Plan Review Details - Permit 20010097
Plan Review Stops For Permit 20010097
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-02-20 Cont ID  
Sent By lcrespo Date 2020-02-20 Time 07:04 Rev Time 0.00
Received By lcrespo Date 2020-02-18 Time 16:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-01-29 Cont ID  
Sent By lmarchan Date 2020-01-29 Time 16:17 Rev Time 0.00
Received By lmarchan Date 2020-01-27 Time 08:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-02-20 Cont ID  
Sent By lcrespo Date 2020-02-20 Time 07:04 Rev Time 0.00
Received By lcrespo Date 2020-02-20 Time 07:04 Sent To  
Notes
2020-02-20 07:05:1702/20/20 REVIEWED FOR CODE COMPLIANCE
 (PLUMBING/IRRRIGATION)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM
 [email protected]
 561-701-6437
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2020-01-29 Cont ID  
Sent By lcrespo Date 2020-01-29 Time 07:25 Rev Time 0.00
Received By lcrespo Date 2020-01-29 Time 07:22 Sent To  
Notes
2020-01-29 15:36:3901/29/30 1ST PLUMBING/IRRIGATION REVIEW**DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON THE PERMIT APPLICATION FOR PERMITTING IT HAS FOR
 PRIMARY PERMIT: SERVICE C, PLEASE CLOUD ON PLAN THE
 AREA THAT IS BEING REFERENCED ON PLANS AND LABEL PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
 2. IS THE METER NUMBER CORRESPOND TO THE AREA IN THE
 SERVICE LETTER AS WELL BECAUSE YOU HAVE NUMBER AND
 LETTER PLEASE MAKE NOTES OR CLARIFY PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  
2020-01-29 07:25:58 
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM
 [email protected]
 561-701-6437
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2020-01-29 Cont ID  
Sent By lcrespo Date 2020-01-29 Time 14:45 Rev Time 0.00
Received By lcrespo Date 2020-01-29 Time 14:45 Sent To  
Notes
2020-01-29 14:45:57THESE PLANS ARE NOT DONE BY ARCHITECT OR LANDSCAPE
 ENGINEER AS THE ARE DONE BY A VENDOR DO NOR REQUIRE A
 SIGNATURE APPROVAL.