Plan Review Details - Permit 19121066
Plan Review Stops For Permit 19121066
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-02-04 Cont ID  
Sent By dbattles Date 2020-02-04 Time 16:39 Rev Time 0.00
Received By dbattles Date 2020-02-04 Time 16:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2020-01-07 Cont ID  
Sent By dbattles Date 2020-01-07 Time 10:30 Rev Time 0.00
Received By dbattles Date 2020-01-07 Time 10:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-02-04 Cont ID  
Sent By jleahy Date 2020-02-04 Time 09:58 Rev Time 0.00
Received By jleahy Date 2020-02-04 Time 09:58 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-01-06 Cont ID  
Sent By jleahy Date 2020-01-06 Time 14:26 Rev Time 0.00
Received By jleahy Date 2020-01-06 Time 14:26 Sent To B
Notes
2020-01-06 14:30:07FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) NO ADDED VALUE FOR THE ADDITIONAL WORK ADDED TO THE
 SYSTEM.
  
 2) PAGE PV-3.1OW IS TAP MADE INTO THE SERVICE? LOOKS
 LIKE A LOAD SIDE TAP AND LOOKS TO BE MORE THAN 20%?
  
 3) PAGE PV-3.1 WHAT SIZE BATTERY IS BEING USED RISER
 SHOWS 5KW BUT CUT SHEETS SHOW 9.8KW ???
  
 4) BACKUP PANEL CUTSHEETS AND PANEL SCHEDULE.
  
 5) OCP FOR BATTERY WHERE IS IT AND WHAT SIZE IS IT,

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-02-04 Cont ID  
Sent By dbattles Date 2020-02-04 Time 16:40 Rev Time 0.00
Received By dbattles Date 2020-01-27 Time 13:33 Sent To  
Notes
2020-01-30 07:06:26ROUTED TO JAKE LEAHY
2020-01-28 13:34:01RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-01-07 Cont ID  
Sent By hmtribou Date 2020-01-03 Time 09:37 Rev Time 0.00
Received By dbattles Date 2019-12-30 Time 09:59 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-01-29 Cont ID  
Sent By hmtribou Date 2020-01-29 Time 16:20 Rev Time 0.00
Received By hmtribou Date 2020-01-29 Time 16:20 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-01-03 Cont ID  
Sent By dbattles Date 2020-01-07 Time 10:30 Rev Time 0.00
Received By hmtribou Date 2020-01-03 Time 09:35 Sent To E
Notes
2020-01-03 09:36:38PROVIDE DIMSIONS OF SOLAR PANELS AND ROOF. THE PANELS
 MAY NOT EXTEND PAST ROOFS SURFACE.
  