Plan Review Details - Permit 20010028
Plan Review Stops For Permit 20010028
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-09-23 Cont ID  
Sent By rmcphers Date 2020-09-23 Time 08:03 Rev Time 0.00
Received By rmcphers Date 2020-09-23 Time 08:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2020-08-07 Cont ID  
Sent By rmcphers Date 2020-08-07 Time 12:51 Rev Time 0.00
Received By rmcphers Date 2020-08-07 Time 12:51 Sent To  
Notes
2020-08-07 13:00:38SIGNS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 AS NOTED ON PREVIOUS REVIEWS
 1) FOR THE MONUMENT SIGN - PLEASE PROVIDE SIGNED AND
 SEALED MONUMENT SIGN DETAILS SHOWING HOW THE CABINETS
 ARE ATTACHMENT TO THE POLE FROM AN ARCHITECT OR
 ENGINEER SHOWING THE WIND DESIGN CRITERIA TO COMPLY
 WITH FBC 1609
  
 FYI = SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO
 BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-03-05 Cont ID  
Sent By jgomez Date 2020-03-05 Time 17:20 Rev Time 0.00
Received By jgomez Date 2020-03-05 Time 16:53 Sent To  
Notes
2020-03-05 15:51:54SIGN SECOND BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 1- ENGINEERED DRAWINGS ARE INCOMPLETE. FRONT ELEVATION
 W/ CAISSON FOUNDATION DETAIL 1 ON DRAWING #1 STATES
 THAT "SIGN CABINETS, BASE AND CONNECTIONS TO POLE BY
 SIGNS UNLIMITED-NC" SIGN ENGINEER OF RECORD NEEDS TO
 PROVIDE COMPLETE INFORMATION FOR THE CONSTRUCTION AND
 PROPOSED INSTALLATION OF THE SIGN CABINET AND BASE.
 SEC. 107.2.1 CITY AMENDMENTS. SEC. 1609.1 FBC-BUILDING.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. SAME PLANS SUBMITTED.
 NOTE; THIS COMMENT APPLIES TO SIGN SHOWN ON DRAWING #5
 ALSO. ENGINEER NEEDS TO SPECIFY THE FASTENING OF THE
 WALL SIGN NOT SIGNS UNLIMITED.
  
  
 ORIGINAL COMMENT:
 2- PLANS NEED TO SPECIFY THE LOCATION OF EACH OF THE
 SIGNS SHOWN ON THE ENGINEERED DRAWINGS 1 THRU 6.
 SEC. 107.2.1 CITY AMENDMENTS. SEC. 1609.1 FBC-BUILDING.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. SAME PLANS SUBMITTED.
  
 ORIGINAL COMMENT:
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. PROVIDE COPY OF SIGNED CONTRACTS INCLUDING
 DESIGN PROFESSIONAL FEES.
  
 RESPONSE.
 REPEAT COMMENT. NOT ADDRESSED.
  
 4- NOTICE OF COMMENCEMENT WILL BE REQUIRED. SEC. 713.13
 F.S.
  
  
  
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
  
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-01-22 Cont ID  
Sent By jgomez Date 2020-01-22 Time 17:07 Rev Time 0.00
Received By jgomez Date 2020-01-22 Time 16:05 Sent To E
Notes
2020-01-22 17:07:53SIGN BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- ENGINEERED DRAWINGS ARE INCOMPLETE. FRONT ELEVATION
 W/ CAISSON FOUNDATION DETAIL 1 ON DRAWING #1 STATES
 THAT "SIGN CABINETS, BASE AND CONNECTIONS TO POLE BY
 SIGNS UNLIMITED-NC" SIGN ENGINEER OF RECORD NEEDS TO
 PROVIDE COMPLETE INFORMATION FOR THE CONSTRUCTION AND
 PROPOSED INSTALLATION OF THE SIGN CABINET AND BASE.
 SEC. 107.2.1 CITY AMENDMENTS. SEC. 1609.1 FBC-BUILDING.
  
 2- PLANS NEED TO SPECIFY THE LOCATION OF EACH OF THE
 SIGNS SHOWN ON THE ENGINEERED DRAWINGS 1 THRU 6.
 SEC. 107.2.1 CITY AMENDMENTS. SEC. 1609.1 FBC-BUILDING.
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. PROVIDE COPY OF SIGNED CONTRACTS INCLUDING
 DESIGN PROFESSIONAL FEES.
  
