Plan Review Details - Permit 20010107
Plan Review Stops For Permit 20010107
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2020-03-02 Cont ID  
Sent By shill Date 2020-03-02 Time 08:01 Rev Time 0.00
Received By shill Date 2020-03-02 Time 08:01 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2020-02-11 Cont ID  
Sent By jwitmer Date 2020-02-11 Time 09:34 Rev Time 0.00
Received By jwitmer Date 2020-02-10 Time 15:38 Sent To  
Notes
2020-02-11 09:34:44PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
 19120504
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN PDF
 FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE
 THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-04-07 Cont ID  
Sent By pvalenti Date 2020-04-07 Time 09:36 Rev Time 0.00
Received By pvalenti Date 2020-04-07 Time 09:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-04-05 Cont ID  
Sent By jwitmer Date 2020-04-05 Time 12:08 Rev Time 0.00
Received By jwitmer Date 2020-04-04 Time 20:57 Sent To  
Notes
2020-04-05 12:08:392017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20010107
 ADD: 315 ALMERIA RD. / 73 DWELLING UNITS
 CONT: TBD/ TO BE DETERMINED
 TEL: ???????
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: SUN.4/052020
 ACTION: BUILDING PROVISOS
  
 1) SHEET A-003. PARKING STALLS ARE TO SHOW COMPLIANCE
 WITH THE W.P.B. MUNI CODE FOR STANDARD AND ACCESSIBLE
 STALLS FOR STRIPING, STANDARD 94-485/ CD94:276.
  
 2) PROVIDE SAFE GUARDS DURING CONSTRUCTION IN
 ACCORDANCE WITH THE 2017 FBC-B SECTION 33.
  
 3) AT THE TIME OF INSPECTIONS, PROVIDE THE ENGINEERS
 APPROVAL LETTER (SIGNED & SEALED) WITH SPECIFIC
 CONNECTION DETAILS FOR ALL ROOF TOP UNITS.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-03-11 Cont ID  
Sent By pvalenti Date 2020-03-11 Time 16:54 Rev Time 0.00
Received By pvalenti Date 2020-03-11 Time 07:14 Sent To  
Notes
2020-03-11 17:01:20***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 2ND BUILDING REVIEW APPROVED WITH THE FOLLOWING
 PROVISOS:
  
  
 1E) PROVIDE SAFEGUARDS DURING CONSTRUCTION AS PER
 SECTION 33 OF THE FLORIDA BUILDING CODE.
  
 7B) AT TIME OF INSPECTION, PROVIDE ENGINEER APPROVED
 (SIGNED/SEALED)SPECIFIC CONNECTION DETAILS FOR ALL ROOF
 TOP UNITS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-02-11 Cont ID  
Sent By jwitmer Date 2020-02-11 Time 09:33 Rev Time 0.00
Received By jwitmer Date 2020-02-10 Time 15:38 Sent To  
Notes
2020-02-11 09:33:512017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20010107
 ADD: 315 ALMERIA RD. / 73 DWELLING UNITS
 CONT: TBD/ TO BE DETERMINED
 TEL: ???????
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. FEB. 11/2020
 ACTION: DENIED
  
 1) THE COVERSHEET LIST UNDER THE HEADING APPLICABLE
 CODES INCLUDING THE EXISTING BUILDING CODE AND
 ACCESSIBILITY CODE.
  
 1A) WHAT THE DESIGNER OF RECORD DOES NOT PROVIDE IS THE
 OCCUPANCY GROUP, MINIMUM BUILDING TYPE, BUILDING
 HEIGHT, AREA PER STORY AND IS THE BUILDING FIRE
 SPRINKLERED. THESE ARE UNKNOWNS AND CRITICAL TO BE ABLE
 TO COMPLETE A BUILDING PLAN REVIEW FOR A COMMERCIAL
 BUILDING.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATIVE CODE
 107.3.5.1 COMMERCIAL BUILDINGS:
 OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED
 MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE
 TABLES 504.3, 504.4 & 506.2).
 IS THE BUILDING FIRE SPRINKLERED OR NOT, IS IT REQUIRED
 UNDER TODAY?S CODE?
  
 1B) THE DESIGNER OF RECORD HAS NOT SHOWN HOW COMPLIANCE
 WITH THE EXISTING BUILDING CODE SECTION 301.1 WILL BE
 ACHIEVED. ALL EXISTING BUILDINGS SHALL COMPLY WITH ONE
 OF THE METHODS LISTED IN SECTIONS 301.1.1 THROUGH
 301.1.3.
  
 1C) THE DESIGNER OF RECORD LIST ON THE COVERSHEET
 ACCESSIBLE DATA, 73 UNITS X .05= 4 ACCESSIBLE UNITS AND
 73 UNITS X .02= 2 HEAR/VISION UNITS. FROM THE
 INFORMATION PROVIDED FROM THE DESIGNER OF RECORD A
 THOROUGH REVIEW CANNOT BE DETERMINED. WHEN THE DESIGNER
 OF RECORD SHOWS ACCESSIBILITY REQUIREMENTS TO THE
 APARTMENT AS UPGRADES IN ACCESSIBILITY, THE QUESTION IS
 ASKED IS A PORTION OF THE APARTMENTS TO BE CONSIDERED
 TRANSIENT APARTMENTS WHERE IN THE BUILDING MORE THAN 25
 PER CENT OR MORE OF THE UNITS ARE ADVERTISED OR HELD
 OUT TO THE PUBLIC AS AVAILABLE FOR TRANSIENT USE (STAYS
 LESS THAN 30 DAYS)? FLORIDA STATUTE 509 WOULD KICK IN
 AND TOUGHS UNITS WHICH ARE PUBLIC LODGING, (TRANSIENT
 LODGING) WOULD NEED TO SHOW COMPLIANCE WITH THE 2017
 FLORIDA ACCESSIBILITY CODE AND FLORIDA STATUTE 509.
 LONG TERM STAYS OVER 30 DAYS IS NOT COVERED UNDER
 FLORIDA ACCESSIBILITY AND THIS BUILDING WAS BUILT AND
 OCCUPIED BEFORE FAIR HOUSING WOULD HAVE BEEN A SAFE
 HAVEN. IS THERE FEDERAL ASSISTANCE PROVIDED?
  
