Plan Review Details - Permit 20010152
Plan Review Stops For Permit 20010152
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2020-03-20 Cont ID  
Sent By jgomez Date 2020-03-20 Time 18:14 Rev Time 0.00
Received By jgomez Date 2020-03-19 Time 18:14 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-01-30 Cont ID  
Sent By jgomez Date 2020-01-30 Time 08:26 Rev Time 0.00
Received By jgomez Date 2020-01-30 Time 07:54 Sent To  
Notes
2020-01-30 08:27:31PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE ADDRESS, PERMIT NUMBER AND ASBESTOS IN THE SUBJECT
 LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-03-20 Cont ID  
Sent By jgomez Date 2020-03-20 Time 17:20 Rev Time 0.00
Received By jgomez Date 2020-03-19 Time 18:11 Sent To  
Notes
2020-03-20 17:20:36PROVISO:
 1-SEPARATE FIRE SPRINKLERS AND FIRE ALARM PERMITS
 REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-01-29 Cont ID  
Sent By jgomez Date 2020-01-29 Time 18:58 Rev Time 0.00
Received By jgomez Date 2020-01-29 Time 16:43 Sent To  
Notes
2020-01-29 18:58:56RESIDENTIAL (R2) ALTERATION BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE.
  
 1- THIS IS TYPE I CONSTRUCTION FIRE SPRINKLERED
 BUILDING. THE SCOPE OF WORK INCLUDES THE REMOVAL OF
 WALLS AND CEILINGS. NEW DROPPED CEILINGS ARE PROPOSED.
 PLANS DON'T PROVIDE ANY INFORMATION HOW THE PROPOSED
 WORK WILL AFFECT THE EXISTING FIRE SPRINKLER SYSTEM.
 PROVIDE SCHEMATIC LAYOUT SHOWING HOW THE FIRE SPRINKLER
 SYSTEM WILL BE AFFECTED. SEC. 801.3 FBC-EXISTING
 BUILDING. SEC. 107.3.5.1.1 CITY AMENDMENTS.
 NOTE: SEPARATE PERMITS ARE REQUIRED FOR FIRE SPRINKLERS
 AND FIRE ALARMS.
  
 2- PLANS SUBMITTED SEEM TO HAVE A COPY OF THE
 ARCHITECT'S SIGNATURE. ALL PLANS NEED TO BE PERSONALLY
 SIGNED BY THE ARCHITECT OF RECORD (NO COPIES) AS
 REQUIRED BY 61G1-16.003 FLORIDA ADMINISTRATIVE CODE
 WHEN SUBMITTING PLANS FOR PUBLIC RECORDS.
 ARCHITECT TO PROVIDE SIGNATURE AND DATE ON ALL
 DRAWINGS.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY.(NOTE: SUBMIT OLD DRAWINGS FOR REFERENCE) A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-03-26 Cont ID  
Sent By jpearson Date 2020-03-26 Time 14:02 Rev Time 0.00
Received By jpearson Date 2020-03-26 Time 14:02 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-01-29 Cont ID  
Sent By jpearson Date 2020-01-29 Time 15:24 Rev Time 0.00
Received By jpearson Date 2020-01-29 Time 15:24 Sent To  
Notes
2020-01-29 15:18:33CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12; FBC EX 607.1.1
 OR 801.1, 801.2, OR 901.2 AS APPLICABLE.
 2. RECEPTACLES INSTALLED TO SERVE THE COUNTER TOP IN
 KITCHEN REQUIRE GFCI PROTECTION. PROVIDE CORRECTION.
 NEC 210.8
 3. ALL RECEPTACLE OUTLETS INSTALLED IN LAUNDRY AREAS
 SHALL HAVE GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8(A)(9)
 4. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE
 SUITABLE FOR DAMP LOCATIONS. PROVIDE CORRECTION OR NOTE
 FOR COMPLIANCE. NEC 410.10(D)
 5. LIGHTING IN CLOSETS APPEARS TO BE STANDARD RECESS
 LIGHTS. PER CODE, LIGHTING WITH OPEN OR PARTIALLY
 ENCLOSED LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS
 SHALL NOT BE PERMITTED IN CLOTHES CLOSETS. PROVIDE
 CORRECTION OR NOTE FOR COMPLIANCE. NEC 410.16
 6. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12
 7. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D)
 8. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. LOAD CALCULATION PROVIDED DOES NOT
 USE 208 AS THE VOLTAGE FOR AMPERAGE DEMAND. NEC 215.2,
 220, 408.30
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-03-06 Cont ID  
Sent By pleduc Date 2020-03-06 Time   Rev Time 0.00
Received By pleduc Date 2020-03-06 Time 14:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-01-15 Cont ID  
Sent By pleduc Date 2020-01-15 Time   Rev Time 0.00
Received By pleduc Date 2020-01-15 Time 14:36 Sent To  
Notes
2020-01-15 14:42:02THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEETS A 001 & 002 - THERE IS NO INDICATIONS OF
 COMPLAINCE WITH THE FLORIDA FIRE PREVENTION CODE.
  
