH TYPE OF COMMERCIAL HOOD WILL BE NEED FOR THIS
 PROJECT. FBC M 507.1.2 ALLOWS DOMESTIC COOKING
 APPLIANCES USED FOR COMMERCIAL PURPOSES. THIS SECTION
 IS VERY CLEAR AS IT STATES ?SHALL BE PROVIDED WITH TYPE
 I OR TYPE II HOODS AS REQUIRED FOR THE TYPE OF
 APPLIANCES AND PROCESSES IN ACCORDANCE WITH SECTIONS
 507.2 AND 507.3. THERE ARE SEVERAL CODE SECTIONS THAT
 WOULD COME INTO PLAY ONCE THE HOOD TYPE HAS BEEN
 ESTABLISHED INCLUDING CLEARANCE TO COMBUSTIBLES (
 507.2.6 ).
  
 2) THE ROOM THAT WILL BE THE KITCHEN WAS PREVIOUSLY A
 LAB. THIS WOULD MAKE THE AREA A CHANGE OF USE. PLEASE
 PROVIDE OUTDOOR AIR CALCULATIONS FOR THIS CHANGE OF USE
 AND THE NEW BREAKROOM AREA. FBC M TABLE 403.3.1.1
  
 3) PLEASE PROVIDE DETAILS OF THE MAKE UP AIR SYSTEM FOR
 THIS NEW HOOD. FBC M 508
  
 4) PLEASE PROVIDE INFORMATION FOR THE DISHWASHER ON
 SHEET E-2. FBC M 507.3
  
 5) PLEASE PROVIDE AN AIR BALANCE PLAN FOR THIS EXHAUST
 SYSTEM. FBC M 508.1.2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2020-09-22 Cont ID  
Sent By medwards Date 2020-09-22 Time 08:13 Rev Time 0.00
Received By medwards Date 2020-09-22 Time 08:07 Sent To  
Notes
2020-09-22 08:13:181ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20010166
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE ADDRESS FIRST REVIEWERS COMMENTS ABOUT THE
 KITCHEN COOKING EQUIPMENT. THE COOKING EQUIPMENT MUST
 HAVE A COMMERCIAL HOOD ABOVE IT. PLEASE PROVIDE A MENU
 OF WHAT IS TO BE COOKED ON THIS KITCHEN RANGE. FBC M
 507
  
 2) IT APPEARS THAT THE NEW DESIGN IS REMOVING A
 CLASSROOM AND CREATING A CORRIDOR AND 2 NEW STORAGE
 AREAS. PLEASE PROVIDE A MECHANICAL SHEET ADDRESSING
 VENTILATION OF THE NEW CORRIDOR AND THE NEW STORAGE
 ROOMS. THIS DRAWING SHOULD ALSO ADDRESS THE NEW KITCHEN
 COOKING EQUIPMENT. FBC M 403
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-01-31 Cont ID  
Sent By ccole Date 2020-01-31 Time 10:05 Rev Time 0.00
Received By ccole Date 2020-01-31 Time 10:05 Sent To  
Notes
2020-01-31 10:16:231ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20010166
 1/31/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THIS IS A COMMERCIAL KITCHEN THEREFORE COOKING
 APPLIANCES THAT ARE LISTED AND LABELED FOR DOMESTIC OR
 HOUSEHOLD USE ARE NOT PERMITTED- SECTIONS 917.1 & 917.2
 FBC M. PLEASE PROVIDE THE MAKE AND MODEL OF THE RANGE
 AND SUBMIT A PRODUCT DATA SHEET FOR REVIEW.
  
 2) THE MICOWAVE/RANGE HOOD MUST BE LISTED FOR
 COMMERCIAL USE- SECTIONS 917.1, 917.2 FBC M. A TYPE I
 OR TYPE II KITCHEN EXHAUST HOOD SHALL BE INSTALLED OVER
 THE COOKING APPLIANCE- SECTION 507.1 FBC M.
 FACTORY-BUILT RECIRCULATION HOOD SYSTEMS SHALL BE
 LISTED AND LABELED IN ACCORDANCE WITH UL 710B- SECTION
 507.1(2). PLEASE PROVIDE CORRECTED PLANS AND
 SPECIFICATIONS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK ?VOID? OR "OLD" ON THEM. PLEASE
 RETAIN THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS.
 THIS PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2021-02-04 Cont ID  
Sent By lcrespo Date 2021-02-04 Time 08:50 Rev Time 0.00
Received By lcrespo Date 2021-02-04 Time 08:18 Sent To  
Notes
2021-02-04 08:49:4802/04/21 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 THIS IS A SECOND REQUEST FOR THE INFORMATION BELOW.
  