 1D) IF THIS BUILDING IS TO BE CONSIDERED TRANSIENT
 LODGING (OVER 25% OF THE UNITS TRANSIENT) PLEASE REVIEW
 IN THE 2017 FLORIDA ACCESSIBILITY CODE SECTION 224 .6.2
 FACILITIES WITH RESIDENTIAL UNITS AND TRANSIENT LODGING
 UNITS. RESIDENTIAL DWELLING UNITS THAT ARE DESIGNED AND
 CONSTRUCTED FOR RESIDENTIAL USE EXCLUSIVELY ARE NOT
 SUBJECT TO THE TRANSIENT LODGING STANDARDS. ONLY 2
 UNITS ARE FOR HEARING/ VISION IMPAIRED WHEREAS THE
 ACCESSIBILITY CODE TABLE 224.4 FOR 73 UNITS REQUIRES 7
 UNITS TO SHOW COMPLIANCE?
  
 1E) PLEASE PROVIDE A LIFE SAFETY PLAN ON HOW WORK WILL
 BE COMPLETED IN THE UNITS, WILL THERE STILL BE
 OCCUPANTS IN THE UNITS UNDER REMODELING, WILL THERE BE
 OCCUPANTS IN THERE UNITS ON THE SAME FLOOR AS OTHER
 UNITS ARE BEING REMODELED? PLEASE SHOW COMPLIANCE WITH
 THE 2017 FBC-B:
 1E)(1) 3302.1 ALTERATIONS AND REPAIRS. REQUIRED EXITS,
 EXISTING STRUCTURAL ELEMENTS, FIRE PROTECTION DEVICES
 AND SANITARY SAFEGUARDS SHALL BE MAINTAINED AT ALL
 TIMES DURING CONSTRUCTION, ALTERATIONS AND OR REPAIRS
 TO ANY BUILDING OR STRUCTURE.
 1E)(2) 3302.2 MANNER OF REMOVAL. WASTE MATERIALS SHALL
 BE REMOVED IN A MANNER THAT PREVENTS INJURY OR DAMAGE
 TO PERSONS, ADJOINING PROPERTIES AND THE PUBLIC-RIGHT
 OF WAYS.
 1E)(3) 3302.3 FIRE SAFETY DURING CONSTRUCTION. FIRE
 SAFETY DURING CONSTRUCTION SHALL COMPLY WITH THE
 APPLICABLE REQUIREMENTS OF THIS CODE AND THE PROVISIONS
 OF THE FLORIDA FIRE PREVENTION CODE.
  
 1F) THE ELEVATION VIEWS ON SHEET A-301 SHOWS THIS AS A
 4 STORY BUILDING BUT THE PLANS ONLY SHOW WORK ON FLOOR
 LEVELS 1-3, IS THERE NO WORK TO OCCUR ON THE 4TH FLOOR?
 IS THE 4TH FLOOR OCCUPIED? 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 1G) 2017 FBC- EXISTING BUILDING. 804.2.2 R-2 OCCUPANCY
 REQUIRES AUTOMATIC FIRE SPRINKLERS WHEN THE SHARED
 CORRIDORS AND EXITS HAVE AN OCCUPANT LOAD GREATER THAN
 30 OCCUPANTS.
  
 1H) 2017 FBC-EXISTING BUILDING CODE 804.4.1.6. A FIRE
 ALARM SYSTEM SHALL BE INSTALLED IN WORK AREAS OF R-2
 APARTMENT BUILDINGS AS REQUIRED BY THE FLORIDA FIRE
 PREVENTION CODE FOR EXISTING GROUP R-2 OCCUPANCIES.
  
 1I) THE PLANS DO NOT INDICATE IF THERE IS FIRE
 SEPARATION BETWEEN THE DWELLING UNITS AS WELL AS A FIRE
 RATED CORRIDOR. PLEASE REVIEW THE REQUIREMENTS OF THE
 2017 FBC-EXISTING BUILDING SECTION 803.6 FIRE
 RESISTANCE RATINGS AND IN THE FBC-B SECTION 420.2
 REQUIRED SEPARATION WALLS.
  
 1J) SHEET A-202 THE PROPOSED 1ST FLOOR PLAN CENTER OF
 BUILDING FRONT EXIT STAIRWAY SHOWS THE EXIT STAIRWAY
 DOOR WITH A IN-SWING DOOR. THE 2017 FBC-EXISTING
 BUILDING CODE SECTION 805.4.2 SHOW A INSWING DOOR,
 PLEASE SHOW COMPLIANCE WITH SECTION 805.4.2 AND OR
 PROVIDE THE OCCUPANT LOAD FOR THE 2ND FLOOR AND 3RD
 FLOOR SEPARATELY, NOT COMBINED.
  
