Plan Review Details - Permit 19121041
Plan Review Stops For Permit 19121041
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-02-06 Cont ID  
Sent By pvalenti Date 2020-02-06 Time 15:59 Rev Time 0.00
Received By pvalenti Date 2020-02-06 Time 15:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-01-21 Cont ID  
Sent By shill Date 2020-01-21 Time 18:06 Rev Time 0.00
Received By shill Date 2020-01-21 Time 18:06 Sent To  
Notes
2020-01-21 18:06:20****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC 107, EACH PLAN PAGE IS TO BE INDIVIDUALLY
 UPLOADED, DIGITALLY SIGNED. A 3 PAGE PDF WAS UPLOADED
 AS "ENGINEERING DRAWINGS".
  
 2. FBC 107, THE 2ND PAGE OF THE ENGINEERING DRAWINGS IS
 FOR A SIGN "SPRUZZO", PERMIT APPLICATION IS FOR ONE
 SIGN, CLARIFY.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-02-06 Cont ID  
Sent By fgiaquin Date 2020-02-06 Time 17:40 Rev Time 0.00
Received By fgiaquin Date 2020-02-06 Time 17:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-01-12 Cont ID  
Sent By fgiaquin Date 2020-01-12 Time 18:01 Rev Time 0.00
Received By fgiaquin Date 2020-01-09 Time 07:05 Sent To  
Notes
2020-01-12 17:43:24ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND
 SIGNED/SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
  
 2. EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR FEEDER
 CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR OUT-LINE
 LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN EXTERNALLY
 OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL OPEN ALL
 UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN NEC
 600.6(A)(1)
  
 3. ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 405.1
 SHALL HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT
 OR WHEN NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR &
 TIME CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME
 SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMING
 DURING A LOSS OF POWER FOR A MINIMUM OF 10 HOURS.
 FBC-EC 405.2.5
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-02-06 Cont ID  
Sent By fgiaquin Date 2020-02-06 Time 17:41 Rev Time 0.00
Received By fgiaquin Date 2020-02-06 Time 11:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-02-05 Cont ID  
Sent By lmarchan Date 2020-02-05 Time 16:42 Rev Time 0.00
Received By lmarchan Date 2020-01-02 Time 15:31 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2020-02-06 Cont ID  
Sent By pvalenti Date 2020-02-06 Time 15:59 Rev Time 0.00
Received By pvalenti Date 2020-02-06 Time 15:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-01-21 Cont ID  
Sent By shill Date 2020-01-21 Time 18:06 Rev Time 0.00
Received By shill Date 2020-01-21 Time 18:06 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2020-02-06 Cont ID  
Sent By aaponte Date 2020-02-06 Time 14:07 Rev Time 0.00
Received By aaponte Date 2020-02-06 Time 14:07 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2020-02-05 Cont ID  
Sent By aaponte Date 2020-02-05 Time 15:10 Rev Time 0.00
Received By aaponte Date 2020-02-05 Time 15:10 Sent To  
Notes
***NONE***