 1. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 2. PLEASE PROVIDE A DESCRIPTIVE SCOPE OF WORK BEING
 DONE PER THE 2017 FBC WPB AMENDMENTS SEC. 107.3.5
 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
  
 3. PLUMBING RISER DIAGRAM FOR THE SANITARY PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.5.1.3 (13) COMMERCIAL
 PLUMBING.
  
 4. HOT WATER AND COLD NOT SHOW AND ITS SOURCE, SIZING,
 DISTRIBUTION, SHUTOFF VALVES, WATER HAMMER, WITHIN
 ACCORDANCE 2017 FBC P SEC. 604, PLEASE PROVIDE A LAYOUT
 AND RISER WPB AMENDMENTS TO THE FBC 107.5.1.3 (13)
 PLUMBING RISER DIAGRAM REQUIRED.
  
 5. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS, AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3 PER THE 2017 FBC
 SEC. 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING
 FACILITIES.
  
 6. SIGNED AND SEALED DRAWINGS NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR -
 IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROPBOX) THE
 ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN
 REVIEW REQUEST FORM" EXPLAINING THE REASON FOR
 SUBMITTING THE DOCUMENT OR DRAWINGS. THE PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY EMAILING [email protected] AND
 ASKING FOR THE FORM.
  
 7. PLEASE SUBMIT A SLAB REPAIR DETAIL AND SHOW THE
 WIDTH OF THE REPAIR, THE MINIMUM THICKNESS OF THE
 CONCRETE TO BE REPLACED, AND THE PSI OF THE CONCRETE.
 SHOW THE DOWELS' SIZE AND LENGTH, THE MINIMUM EMBEDMENT
 DEPTH INTO THE EXISTING SLAB, AND THE SPACING OF THE
 DOWELS IN THE CENTER. THE REPAIR SHALL ALSO INCLUDE
 TERMITE TREATMENT OF THE SOIL AND THE REQUIRED VAPOR
 BARRIER OVER THE SOIL. A COPY OF THE TERMITE
 CERTIFICATE SHALL BE ONSITE FOR A FINAL INSPECTION.
  
 8. ALL PLUMBING MUST COMPLY WITH THE FLORIDA BUILDING
 CODE 2017 6TH EDITION.
  
 9. PLEASE GIVE THE LEVEL OF ALTERATION PER 2017 FLORIDA
 EXISTING BUILDING CODE 301.1.
  
 10. ON SHEET E-1 AND E2, IT SHOWS A SINK BEHIND THE
 HANDICAP BATHROOM, AND ON A-1 AND A-2, NONE IS SHOWING.
 PLEASE CLARIFY PER THE 2017 FBC WPB AMENDMENTS SEC.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
  
 11. SHEET E-2 HAS A DISHWASHER. PLEASE SHOW THE
 LOCATION AND DISCHARGE PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 12. PLEASE SHOW THE SOURCE OF HOT WATER FOR THE HC
 RESTROOM AND KITCHEN AREA PER THE 2017 FBC WPB
 AMENDMENTS SEC. 107.3.5 MINIMUM PLAN REVIEW CRITERIA
 FOR BUILDINGS.
  
 13. TOILET PAPER DISPENSER MISSING DIMENSION, THE
 TOILET PAPER DISPENSERS SHALL BE 7" INCHES MINIMUM AND
 9" INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED
 TO THE CENTERLINE OS DISPENSER PER THE 2017 FBC ACC
 SEC. 604.7.
  
 14. ON SHEET A-2, ADA DETAIL OF HEIGHTS AND DIMENSIONS
 OF KITCHEN SINKS NOT SHOWN. PLEASE PROVIDE DETAILED
 DRAWINGS PER THE 2017 FBC ACCESSIBILITY. PLEASE GIVE
 MEASUREMENTS FOR FIXTURE CLEARANCES FOR SINKS PER THE
 FLORIDA BUILDING CODE AND FLORIDA ACCESSIBILITY CODE.
 PLEASE SHOW CLEAR FLOOR SPACE FOR A FORWARD OR SIDE
 APPROACH, AND IT SHALL COMPLY PER THE 2017 ACC SEC.
 602.2.
  