 4- NOTICE OF COMMENCEMENT WILL BE REQUIRED. SEC. 713.13
 F.S.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2020-09-23 Cont ID  
Sent By jleahy Date 2020-09-23 Time 10:54 Rev Time 0.00
Received By jleahy Date 2020-09-23 Time 10:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2020-07-08 Cont ID  
Sent By jleahy Date 2020-07-08 Time 11:10 Rev Time 0.00
Received By jleahy Date 2020-07-08 Time 11:09 Sent To  
Notes
2020-07-08 11:12:50CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 AGAIN VALUE IS TOO LOW FOR ALL THESE SIGNS VALUE TO
 INCLUDE ALL LABOR AND MATERIALS INCLUDING THE SIGNS
  
 DISCONNECT REQUIRED PER 600.6(A) FOR ALL ILLUMINATED
 SIGNS

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-03-04 Cont ID  
Sent By jleahy Date 2020-03-04 Time 16:01 Rev Time 0.00
Received By jleahy Date 2020-03-04 Time 16:01 Sent To  
Notes
2020-03-04 16:09:54FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) VALUE LOW FOR WORK. SUBMIT A SIGNED CONTRACT FOR THE
 WORK, WHICH INCLUDES SIGN, LABOR AND ALL EQUIPMENT USED
 TO INSTALL.
  
 2) NO ELECTRIC SHOWN FOR SIGN.
  
 3) FREE STANDING SIGN IS THIS NEW OR EXISTING, DOES IT
 HAVE ELECTRIC? IF SO SHOW DETAILS OF THE ELECTRIC.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-01-30 Cont ID  
Sent By jleahy Date 2020-01-30 Time 16:06 Rev Time 0.00
Received By jleahy Date 2020-01-30 Time 16:06 Sent To  
Notes
2020-01-30 16:07:37NO ELECTRIC SHOWN
  
 VALUE TO LOW.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-09-28 Cont ID  
Sent By lmarchan Date 2020-09-28 Time 09:28 Rev Time 0.00
Received By lmarchan Date 2020-09-18 Time 15:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-08-07 Cont ID  
Sent By rmcphers Date 2020-08-07 Time 13:02 Rev Time 0.00
Received By rmcphers Date 2020-06-22 Time 09:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-03-05 Cont ID  
Sent By jgomez Date 2020-03-05 Time 17:57 Rev Time 0.00
Received By jgomez Date 2020-02-18 Time 13:43 Sent To I
Notes
2020-02-28 07:52:002/28 ROTUED TO JLEAHY
2020-02-19 13:43:18RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-01-30 Cont ID  
Sent By jleahy Date 2020-01-30 Time 16:07 Rev Time 0.00
Received By jleahy Date 2020-01-02 Time 10:30 Sent To  
Notes
2020-01-03 10:30:44ROUTED TO ZONING INBOX

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-09-23 Cont ID  
Sent By rmcphers Date 2020-09-23 Time 08:03 Rev Time 0.00
Received By rmcphers Date 2020-09-23 Time 08:03 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-08-07 Cont ID  
Sent By rmcphers Date 2020-08-07 Time 13:01 Rev Time 0.00
Received By rmcphers Date 2020-08-07 Time 13:01 Sent To  
Notes
2020-08-07 13:02:16ELECTRONICALLY SIGNED AS A PACKAGE IN THE SIGNATURE
 FOLDER
2020-07-16 11:39:11DIGITALLY SIGNED PDF IN SIGNATURE FOLDER (RECEIVED VIA
 EMAIL)

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-06-29 Cont ID  
Sent By shill Date 2020-06-29 Time 09:40 Rev Time 0.00
Received By shill Date 2020-06-29 Time 09:40 Sent To  
Notes
2020-06-29 09:41:26SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FS471, DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. A SCAN OF A SIGNED PLAN IS NOT CONSIDERED AN
 ORIGINAL.
  
 EITHER EMAIL A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO ME, OR YOU CAN MAIL (OR DROP OFF) ONE ORIGINAL
 SIGNED AND SEALED PAPER ORIGINAL WITH A WET SIGNATURE
 TO:
  
 SAMANTHA M. HILL
 CHIEF PLANS EXAMINER
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6724.

Review Stop Z ZONING
Rev No 4 Status P Date 2020-09-28 Cont ID  
Sent By rthermid Date 2020-09-28 Time   Rev Time 0.00
Received By rthermid Date 2020-09-28 Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2020-07-31 Cont ID  
Sent By rthermid Date 2020-07-31 Time   Rev Time 0.00
Received By rthermid Date 2020-07-31 Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-02-27 Cont ID  
Sent By rfalcone Date 2020-02-27 Time 14:47 Rev Time 0.00
Received By rfalcone Date   Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-01-09 Cont ID  
Sent By rfalcone Date 2020-01-09 Time 09:57 Rev Time 0.00
Received By rfalcone Date 2020-01-09 Time 09:57 Sent To B
Notes
2020-01-09 09:57:191/9/20 FAILED.
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION:
 1. SURVEY
 2. PHOTOS OF THE FACADE OF THE BUILDING - SHOWING THE
 SIZE OF EACH SIDE OF THE BUILDING WHERE A PROPOSED SIGN
 WILL BE INSTALLED.
 3. SHOW ON THE PLANS THE LOCATION OF THE SIGNS (I.E.
 NORTH, WEST, EAST, SOUTH FACADE)
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 RACHEL FALCONE, ASSOCIATE PLANNER
 DEVELOPMENT SERVICES DEPARTMENT
 E-MAIL: [email protected]
 TEL: (561) 822-1442
  