Plan Review Details - Permit 19121112
Plan Review Stops For Permit 19121112
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2020-09-28 Cont ID  
Sent By pvalenti Date 2020-09-28 Time 08:18 Rev Time 0.00
Received By pvalenti Date 2020-09-28 Time 06:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2020-08-08 Cont ID  
Sent By pvalenti Date 2020-08-08 Time 09:27 Rev Time 0.00
Received By pvalenti Date 2020-08-08 Time 09:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2020-08-03 Cont ID  
Sent By pvalenti Date 2020-08-03 Time 09:25 Rev Time 0.00
Received By pvalenti Date 2020-08-03 Time 09:21 Sent To  
Notes
2020-08-03 09:27:01PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561?805?6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 2ND BUILDING REVIEW DENIED:
  
 FBC B 107, PLEASE PROVIDE ENGINEER?S SIGNED AND SEALED
 FOUNDATION DETAILS AND WIND LOAD CALCULATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-06-10 Cont ID  
Sent By pvalenti Date 2020-06-10 Time 10:47 Rev Time 0.00
Received By pvalenti Date 2020-06-10 Time 10:47 Sent To  
Notes
2020-06-10 10:49:02PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 FBC B 107, PLEASE PROVIDE ENGINEER'S SIGNED AND SEALED
 FOUNDATION DETAILS AND WIND LOAD CALCULATIONS.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2020-09-11 Cont ID  
Sent By jleahy Date 2020-09-11 Time 16:35 Rev Time 0.00
Received By jleahy Date 2020-09-11 Time 16:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2020-08-21 Cont ID  
Sent By jleahy Date 2020-08-21 Time 16:15 Rev Time 0.00
Received By jleahy Date 2020-08-21 Time 16:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2020-07-13 Cont ID  
Sent By jleahy Date 2020-07-13 Time 15:26 Rev Time 0.00
Received By jleahy Date 2020-07-13 Time 15:07 Sent To  
Notes
2020-07-13 15:30:38FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 ALL COMMENTS HAVE BEEN ADDRESSED EXCEPT THE FAULT
 CURRENT CALCULATION.
  
 PANEL DETAIL SHOWS PANEL IS RATED AT 10K, NO
 CALCULATION HAS BEEN PROVIDED SO I AM TO ASSUME THAT
 THIS PANEOL WILL NEED TO BE RATED AT 22K.
  
 PLEASE SUBMIT THE AIC CALCULATION PER 110.9, 110.10,
 ALSO PLACE NOTE FOR DECAL ON SERVICE PER 110.24

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-01-03 Cont ID  
Sent By jleahy Date 2020-01-03 Time 10:52 Rev Time 0.00
Received By jleahy Date 2020-01-03 Time 10:52 Sent To  
Notes
2020-01-03 10:53:01FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) VLAUE FOR THE WORK SHOWN IS TOO LOW, PLEASE SUBMIT A
 SIGNED CONTRACT WITH THE OWNER.
  
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2) SHOWS TWO (2) CIRCUITS MAINS CANNOT BE SMALLER THEN
 30A. 230.79(B) (B) TWO-CIRCUIT INSTALLATIONS. FOR
 INSTALLATIONS CONSISTING OF NOT MORE THAN TWO 2-WIRE
 BRANCH CIRCUITS, THE SERVICE DISCONNECTING MEANS SHALL
 HAVE A RATING OF NOT LESS THAN 30 AMPERES.
  
 3) NEED THE AVAILABLE FAULT CURRENT RATING FOR THE
 SERVICE. 110.10 , 110.24 AVAILABLE FAULT CURRENT ( A)
 FIELD MARKING. SERVICE EQUIPMENT IN OTHER THAN DWELLING
 UNITS SHALL BE LEGIBLY MARKED IN THE FIELD WITH THE
 MAXIMUM AVAILABLE FAULT CURRENT. THE FIELD MARKING(S)
 SHALL INCLUDE THE DATE THE FAULT-CURRENT CALCULATION
 WAS PERFORMED AND BE OF SUFFICIENT DURABILITY TO
 WITHSTAND THE ENVIRONMENT INVOLVED.
  
 4) PANEL BOARD NEEDS TO BE LISTED 110.3, 230.66 MARKING
 SERVICE EQUIPMENT RATED AT 1000 VOLTS OR LESS SHALL BE
 MARKED TO IDENTIFY IT AS BEING SUITABLE FOR USE AS
 SERVICE EQUIPMENT. ALL SERVICE EQUIPMENT SHALL BE L
 ISTED. INDIVIDUAL METER SOCKET ENCLOSURES SHALL NOT BE
 CONSIDERED SERVICE EQUIPMENT.
  