 15. ON SHEET A-2, PLEASE PROVIDE GRAB BARS PER THE 2017
 FBC ACC. 604.5.
  
 16. PROVIDE CABINET DETAIL SHOWING THE SINK HEIGHT OF
 34" INCHES MAXIMUM PER THE 2017 FBC ACC SEC. 606.3.
  
 17. THE CLEAR FLOOR SPACE SHALL BE 60" INCHES MINIMUM
 MEASURED PERPENDICULAR FROM THE SIDEWALL, AND 56"
 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL PER 2017 FBC ACC. SEC. 604.3.1, THE SINK SHALL NOT
 BE IN THAT CLEAR FLOOR SPACE PER THE 2017 FBC ACC SEC.
 604.3.2.
  
 18. LAVATORY WATER SUPPLY AND DRAINPIPES UNDER THE SIDE
 SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT
 AGAINST CONTACT PER THE 2017 FBC ACC SEC. 606.5.
  
 19. ON PLANS, THERE ARE TWO REFRIGERATOR SHOWS. IF THEY
 HAVE AN ICE MAKER, THEY SHALL BE EQUIPPED WITH AN
 IN-LINE VACUUM BREAKER THAT COMPLIES WITH ASSE 1024 PER
 THE 2017 FBC SEC. 608.13.10.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-09-22 Cont ID  
Sent By lcrespo Date 2020-09-22 Time 14:19 Rev Time 0.00
Received By lcrespo Date 2020-09-22 Time 13:55 Sent To  
Notes
2020-09-22 14:20:2909/22/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A SUB PLUMBING PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
  
 2. PLEASE PROVIDE A DESCRIPTIVE SCOPE OF WORK BEING
 DONE PER THE 2017 FBC WPB AMENDMENTS SEC. 107.3.5
 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
  
 3. PLUMBING RISER DIAGRAM FOR THE SANITARY PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.5.1.3 (13) COMMERCIAL
 PLUMBING.
  
 4. HOT WATER AND COLD NOT SHOW AND ITS SOURCE, SIZING,
 DISTRIBUTION, SHUTOFF VALVES, WATER HAMMER, WITHIN
 ACCORDANCE 2017 FBC P SEC. 604, PLEASE PROVIDE A LAYOUT
 AND RISER WPB AMENDMENTS TO THE FBC 107.5.1.3 (13)
 PLUMBING RISER DIAGRAM REQUIRED.
  
 5. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS, AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3 PER THE 2017 FBC
 SEC. 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING
 FACILITIES.
  
 6. SIGNED AND SEALED DRAWINGS NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW - OR -
 IF YOUR ENGINEER DOES NOT HAVE AN ELECTRONIC OR DIGITAL
 SIGNATURE - PLEASE DROP OFF (CITY HALL DROPBOX) THE
 ORIGINAL SIGNED AND SEALED DOCUMENT ALONG WITH A "PLAN
 REVIEW REQUEST FORM" EXPLAINING THE REASON FOR
 SUBMITTING THE DOCUMENT OR DRAWINGS. THE PLAN REVIEW
 REQUEST FORM CAN BE OBTAINED BY EMAILING [email protected] AND
 ASKING FOR THE FORM.
  
 7. PLEASE SUBMIT A SLAB REPAIR DETAIL AND SHOW THE
 WIDTH OF THE REPAIR, THE MINIMUM THICKNESS OF THE
 CONCRETE TO BE REPLACED, AND THE PSI OF THE CONCRETE.
 SHOW THE DOWELS' SIZE AND LENGTH, THE MINIMUM EMBEDMENT
 DEPTH INTO THE EXISTING SLAB, AND THE SPACING OF THE
 DOWELS IN THE CENTER. THE REPAIR SHALL ALSO INCLUDE
 TERMITE TREATMENT OF THE SOIL AND THE REQUIRED VAPOR
 BARRIER OVER THE SOIL. A COPY OF THE TERMITE
 CERTIFICATE SHALL BE ONSITE FOR A FINAL INSPECTION.
  