 THE PROPOSED SHALL COMPLY WITH THE APPLICABLE CODES OF
 THE 6THE EDITION OF THE FLORIDA FIRE PREVENTION CODE
 WHICH INCLUDER THE 2015 EDITIONA OF NFPA 1 & 101.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE A
 APPLICABLE NOTE OF ACKNOWLEDGEMENT.
  
  
  
 2) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR
 FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED
 CONTRACTORS FOR CODE COVERAGE COMPLIANCE.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE PERMITS
 AND SHOP DRAWINGS.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE A
 APPLICABLE NOTE OF ACKNOWLEDGEMENT.
  
  
  
 3) THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR
 FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE A
 APPLICABLE NOTE OF ACKNOWLEDGEMENT.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2020-03-26 Time   Rev Time 0.00
Received By lmarchan Date 2020-03-03 Time 13:55 Sent To  
Notes
2020-03-04 13:55:27B26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-01-30 Cont ID  
Sent By jgomez Date 2020-01-30 Time 08:27 Rev Time 0.00
Received By jgomez Date 2020-01-07 Time 13:02 Sent To I
Notes
2020-01-08 13:02:56B02

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2020-01-29 Cont ID  
Sent By jgomez Date 2020-01-29 Time 18:59 Rev Time 0.00
Received By jgomez Date 2020-01-29 Time 18:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-04-02 Cont ID  
Sent By ccole Date 2020-03-23 Time 13:30 Rev Time 0.00
Received By ccole Date 2020-03-23 Time 11:56 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-01-16 Cont ID  
Sent By ccole Date 2020-01-16 Time 08:31 Rev Time 0.00
Received By ccole Date 2020-01-16 Time 07:38 Sent To  
Notes
2020-01-16 08:32:191ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20010152
 1/16/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) NO MECHANICAL PLANS HAVE BEEN SUBMITTED. PLEASE
 CLARIFY IF ANY ALTERATIONS TO THE EXISTING HVAC SYSTEMS
 ARE PROPOSED SUCH AS KITCHEN AND BATH EXHAUST SYSTEMS,
 AC SYSTEM REPLACEMENTS, OR DUCT ALTERATIONS- SECTION
 107.2.1 WPB. PLEASE NOTE THAT MECHANICAL EXHAUST IS
 REQUIRED FOR THE BATHS AT AN INTERMITTENT RATE OF 50
 CFMS, AND FOR THE KITCHENS AT AN INTERMITTENT RATE OF
 100 CFMS- TABLE 403.3.1.1 FBC M.
  
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL NEW
 COOKING APPLIANCES AND KITCHEN HOODS- SECTIONS 505 AND
 917.2 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-03-19 Cont ID  
Sent By jbaker Date 2020-03-19 Time 13:58 Rev Time 0.00
Received By jbaker Date 2020-03-19 Time 13:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-01-14 Cont ID  
Sent By tklarge Date 2020-01-14 Time 14:14 Rev Time 0.00
Received By tklarge Date 2020-01-14 Time 09:04 Sent To  
Notes
2020-01-14 09:50:241) THE VALVES TO THE STACKED WASHER AND DRYER SHALL BE
 ACCESSIBLE. 2017 FBC- PLUMBING SEC. 606.
 2) SHT. A3.01 - DETAIL # 7 - THE SHOWER FLOOR SHALL BE
 PITCHED A MINIMUM OF 1/4 INCH PER FOOT TO THE DRAIN.
 2017 FBC-PLUMBING SEC.
  
 REVIEW NOT COMPLETE.
  
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***