 5) CUT SHEETS FOR SURGE ARRESTOR 110.3
  
 6) 250.94 BONDING FOR OTHER SYSTEMS AN INTERSYSTEM
 BONDING TERMINATION FOR CONNECTING INTERSYSTEM BONDING
 CONDUCTORS REQUIRED FOR OTHER SYSTEMS SHALL BE PROVIDED
 EXTERNAL TO ENCLOSURES AT THE SERVICE EQUIPMENT OR
 METERING EQUIPMENT ENCLOSURE AND AT THE DISCONNECTING
 MEANS FOR ANY ADDITIONAL BUILDINGS OR STRUCTURES.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2020-09-28 Cont ID  
Sent By pvalenti Date 2020-09-28 Time 08:23 Rev Time 0.00
Received By pvalenti Date 2020-09-01 Time 09:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2020-08-21 Cont ID  
Sent By jleahy Date 2020-08-21 Time 16:16 Rev Time 0.00
Received By jleahy Date 2020-08-06 Time 15:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-08-03 Cont ID  
Sent By pvalenti Date 2020-08-03 Time 09:27 Rev Time 0.00
Received By pvalenti Date 2020-06-23 Time 10:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-01-03 Cont ID  
Sent By jleahy Date 2020-01-03 Time 10:53 Rev Time 0.00
Received By jleahy Date 2019-12-31 Time 16:18 Sent To  
Notes
2020-01-02 16:18:09ELEC <5K

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2020-09-28 Cont ID  
Sent By pvalenti Date 2020-09-28 Time 08:19 Rev Time 0.00
Received By pvalenti Date 2020-09-28 Time 06:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2020-08-08 Cont ID  
Sent By pvalenti Date 2020-08-08 Time 09:27 Rev Time 0.00
Received By pvalenti Date 2020-08-08 Time 09:27 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-08-03 Cont ID  
Sent By pvalenti Date 2020-08-03 Time 09:24 Rev Time 0.00
Received By pvalenti Date 2020-08-03 Time 09:21 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2020-06-10 Cont ID  
Sent By pvalenti Date 2020-06-10 Time 10:46 Rev Time 0.00
Received By pvalenti Date 2020-06-10 Time 10:46 Sent To  
Notes
2020-06-10 10:47:17PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561?805?6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 SIGNATURE REVIEW DENIED:
  
 FBC B 107.2.1, FS 471, FS 481; PLEASE PROVIDE:
 1) VERIFIED DIGITAL SIGNATURES IN PROJECT DOX,
 2) VERIFIED DIGITALLY SIGNED DOCUMENTS EMAILED IN PDF?S
 OR
 3) PAPER PLANS WITH ORIGINAL SIGNATURES AND SEALS.

Review Stop Z ZONING
Rev No 3 Status P Date 2020-09-22 Cont ID  
Sent By eschneid Date 2020-09-22 Time 10:46 Rev Time 0.25
Received By eschneid Date 2020-09-22 Time 10:36 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2020-08-20 Cont ID  
Sent By eschneid Date 2020-08-20 Time 14:38 Rev Time 0.25
Received By eschneid Date 2020-08-20 Time 11:56 Sent To  
Notes
2020-08-20 14:46:42FAILED
  
 1) UPDATE PLANS TO REFLECT THE STEALTH POLE - EX RISER
 DETAIL SHOWS EXTERIOR MOUNTED EQUIPMENT FOR THE OLD
 POLE.
  
 2) POLE DESIGN PASSES.
  
 3) REVIEWING THE SURVEY AND SITE PLAN DRAWINGS
 (ESPECIALLY FROM THE RIGHT-OF-WAY PERMIT) YOU NEED TO
 BE VERY CAREFUL OF THE INSTALLATION LOCATION WITH THE
 NEW POLE DESIGN. IT IS 12 INCHES IN DIAMETER AND IT
 APPEARS THAT THERE MAY BE AT MOST18 INCHES BETWEEN THE
 SIDEWALK AND THE PROPERTY LINE. YOUR INSTALL TEAM HAS
 ALREADY ACCIDENTALLY INSTALLED ONE POLE AND MOST LIKELY
 ANOTHER ONE ON PRIVATE PROPERTY. YOU SHOULD HAVE THE
 SURVEYOR STAKE THE EDGE OF THE RIGHT-OF-WAY LINE PRIOR
 TO INSTALLATION TO AVOID AN INCORRECT PLACEMENT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2020-07-24 Cont ID  
Sent By awooten Date 2020-07-24 Time 13:59 Rev Time 0.00
Received By eschneid Date 2020-07-24 Time 13:59 Sent To  
Notes
2020-07-24 14:04:42FAILED
  
 1) PROVIDE A PROVIDE A SURVEY, PREPARED BY A FLORIDA
 LICENSED SURVEYOR, WHICH SHOWS THE POLE LOCATION AND
 THE RIGHT-OF-WAY LINE SO THAT STAFF CAN VERIFY THAT THE
 WIRELESS COMMUNICATION FACILITY IS WITHIN THE
 RIGHT-OF-WAY AND NOT ON PRIVATE PROPERTY.
  
 2) PROVIDE A COPY OF THE PALM BEACH COUNTY RIGHT-OF-WAY
 APPROVAL IF THE SURVEY SHOWS THE PROPOSED WIRELESS
 COMMUNICATION FACILITY IN THE RIGHT-OF-WAY. NOTE: THE
 ROW PERMIT APPROVAL NUMBER IS LISTED ON THE ENGINEERING
 SITE PLAN.
  
 3) PROVIDE VERIFICATION THAT THE PROPOSED WIRELESS
 FACILITY (POLE) MEETS THE CITY OF WEST PALM BEACH
 CONCEALMENT (STEALTH), STYLE OR HEIGHT REQUIREMENTS
 LISTED IN SECTIONS 78-411(E), 78-411(F) AND 78-411(G)
 OF THE CITY CODE. PROVIDE A POLE THAT MEETS THE CITY
 CODE REQUIREMENTS. NOTE: AT&T HAS SHOWN POLES ON OTHER
 APPLICATIONS THAT MEET THE CITY CODE REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  