 2) THE PROPOSED NEW ACCESSIBLE PARKING IS SHOWN ON
 SHEET A-002 AND DETAIL FOR STALL STANDARDS ON A-003.
 PLEASE UPDATE THE STALL AND ACCESS AISLES TO THE 2017
 ACCESSIBILITY REQUIREMENTS. AN ACCESSIBLE PARKING SPACE
 AND ACCESS AISLE, PLEASE SEE THE 2017 FBC-ACCESSIBILITY
 CODE 502.3.3 MARKING. ACCESS AISLES SHALL BE MARKED SO
 AS TO DISCOURAGE PARKING IN THEM. THE ACCESS AISLE MUST
 BE STRIPED DIAGONALLY TO DESIGNATE IT AS A NO-PARKING
 ZONE.
 ADVISORY 502.3.3 MARKING. THE METHOD AND COLOR OF
 MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT MAY
 BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS.
 BECAUSE THESE REQUIREMENTS PERMIT THE VAN ACCESS AISLE
 TO BE AS WIDE AS A PARKING SPACE, IT IS IMPORTANT THAT
 THE AISLE BE CLEARLY MARKED. FLORIDA LAW, S.553.5041
 (5)(C)1., REQUIRES DIAGONAL STRIPING OF ACCESS AISLES.
 THE CITY OF W. P. B. MUNI CODE ARTICLE XV 94-485
 PARKING PROVIDES A DOUBLE LINED DIMENSIONED PARKING
 STALL DETAIL.
  
 3) SHEETS A-202 THE 1ST FLOOR LEVEL, SHEET A-203 THE
 2ND FLOOR LEVEL AND A-204 THE 3RD FLOOR LEVEL ALL SHOW
 THE PROPOSED WORK ON EACH OF THE FLOORS. WHAT ALL OF
 THESE FLOORS SHOW IS NEW A/C SPLIT SYSTEMS BEING
 INSTALLED IN EACH OF THESE UNITS. PLEASE PROVIDE HOW
 COMPLIANCE WILL BE ACHIEVED WITH THE 2017 ENERGY CODE
 SECTIONS:
 R101.5.1.2 COMMERCIAL AND RESIDENTIAL> 3 STORIES. SEE
 FBC- ENERGY CONSERVATION COMMERCIAL PROVISIONS.
 C401.2 APPLICATION. COMMERCIAL BUILDINGS SHALL COMPLY
 WITH ONE OF THE FOLLOWING:
 1) REQUIREMENTS OF ANSI/ ASHRAE/ IESNA 90.1 EXCLUDING
 9.4.1.1(G) OF THE STANDARD.
 2) THE REQUIREMENTS OF SECTIONS C402 THROUGH C405 IN
 ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY WITH
 SECTION C406 AND TENANT SPACES SHALL COMPLY WITH
 SECTION C406.1.1.
 3) THE REQUIREMENTS OF SECTIONS C402.5, C403.2, C404,
 C405.2, C405.3, C405.5, C405.6 AND C405.7. THE BUILDING
 ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85% OF THE
 STANDARD REFERENCE DESIGN BUILDING.
  
 4) SHEET A-302 SHOW THE EAST & WEST WALLS WITH NEW
 PROPOSED MECHANICAL CHASES TO HOUSE THE MECHANICAL
 REFRIGERANT LINES. THERE IS NO STRUCTURAL PLANS ON HOW
 THE MECHANICAL CHASE ON THE EXTERIOR SIDES OF THE
 BUILDING ARE TO BE BUILT, SECURED TO THE BUILDING, AND
 THE SEALING OF THE EXTERIOR WALL PENETRATION OF THE
 REFRIGERANT LINES, FIRE RATING FOR THROUGH
 PENETRATIONS. NOR DOES SHEET A-703 DEPICT CORRECTLY THE
 ROOF PENETRATION FOR THE REFRIGERANT LINES. THEY SHOULD
 BE A THROUGH THE WALL PARAPET PENETRATION, OR IF THEY
 PENETRATE THE ROOF AS SHOWN THEN THERE NEEDS MORE CUT
 SECTIONS OF HOW THE REFRIGERANT LINES LEAVE THE NEW
 EXTERIOR CHASE AND RUN THROUGH THE ATTIC SPACE AND THEN
 PENETRATE FROM THE ATTIC SPACE AND THROUGH THE ROOF.
 THERE IS NOT ENOUGH INFORMATION TO THOROUGHLY DO A
 REVIEW ON THIS SUBJECT!!!!!
 CHASES VERSES SHAFTS. FBC-B 707.3.1 SHAFT ENCLOSURES
 SHALL COMPLY WITH 713.4.
 707.7 PENETRATIONS OF FIRE BARRIERS SHALL COMPLY WITH
 SECTION 714.
 FIRE BLOCKING SHALL COMPLY WITH 2017 FBC-B SECTION
 718.2.
 718.2.2 CONCEALED WALL SPACES.
  
 5) SHEET A-703 THE SPLIT SYSTEM SHOWS THE USER OF WOOD
 SLEEPERS TO MOUNT THE NEW A/C CONDENSING UNITS WITH
 LESS THAN 6 INCHES FROM THE ROOF FINISH TO THE
 UNDERSIDE OF THE NEW CONDENSING INSTALLATION. PLEASE
 NOTE IN THE 2017 FBC-B THE EXCEPTION TO USING SLEEPERS
 ON THE ROOF DECK IS IN EXISTING CONDITIONS, NOT NEW
 INSTALLATIONS. THE 2017 FBC-B REQUIRES MECHANICAL UNITS
 TO BE RAISED UP OFF THE ROOF TOP FOR THE APPLICATION OF
 RE-ROOFING, THERE IS ENOUGH CLEARANCE UNDER THE UNITS
 THAT THE A/C COMPRESSORS DO NOT NEED TO BE DETACHED AND
 RE-INSTALLED FOR RE-ROOFING. PLEASE REVIEW TABLE
 1510.10 FOR THE REQUIRED MINIMUM CLEARANCE BENEATH THE
 A/C STAND. THIS IS THE LOWEST HORIZONTAL FRAMING MEMBER
 OF THE STAND.
  
 6) SINCE THE A/C STANDS ARE TO BE INSTALLED ON THE 3RD
 FLOOR ROOF PLEAS PROVIDE THE WIND DESIGN CRITERIA.
  
 2017 FBC-B 1603.1.4 WIND DESIGN DATA. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
 6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 7A) 2017 FBC-B 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE
 CODE 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(G) PRE-ENGINEERED A/C STANDS.
  
 7B) THE ROOF TOP A/C STAND PRODUCT APPROVALS WILL NEED
 TO BE REVIEWED BY THE DESIGNER OF RECORD. PLEASE
 IDENTIFY THE FOLLOWING REQUIREMENTS CALCULATING THE
 AREA (SIDE VIEW) OF THE ROOF TOP COMPRESSORS,
 CONFIGURATION ON STAND, THE MEAN ROOF HEIGHT OF THE
 STAND AND COMPRESSORS, WEIGHT, CIRCLED THE DESIGN
 PARAMETERS IN THE TABLES, ANCHORS AND UPLIFT VERSES
 MOMENT FOR THE UNIT TO THE STAND AND THE STAND TO THE
 ROOF. THE PRODUCT APPROVAL IS TO BE REVIEWED BY THE
 DESIGNER OF RECORD, APPROVED BEFORE SUBMISSION TO THE
 BUILDING DEPARTMENT.
  
 7C) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 7D) THE ROOF PLAN A-601 SHOWS THE PROPOSED A/C
 COMPRESSORS ON THE ROOF BUT NO WAY TO SERVICE THE
 UNITS. 2017 FBC-M 306.5. EQUIPMENT AND APPLIANCES ON
 ROOFS OR ELEVATED STRUCTURES. WHERE EQUIPMENT REQUIRING
 ACCESS OR APPLIANCES ARE LOCATED ON AN ELEVATED
 STRUCTURE OR ROOF OF A BUILDING SUCH AS PERSONNEL WILL
 HAVE TO CLIMB HIGHER THAN 16 FEET ABOVE GRADE TO ACCESS
 SUCH EQUIPMENT OR APPLIANCES, AN INTERIOR OR EXTERIOR
 MEANS OF EGRESS SHALL BE PROVIDED.
  
 7E) WHEN VIEWING THE ROOF TOP THROUGH GOGGLE MAPS IT
 APPEARS THE PARAPETS AROUND THE PERIMETER AND
 COURTYARDS MAY NEED GUARDS WHERE THE A/C CONDENSERS ARE
 WITHIN 10 FEET OF THE EDGE OF THE BUILDING.
 SHOW COMPLIANCE WITH FBC-B 1013.7 ROOF GUARDS/ ACCESS.
 GUARDS SHALL BE PROVIDED WHERE THE ROOF HATCH OPENING
 IS LOCATED WITHIN 10 FEET OF A ROOF EDGE OR OPEN SIDE
 OF A WALKING SURFACE AND SUCH EDGE OR OPEN SIDE IS
 LOCATED MORE THAN 30 INCHES ABOVE THE FLOOR, ROOF OR
 GRADE BELOW. THE GUARD SHALL BE CONSTRUCTED SO AS TO
 PREVENT THE PASSAGE OF A SPHERE 21 INCHES (533 MM) IN
 DIAMETER.
  
 7F) ZONING MAY REQUIRE THE NEW A/C CONDENSERS TO BE
 SCREENED FROM VIEW. IF SO SHOW COMPLIANCE WITH THE 2017
 FBC-B SECTIONS:
 1509.6 MECHANICAL EQUIPMENT SCREENS. MECHANICAL
 EQUIPMENT SCREENS SHALL BE CONSTRUCTED OF THE MATERIALS
 SPECIFIED FOR THE EXTERIOR WALLS IN ACCORDANCE WITH THE
 TYPE OF CONSTRUCTION OF THE BUILDING. WHERE THE FIRE
 SEPARATION DISTANCE IS GREATER THAN 5 FEET (1524 MM),
 MECHANICAL EQUIPMENT SCREENS SHALL NOT BE REQUIRED TO
 COMPLY WITH THE FIRE-RESISTANCE RATING REQUIREMENTS.
 1509.6.1 HEIGHT LIMITATIONS. MECHANICAL EQUIPMENT
 SCREENS SHALL NOT EXCEED 18 FEET (5486 MM) IN HEIGHT
 ABOVE THE ROOF DECK, AS MEASURED TO THE HIGHEST POINT
 ON THE MECHANICAL EQUIPMENT SCREEN.
  
 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2020-04-07 Cont ID  
Sent By jpearson Date 2020-04-07 Time 09:15 Rev Time 0.00
Received By jpearson Date 2020-04-07 Time 09:15 Sent To  
Notes
2020-04-07 09:15:47JAKE LEAHY REVIEWED.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2020-04-01 Cont ID  
Sent By jleahy Date 2020-04-01 Time 12:55 Rev Time 0.00
Received By jleahy Date 2020-03-31 Time 17:06 Sent To  
Notes
2020-04-01 12:58:26ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 SORRY I MISSED THIS ON THE LAST REVIEWS, BUT VALUE WAS
 NOT SHOWN ON APPLICATION SO THAT IS WHY I MISSED IT.
  
 1) VALUE OF WORK IS LOW, PLEASE SUBMIT CONTRACT WITH A
 TOTAL VALUE FOR ALL TRADES INVOLVED.
  
 ELECTRICAL PLANS ARE OK AND WILL PASS AFTER CONTRACT IS
 SUBMITTED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-03-11 Cont ID  
Sent By jleahy Date 2020-03-11 Time 08:05 Rev Time 0.00
Received By jleahy Date 2020-03-11 Time 08:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-02-07 Cont ID  
Sent By jleahy Date 2020-02-07 Time 13:05 Rev Time 0.00
Received By jleahy Date 2020-02-07 Time 11:44 Sent To  
Notes
2020-02-07 13:08:18FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 NOT REAL SURE WHAT IS BEING DONE PLEASE EXPLAIN???????
  
 NEW SERVICE?
  
 NEW AC?
  
 NEW ELECTRIC IN UNITS?
  
 HARD TO READ LOAD CALCULATION THAT IS ON PLAN NEED
 CLEARER VERSION.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2020-04-03 Time 11:33 Rev Time 0.00
Received By pleduc Date 2020-04-03 Time 10:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2020-03-12 Cont ID  
Sent By pleduc Date 2020-03-12 Time   Rev Time 0.00
Received By pleduc Date 2020-03-09 Time 16:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2020-01-14 Cont ID  
Sent By pleduc Date 2020-01-14 Time   Rev Time 0.00
Received By pleduc Date 2020-01-14 Time 11:14 Sent To  
Notes
2020-01-14 16:21:27THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET G 001 - THERE IS NO CODE REFERENCE INDICATING
 REVIEW NOR COMPLIANCE WITH THE FLORIDA FIRE PREVENTION
 CODE, 6TH ED.
  
 PLEASE REVIEW AND ENSURE COMPLAINCE AND ADD THE CODE
 REFERENCE.
  
  
  
  
 2) THE IS NO LIFE SAFETY PLAN.
  
 PER NFPA 1
  
 4.1.3.2.2.3 BUILDINGS SHALL BE DESIGNED AND CONSTRUCTED
 TO PROVIDE
 REASONABLE LIFE SAFETY FOR OCCUPANTS AND WORKERS DURING
 CONSTRUCTION AND DEMOLITION.
  
 4.1.3.2.2.4 BUILDINGS SHALL BE DESIGNED AND CONSTRUCTED
 TO PROVIDE
 REASONABLE NOTIFICATION TO OCCUPANTS OF FIRE AND OTHER
 EMERGENCY
 SITUATIONS.
 4.1.3.2.2.5 BUILDINGS SHALL BE DESIGNED AND CONSTRUCTED
 TO PROVIDE
 REASONABLE SIGNAGE AND LIGHTING TO IDENTIFY HAZARDS,
 EXITS, MEANS
 OF EGRESS, AND OTHER BUILDING SAFETY FEATURES.
  
  
 WILL THE BUILDING REMIAN OCCUPIED DURING DEMO AND
 RECONSTRUCTION? HOW WILL THE EXITS AND TRAVEL PATHS BE
 MAINTAINED AT ALL TIMES.?
  
 4.5.6 CONSTRUCTION, REPAIR, AND IMPROVEMENT OPERATIONS.
 4.5.6.1 BUILDINGS OR PORTIONS OF BUILDINGS SHALL BE
 PERMITTED TO BE
 OCCUPIED DURING CONSTRUCTION, REPAIR, ALTERATIONS, OR
 ADDITIONS ONLY
 WHERE REQUIRED MEANS OF EGRESS AND REQUIRED FIRE
 PROTECTION
 FEATURES ARE IN PLACE AND CONTINUOUSLY MAINTAINED FOR
 THE PORTION
 OCCUPIED OR WHERE ALTERNATIVE LIFE SAFETY MEASURES AND
 BUILDING
 PROTECTION MEASURES ACCEPTABLE TO THE AHJ ARE IN PLACE.
  
 PLEASE REVIEW AND PROVIDE DETAILS FOR DEMO AND
 RECONSRTRUCTION.
  
  
  
 3) THERE ARE NO INDICAZTIONS OF WHETHER THIS BUILDING
 HAS A FIRE SPRINKLER OR FIRE ALARM SYSTEM.
  
 PER NFPA 101
  
 31.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 31.3.4.1 GENERAL.
 31.3.4.1.1 APARTMENT BUILDINGS FOUR OR MORE STORIES IN
 HEIGHT OR WITH
 MORE THAN 11 DWELLING UNITS, OTHER THAN THOSE MEETING
 THE REQUIREMENTS
 OF 31.3.4.1.2, SHALL BE PROVIDED WITH A FIRE ALARM
 SYSTEM IN ACCORDANCE
 WITH SECTION 9.6, EXCEPT AS MODIFIED BY 31.3.4.2
 THROUGH 31.3.4.5.
  
 31.3.4.5 SMOKE ALARMS.
 31.3.4.5.1* IN BUILDINGS OTHER THAN THOSE EQUIPPED
 THROUGHOUT WITH AN
 EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM,
 SMOKE ALARMS
 SHALL BE INSTALLED IN ACCORDANCE WITH 9.6.2.10, AS
 MODIFIED BY 31.3.4.5.2,
 OUTSIDE EVERY SLEEPING AREA IN THE IMMEDIATE VICINITY
 OF THE BEDROOMS
 AND ON ALL LEVELS OF THE DWELLING UNIT, INCLUDING
 BASEMENTS.
 31.3.4.5.2 SMOKE ALARMS REQUIRED BY 31.3.4.5.1 SHALL
 NOT BE REQUIRED TO
 BE PROVIDED WITH A SECONDARY (STANDBY) POWER SOURCE.
 31.3.4.5.3 IN BUILDINGS OTHER THAN THOSE EQUIPPED
 THROUGHOUT WITH AN
 EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM OR
 A COMPLETE,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH 31.3.5,
 SMOKE ALARMS SHALL BE INSTALLED IN EVERY SLEEPING AREA
 IN
 ACCORDANCE WITH 9.6.2.10, AS MODIFIED BY 31.3.4.5.4.
 31.3.4.5.4 SMOKE ALARMS REQUIRED BY 31.3.4.5.3 SHALL BE
 PERMITTED TO BE
 BATTERY POWERED.
  
 31.3.5 EXTINGUISHMENT REQUIREMENTS.
 31.3.5.1 RESERVED.
 31.3.5.2* WHERE AN AUTOMATIC SPRINKLER SYSTEM IS
 INSTALLED, EITHER FOR
 TOTAL OR PARTIAL BUILDING COVERAGE, THE SYSTEM SHALL BE
 INSTALLED IN
 ACCORDANCE WITH SECTION 9.7, AS MODIFIED BY 31.3.5.3
 AND 31.3.5.4. IN
 BUILDINGS FOUR OR FEWER STORIES ABOVE GRADE PLANE,
 SYSTEMS IN
 ACCORDANCE WITH NFPA 13R, STANDARD FOR THE INSTALLATION
 OF SPRINKLER
 SYSTEMS IN LOW-RISE RESIDENTIAL OCCUPANCIES, SHALL BE
 PERMITTED.
  
 ANY WORK ON THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS
 SHALL BE DONE UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
 ALL LIFE SAFETY SYSTEMS SHALL BE MAINTAINED THROUGHOUT
 DEMO AND RECONSTRUCTION.
  
 PLEASE PROVIDE DETAILS AND AN APPLICABLE NOTE OF
 ACKNOWLEDGEMENT.
  
  
  
 4) THERE ARE NO INDICATIONS OF ANY FIRE ALARM NOR SMOKE
 DETECTION/ALARMS IN THE AFFECTED UNITS.
  
 PLEASE PROVIDE DETAILS IN COMPLIANCE WITH NFPA 101.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2020-04-03 Cont ID  
Sent By fmittner Date 2020-04-03 Time 10:58 Rev Time 0.00
Received By fmittner Date 2020-04-03 Time 10:58 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2020-03-11 Cont ID  
Sent By fmittner Date 2020-03-11 Time 09:46 Rev Time 0.00
Received By fmittner Date 2020-03-11 Time 09:46 Sent To  
Notes
2020-03-11 09:49:56THANK YOU FOR ELECTRONIC SUBMITTAL OF COA. HOWEVER,
 NEED PHYSICAL COPY SUBMITTAD (CAN MAIL) TO PLANNING
 DIVISION WITH $40 REVIEW FEE. OTHERWISE LOOKS GOOD.
  
 QUESTIONS, CONTACT: FRIEDERIKE MITTNER, CITY HISTORIC
 PRESERVATION PLANNER (561) 822-1457

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2020-01-24 Cont ID  
Sent By fmittner Date 2020-01-24 Time 16:55 Rev Time 0.00
Received By fmittner Date 2020-01-24 Time 16:55 Sent To  
Notes
2020-01-24 16:56:30HISTORIC PROPERTY. EXTERIOR MODIFICATIONS REQUIRE
 SUBMITTAL OF COA, QUESTIONS CONTACT: FRIEDERIKE
 MITTNER, CITY HISTORIC PRESERVATION PLANNER AT (561)
 822-1457 OR [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-04-07 Cont ID  
Sent By pvalenti Date 2020-04-07 Time 09:38 Rev Time 0.00
Received By pvalenti Date 2020-04-06 Time 14:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-04-06 Cont ID  
Sent By lmarchan Date 2020-04-06 Time 08:13 Rev Time 0.00
Received By lmarchan Date 2020-03-30 Time 09:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-03-19 Cont ID  
Sent By shill Date 2020-03-19 Time 15:45 Rev Time 0.00
Received By shill Date 2020-03-02 Time 09:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-02-14 Cont ID  
Sent By shill Date 2020-02-14 Time 16:13 Rev Time 0.00
Received By shill Date 2020-01-06 Time 11:16 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2020-04-05 Cont ID  
Sent By jwitmer Date 2020-04-05 Time 12:09 Rev Time 0.00
Received By jwitmer Date 2020-03-25 Time 14:00 Sent To  
Notes
2020-03-25 14:00:363/25/20 EMAILED IMPACT FEE OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-02-11 Cont ID  
Sent By jwitmer Date 2020-02-11 Time 09:34 Rev Time 0.00
Received By jwitmer Date 2020-02-10 Time 15:38 Sent To  
Notes
2020-02-11 09:35:41PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2020-03-31 Cont ID  
Sent By medwards Date 2020-03-31 Time 08:32 Rev Time 0.00
Received By medwards Date 2020-03-31 Time 07:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-03-17 Cont ID  
Sent By ccole Date 2020-03-17 Time 10:49 Rev Time 0.00
Received By ccole Date 2020-03-13 Time 09:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-02-07 Cont ID  
Sent By ccole Date 2020-02-07 Time 14:09 Rev Time 0.00
Received By ccole Date 2020-02-06 Time 17:08 Sent To  
Notes
2020-02-07 15:13:351ST REVIEW FBC-2017 MECHANICAL
 PERMIT #20010107
 2/7/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE LABEL THE A601, 701, 702, & 703
 (ARCHITECTURAL) PLANS THAT ARE MECHANICAL AS "M" PLANS-
 SECTION 107.2.1 WPB.
  
 2) FULL COMPLIANCE WITH THE FLORIDA ENERGY CODE- 2017
 IS REQUIRED BECAUSE THE PREVIOUSLY UNCONDITIONED
 APARTMENTS ARE NOW BEING CONDIITONED WITH NEW HEAT PUMP
 SYSTEMS- REFER TO SECTIONS C503.2 & C101.5 FBC EC.
  
 3) PROVIDE REFRIGERANT PIPING RISER DRAWINGS, AND SHOW
 CONSTRUCTION DETAILS FOR THE EXTERIOR CHASES- SECTION
 107.2.1 WPB. PLEASE INCLUDE A UL TESTED FIRESTOPPING
 ASSEMBLY DETAIL- SECTION 714.3.1.1 FBC B.
  