 8. ALL PLUMBING MUST COMPLY WITH THE FLORIDA BUILDING
 CODE 2017 6TH EDITION.
  
 9. PLEASE GIVE THE LEVEL OF ALTERATION PER 2017 FLORIDA
 EXISTING BUILDING CODE 301.1.
  
 10. ON SHEET E-1 AND E2, IT SHOWS A SINK BEHIND THE
 HANDICAP BATHROOM, AND ON A-1 AND A-2, NONE IS SHOWING.
 PLEASE CLARIFY PER THE 2017 FBC WPB AMENDMENTS SEC.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
  
 11. SHEET E-2 HAS A DISHWASHER. PLEASE SHOW THE
 LOCATION AND DISCHARGE PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 12. PLEASE SHOW THE SOURCE OF HOT WATER FOR THE HC
 RESTROOM AND KITCHEN AREA PER THE 2017 FBC WPB
 AMENDMENTS SEC. 107.3.5 MINIMUM PLAN REVIEW CRITERIA
 FOR BUILDINGS.
  
 13. TOILET PAPER DISPENSER MISSING DIMENSION, THE
 TOILET PAPER DISPENSERS SHALL BE 7" INCHES MINIMUM AND
 9" INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED
 TO THE CENTERLINE OS DISPENSER PER THE 2017 FBC ACC
 SEC. 604.7.
  
 14. ON SHEET A-2, ADA DETAIL OF HEIGHTS AND DIMENSIONS
 OF KITCHEN SINKS NOT SHOWN. PLEASE PROVIDE DETAILED
 DRAWINGS PER THE 2017 FBC ACCESSIBILITY. PLEASE GIVE
 MEASUREMENTS FOR FIXTURE CLEARANCES FOR SINKS PER THE
 FLORIDA BUILDING CODE AND FLORIDA ACCESSIBILITY CODE.
 PLEASE SHOW CLEAR FLOOR SPACE FOR A FORWARD OR SIDE
 APPROACH, AND IT SHALL COMPLY PER THE 2017 ACC SEC.
 602.2.
  
 15. ON SHEET A-2, PLEASE PROVIDE GRAB BARS PER THE 2017
 FBC ACC. 604.5.
  
 16. PROVIDE CABINET DETAIL SHOWING THE SINK HEIGHT OF
 34" INCHES MAXIMUM PER THE 2017 FBC ACC SEC. 606.3.
  
 17. THE CLEAR FLOOR SPACE SHALL BE 60" INCHES MINIMUM
 MEASURED PERPENDICULAR FROM THE SIDEWALL, AND 56"
 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE REAR
 WALL PER 2017 FBC ACC. SEC. 604.3.1, THE SINK SHALL NOT
 BE IN THAT CLEAR FLOOR SPACE PER THE 2017 FBC ACC SEC.
 604.3.2.
  
 18. LAVATORY WATER SUPPLY AND DRAINPIPES UNDER THE SIDE
 SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT
 AGAINST CONTACT PER THE 2017 FBC ACC SEC. 606.5.
  
 19. ON PLANS, THERE ARE TWO REFRIGERATOR SHOWS. IF THEY
 HAVE AN ICE MAKER, THEY SHALL BE EQUIPPED WITH AN
 IN-LINE VACUUM BREAKER THAT COMPLIES WITH ASSE 1024 PER
 THE 2017 FBC SEC. 608.13.10.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-01-14 Cont ID  
Sent By tklarge Date 2020-01-14 Time 08:36 Rev Time 0.00
Received By tklarge Date 2020-01-14 Time 08:27 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-01-22 Cont ID  
Sent By medwards Date 2021-01-22 Time 07:48 Rev Time 0.00
Received By medwards Date 2021-01-22 Time 07:48 Sent To  
Notes
2021-01-22 07:49:54SHEET A-2 DOES NOT HAVE THE DESIGNERS DIGITAL
 SIGNATURE.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-09-22 Cont ID  
Sent By medwards Date 2020-09-22 Time 08:14 Rev Time 0.00
Received By medwards Date 2020-09-22 Time 08:13 Sent To  
Notes
2020-09-22 08:14:32PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. ALTERNATIVELY, A SIGNED/SEALED PAPER SET
 MAY BE SUPPLIED TO THE BUILDING DEPARTMENT WHEN ALL
 TRADES ARE APPROVED. WPB FBC 107.1; FS 471/481
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved