| 2020-01-07 08:47:08 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| | NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| | PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| | NFPA 99 = HEALTH CARE FACILITIES CODE |
| | NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | 1ST REVIEW |
| | |
| | PLUMBING COMMENTS: DENIED |
| | 1. PLAN SHEET A-2: SANITARY RISER; BATHTUB FIXTURE |
| | DRAIN SHALL CONNECT TO THE HORIZONTAL WET VENT UPSTREAM |
| | OF THE SINK CONNECTION TO COMPLY WITH FBC RES P3108.1. |
| | 2. PLAN SHEET A-2: SANITARY RISER; HORIZONTAL DRAIN |
| | SERVICING THE WASHER IS SIZED 2 INCH BY THE DESIGNER |
| | AND HAS BEEN MODIFIED BY HAND TO REFLECT 3 INCH SIZE. |
| | PER WPB FBC 107.2.1, REVISE TO REFLECT 3 INCH SIZE. |
| | NOTE THAT MOST MANUFACTURER?S RECOMMENDATIONS DO |
| | REQUIRE THAT THE DRAIN BE 3 INCH. |
| | 3. PLAN SHEET A-2: SANITARY RISER AND PLAN VIEW; |
| | PROVIDE A CLEANOUT AT OR NEAR THE JUNCTION OF THE |
| | BUILDING DRAIN AND BUILDING SEWER TO COMPLY WITH FBC |
| | RES P3005.2.3. |
| | 4. PLAN SHEET A-2: NOTE 11; SELECTED WATER HEATER |
| | PROVIDES A MAXIMUM OF 3.1 GPM. THIS APPEARS NOT TO |
| | SATISFY THE REQUIREMENTS FOR HOT WATER FOR THE FIXTURES |
| | REQUIRING HOT WATER. PER WPB FBC 107.2.1, PROVIDE |
| | CALCULATIONS FOR THE HOT WATER DEMAND AND INSURE THAT |
| | THE SELECTED WATER HEATER WILL SATISFY THE |
| | REQUIREMENTS. |
| | 5. PER THE WPB UTILITIES DEPTMENT, A RPZ BACKFLOW |
| | PREVENTOR SHALL BE INSTALLED AT THE WATER SERVICE TO |
| | THE PROPERTY COMPLYING WITH WPB CCCM. PER WPB FBC |
| | 107.2.1, PROVIDE NOTE ON PLAN SHEET A-1 AND A-2. |
| | 6. SUBMIT TWO COPIES OF A SLAB REPAIR DETAIL FOR |
| | REVIEW. SHOW THE WIDTH OF THE REPAIR, THE MINIMUM |
| | THICKNESS OF THE CONCRETE TO BE REPLACED AND THE PSI OF |
| | THE CONCRETE. SHOW SIZE AND LENGTH OF DOWELS, THE |
| | MINIMUM DEPTH INTO EXISTING SLAB, ANCHORING MATERIAL |
| | FOR DOWELS AND THE SPACING OF THE DOWELSON CENTER. THE |
| | REPAIR SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL |
| | AND THE REQUIRED VAPOR BARRIER OVER WELL COMPACTED |
| | SOIL. A COPY OF THE TERMITE CERTIFICATION SHALL BE |
| | ONSITE FOR THE FINAL INSPECTION. REFER TO FBC RES |
| | R318.1.1, R402.2, R404.1.3.3.7.1, R501.2, R506.1 AND |
| | R506.2.3. |
| | |
| | |
| | |
| | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| | PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| | BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| | APPROVAL. |
| | GAS COMMENTS: |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |
| | 20010067 747 ARDMORE RD |
| | |