 4) SHEET A601: PROVIDE THE HSPF FOR THE HEAT PUMPS IN
 THE EQUIPMENT SCHEDULE- SEE TABLE C403.2.3(2) FBC EC.
  
 5) A703: REFER TO SECTION 1510.10 AND TABLE 1510.10 FBC
 B AND PROVIDE THE CLEARANCE DISTANCE BETWEEN THE ROOF
 SURFACE AND THE UNDERSIDE OF THE CONDENSER.
  
 6) A703: PROVIDE CONDENSATE DISPOSAL RISER DRAWINGS
 THAT SHOW THE TYPES AND SIZES OF CONDENSATE PIPINGS,
 PIPING RUNS AND DISHARGE LOCATIONS- SECTION 307.2.1 FBC
 M. PLEASE REMOVE THE NOTE INDICATING DISCHARGE INTO
 NEARST P-TRAP. CONDENSATE SHALL NOT DISCHARGE INTO THE
 WPB SANITARY SYSTEM- SECTION 90-126.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK "VOID" OR "OLD" ON THEM. PLEASE
 RETAIN THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS.
 THIS PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2020-04-07 Cont ID  
Sent By tklarge Date 2020-04-07 Time 04:56 Rev Time 0.00
Received By tklarge Date 2020-04-07 Time 04:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2020-04-01 Cont ID  
Sent By tklarge Date 2020-04-01 Time 11:58 Rev Time 0.00
Received By tklarge Date 2020-04-01 Time 09:12 Sent To  
Notes
2020-04-01 11:38:211) SHT. A-202 - SEC. 611.2 OF THE FBC-ACCESS.CLEARLY
 STATES A CLEAR FLOOR SPACE POSITIONED FOR A PARALLEL
 APPROACH SHALL BE PROVIDED BUT THE PLANS SHOW A FORWARD
 APPROACH.REVISE THE PLAN.
 2) SUBMIT A RISER DIAGRAM THAT COMPLIES WITH THE
 PLUMBING CODE. WPB AMEND. TO FBC SEC. 107.3.5.1.3.
 3) THE DRAIN AND STACK FOR THE WASHING MACHINE SHALL BE
 3 INCHES IN DIAMETER PER FBC-PLUMBING SEC.406.2.
 4) THE ACCESSIBLE SHOWER/BATHTUB SPECS STILL SHOW
 VERTICAL GRAB BARS IN THE UNIT. CLARIFY.
 5) SHT. A-503 - THE LAVATORY CANNOT ENCROACH INTO THE
 CLEAR FLOOR SPACE FOR THE WATER CLOSET UNLESS THE WATER
 CLOSET CLEAR FLOOR UNLESS THE CLEARANCE FOR THE WATER
 CLOSET IS 66 INCHES MINIMUM MEASURED PERPENDICULAR FROM
 THE REAR WALL. THE PLAN SHOWS THE WATER CLOSET
 CLEARANCE AS 50 INCHES BY 60 INCHES.
 6) SHTS. A-401, A-402, A-403 & A-404 HAS A NOTE STATING
 THE CONDENSATE WILL DISCHARGE A MINIMUM OF ONE FOOT
 FROM THE EXTERIOR WALL AND ALSO A NOTE STATING THE
 CONDENSATE WILL DISCHARGE A MINIMUM OF 2 INCHES FROM
 THE EXTERIOR WALL. REMOVE THE NOTE REFERENCING THE 2
 INCHES.
 7) THE SUBMITTED SPEC SHEET FOR THE TUB /SHOWER GIVES
 NO INFORMATION ON THE TUB SEAT MEASUREMENTS.SUBMIT
 ADDITIONAL SPECS THAT SHOW COMPLIANCE WIRG FBC-ACCESS
 SEC.610.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2020-03-19 Cont ID  
Sent By shill Date 2020-03-19 Time 15:44 Rev Time 0.00
Received By shill Date 2020-03-11 Time 07:34 Sent To  
Notes
2020-03-18 17:44:57PLUMBING 2ND REVIEW**DENIED**20010107** MUST COMMENTS
 ARE 2ND REQUEST. IF A PLAN IS DENIED FOR THE SAME
 COMMENT 3 OR MORE TIMES IT MAY BE SUBJECT TO A 4X PLAN
 REVIEW FEE PER F.S 553.80 (2) B
  
 1) NEW SHEETS ARE NOT DIGITALLY SIGNED AND SEALED PER
 F.S 471,481
 2) SHOW THE WASHER AND DRYER CLEAR FLOOR SPACE. FBC-ACC
 611
 3) SHOW THE TUB CLEAR FLOOR SPACE ON SHT. A-503, A-401,
 A-402, A-403
 4) SHOW THE KITCHEN SINK CLEAR FLOOR SPACE ON SHT. A402
 5) SHOW THE STOVE AND ALL OTHER APPLIANCES CLEAR FLOOR
 SPACE. FBC-ACC 804
 6) SHOW THE LAV CLEAR FLOOR SPACE ON SHT. A 402, A-403.
 7) PROVIDE A SANITARY RISER DRAWING. FOR THE RELOCATION
 OF THE WASHING MACHINE. FBC 107.3.5
 8) PROVIDE A LINT INTERCEPTOR FOR THE WASHING MACHINE.
 FBC-PLB 1003.6
 9) PLEASE REMOVE THE VERTICAL GRAB BAR FROM SHT. A501
 AS PER FBC-ACC 609.4 ALL GRAB BARS SHALL BE IN THE
 HORIZONTAL POSITION.
 10) PROVIDE MOUNTING DETAIL FOR THE TUB SEAT SHOWING IT
 WILL COMPLY WITH FBC-ACC 610.2. I WAS NOT ABLE TO
 LOCATE ANY I.A.P.M.O 0687 APPROVAL FOR ADA SHOWER
 SEAT?S SHOWING COMPLIANCE WITH FLORIDA ACCESSIBILITY.
  
