Plan Review Details - Permit 19121089
Plan Review Stops For Permit 19121089
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-01-08 Cont ID  
Sent By rmcdouga Date 2020-01-08 Time 08:43 Rev Time 0.00
Received By rmcdouga Date 2020-01-08 Time 08:06 Sent To  
Notes
2020-01-08 08:43:12PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT AN ADDITIONAL SET OF CUT SHEETS/SPECS. FOR
 THE EQUIPMENT. FBC107.1 GENERAL. SUBMITTAL DOCUMENTS
 CONSISTING OF CONSTRUCTION DOCUMENTS, STATEMENT OF
 SPECIAL INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA
 SHALL BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION.
  
 2) SUBMIT TWO SETS OF FLORIDA OR MIAMI-DADE PRODUCT
 APPROVALS, OR SIGNED AND SEALED ENGINEERING FOR THE
 PREFABRICATED GENERATOR PAD THAT WILL BE USED. FBC
 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS FOR
 THOSE PRODUCTS WHICH ARE REGULATED BY FAC 61G20-3.001
 PER FLORIDA STATUTE 553.842.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2020-01-07 Cont ID  
Sent By jleahy Date 2020-01-07 Time 14:32 Rev Time 0.00
Received By jleahy Date 2020-01-07 Time 14:32 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2020-01-08 Cont ID  
Sent By lcrespo Date 2020-01-08 Time 18:06 Rev Time 0.00
Received By lcrespo Date 2020-01-08 Time 18:06 Sent To  
Notes
2020-01-08 18:07:3701/08/20 1ST GAS/ REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. GAS RISER DIAGRAM REQUIRED WPB AMENDMENTS TO THE FBC
 SEC. 107.3.5.3 (12) RESIDENTIAL GAS
 2. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF
 THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH
 FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA
 STATUTE 471 AND PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.1 GENERAL.
 3. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON
 PLANS IN FULL, NUMBER, STREET, CITY, STATE AND ZIP CODE
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 4. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017
 FBC-RES. SEC. G 2413.4.1, G2413.4.2.
 5. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS-STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 6. A SUB GAS PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1.
 7. TYPE OF GAS IS IT (LP OR NATURAL) MODEL OF GENERATOR
 YOU ARE USING AND IT'S BTU'S PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 8. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE 2017 FBC RES. SEC. G2421.1.
 9. LABEL SHUTOFF VALVE, DRIP LEG, PRESSURE OF GAS AT
 METER, UNION AND REGULATOR ON GAS ISOMERIC PER THE 2017
 FBC RES. SEC. G2401.1.3.
 10. SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE
 DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR
 ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM PER THE 2017 FBC RES. SEC. G2413.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM
 [email protected]
 561-701-6437
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-01-08 Cont ID  
Sent By lcrespo Date 2020-01-08 Time 18:08 Rev Time 0.00
Received By lcrespo Date 2019-12-30 Time 09:52 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-01-02 Cont ID  
Sent By lcrespo Date 2020-01-08 Time 18:08 Rev Time 0.00
Received By rfalcone Date 2020-01-02 Time 15:02 Sent To B
Notes
2020-01-02 15:03:211/2/19 FAILED.
  
 PLEASE PROVIDE A SURVEY OF THE SUBJECT SITE WITH THE
 LOCATION OF THE PROPOSED GENERATOR WITH ITS SETBACK
 REQUIREMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 RACHEL FALCONE, ASSOCIATE PLANNER
 DEVELOPMENT SERVICES DEPARTMENT
 E-MAIL: [email protected]
 TEL: (561) 822-1442
  