  
 TIM HUNT
 PLUMBING PLAN REVIEW
 CITY OF WEST PALM BEACH (CGA SOLUTIONS)
 561-248-2703
 [email protected]
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-01-30 Cont ID  
Sent By tklarge Date 2020-01-30 Time 14:09 Rev Time 0.00
Received By tklarge Date 2020-01-30 Time 14:09 Sent To  
Notes
2020-01-30 13:55:041) THE WASHERS AND DRYERS SHALL COMPLY WITH FBC-ACCESS.
 SEC.611.1 THRU 611.4. SHOW COMPLIANCE ON THE PLANS.
 2) SHT. A4.01 - CONDENSATE LINES SHALL DISCHARGE A
 MINIMUM OF ONE FOOT FROM THE EXTERIOR WALL PER
 FBC-BUILDING SEC. 1503.7.
 3) SUBMIT MANUFACTURER'S DETAILS ON THE REMOVEABLE TUB
 SEAT. THE SEAT SHALL COMPLY WITH FBC-ACCESS. SEC.610.2.
 4) SHT. A5.01 - NOTE #18 - THE GRAB BARS SHALL BE
 MEASURED FROM THE FINISH FLOOR TO THE TOP OF THE
 GRIPPING SURFACE. FBC-ACCESS. SEC.609.4.
 5) SHT. A5.01 - NOTE #5 - THE HEIGHT OF THE ACCESSIBLE
 WATER CLOSET SHALL BE MEASURED TO THE TOP OF THE SEAT,
 NOT THE RIM OF THE WATER CLOSET. FBC-ACCESS. SEC.604.4.
 6) SHT. A5.01 SHOWS VERTICAL GRAB BARS TO BE INSTALLED.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION
 PER FBC-ACCESS. SEC. 609.4.
 7) SHT.A5.03 - DETAIL #2 SHOWS A PROPOSED ACCESSIBLE
 FLOOR PLAN BUT THE FLOOR PLAN SHOWS THE LAVATORY
 ENCROACHING INTO THE CLEAR FLOOR SPACE FOR THE WATER
 CLOSET.CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-04-07 Cont ID  
Sent By shill Date 2020-04-07 Time 05:52 Rev Time 0.00
Received By shill Date 2020-04-07 Time 05:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-03-31 Cont ID  
Sent By medwards Date 2020-03-31 Time 08:32 Rev Time 0.00
Received By medwards Date 2020-03-31 Time 08:32 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2020-03-11 Cont ID  
Sent By shill Date 2020-03-11 Time 14:02 Rev Time 0.00
Received By shill Date 2020-03-11 Time 14:02 Sent To  
Notes
2020-03-11 14:06:02****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. NONE OF THE PAGES ARE DIGITALLY SIGNED, FS471,
 FS481. PLEASE CONTACT ME BEFORE RESUBMITTING.
  
 2. SINCE THE MEP PAGES ARE NO LONGER DIGITALLY SIGNED,
 THE ENGINEER'S PRINTED NAME IS NO LONGER ON THE PLAN.
 THERE IS NO TITLE BLOCK FOR EITHER THE ARCHITECT OR THE
 ENGINEER. THERE IS AN IMAGE OF A SIGNATURE AND SEAL FOR
 THE ARCHITECT ON EVERY PAGE. IS IT THE INTENT THAT THE
 ARCHITECT IS TAKING RESPONSIBILITY FOR ALL OF THE MEP
 PAGES? IS THE ARCHITECT QUALIFIED/COMPETENT TO DO SO?
 SINCE ENGINEERING WORK IS TO BE INCIDENTAL TO THE
 ARCHITECT'S PRATICE OF ARCHITECTURE, THE BUILDING
 OFFICIAL WOULD NEED TO APPROVE THIS IF THIS IS WHAT IS
 BEING REQUESTED.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-02-12 Cont ID  
Sent By shill Date 2020-02-12 Time 18:13 Rev Time 0.00
Received By shill Date 2020-02-12 Time 18:13 Sent To  
Notes
2020-02-12 18:14:08ADVISED ENGINEER THAT FUTURE SUBMITTALS REQUIRE 3RD
 PARTY DIGITAL SIGNATURE
  

Review Stop Z ZONING
Rev No 3 Status P Date 2020-04-03 Cont ID  
Sent By fmittner Date 2020-04-03 Time 10:59 Rev Time 0.00
Received By fmittner Date 2020-04-03 Time 10:59 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2020-03-11 Cont ID  
Sent By fmittner Date 2020-03-11 Time 09:50 Rev Time 0.00
Received By fmittner Date 2020-03-11 Time 09:50 Sent To  
Notes
2020-03-11 09:53:05PERMIT VALUE EXCEEDS 50% OF IMPROVEMENT VALUE.
  
 PLEASE CONTACT RAY CARANCI, LANDSCAPE PLANNER AT (561)
 822-1462 OR
 TO COORDINATE ADDITIONAL PLANTINGS TO BRING SITE BACK
 INTO LANDSCAPE COMPLIANCE
  
 RAY CARANCI, LANDSCAPE PLANNER
 ISA CERTIFIED ARBORIST
 LIAF CERTIFIED LANDSCAPE INSPECTOR
  
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT
 PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1462
 FAX: 561.822.1460
 TTY: 800.955.8771
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2020-02-13 Cont ID  
Sent By elevezqu Date 2020-02-13 Time 08:23 Rev Time 0.00
Received By fmittner Date 2020-02-13 Time 08:23 Sent To  
Notes
***NONE***