Plan Review Details - Permit 19121027
Plan Review Stops For Permit 19121027
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2020-11-19 Cont ID  
Sent By pvalenti Date 2020-11-19 Time 09:39 Rev Time 0.00
Received By pvalenti Date 2020-11-19 Time 07:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2020-01-27 Cont ID  
Sent By pvalenti Date 2020-01-27 Time 08:42 Rev Time 0.00
Received By pvalenti Date 2020-01-27 Time 06:44 Sent To  
Notes
2020-01-27 08:44:10***CORRECTIONS***
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 BUILDING REVIEW DENIED:
  
 1) FBC EB 402.1/811.1 & FBC EC R 502.1; PROVIDE ENERGY
 & A/C CALCULATIONS INCLUDING NEW DOORS/WINDOWS/WALLS.
  
 2) FBC B 1072.1/107.2.5; PROVIDE SURVEY EITH
 MEASUREMENTS AND SET- BACKS TO ADDITION.
  
 3) FBC B 109.3; THE VALUATION APPEARS TO BE VERY LOW.
 RE-EVALUATE, THE VALUE MUST BE WITHIN THE RANGE OF THE
 INDUSTRY STANDARD.
  
 4) FBC B 107.2.1; PROVIDE THE WINDOW AND DOOR PRODUCT
 APPROVALS (REVIEW STAMPED/SIGNED BY DESIGNER OF
 RECORD).
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2020-11-19 Cont ID  
Sent By equinone Date 2020-11-17 Time 11:55 Rev Time 0.00
Received By equinone Date 2020-11-17 Time 11:55 Sent To  
Notes
2020-11-17 12:07:08CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FROM PREVIOUS REVIEW:
  
 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR
 THE DESIGN, AND THAT PERSON?S INFORMATION SHOULD BE
 SHOWN IN THE TITLE BLOCK AREA. PROVIDE CORRECTION. FS
 481.229; WPB FBC 107.1, 107.2.1, 107.3.5.1.2
  
 NOT CORRECTED.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2020-01-10 Cont ID  
Sent By jpearson Date 2020-01-10 Time 11:37 Rev Time 0.00
Received By jpearson Date 2020-01-10 Time 07:07 Sent To  
Notes
2020-01-10 11:37:09CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR
 THE DESIGN, AND THAT PERSONS INFORMATION SHOULD BE
 SHOWN IN THE TITLE BLOCK AREA. PROVIDE CORRECTION. FS
 481.229; WPB FBC 107.1, 107.2.1, 107.3.5.1.2
 2. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC
 109.3
 3. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE
 OUTLETS IN BATHROOM. PROVIDE CORRECTION. NEC 210.8; FBC
 RE E3902.1
 4. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. ON FLOOR PLAN, SHOW ALL EXISTING ALARMS. IF
 NONE ARE EXISTING OR NOT TO CODE, SHOW AS NEW
 INSTALLATIONS, OR PROVIDE A NOTE REQUIRING COMPLIANCE.
 FBC RE R314.3, R315.1; WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2020-12-23 Cont ID  
Sent By jleahy Date 2020-12-23 Time 12:16 Rev Time 0.00
Received By jleahy Date 2020-11-06 Time 14:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2020-01-27 Cont ID  
Sent By pvalenti Date 2020-01-27 Time 10:03 Rev Time 0.00
Received By pvalenti Date 2019-12-27 Time 13:22 Sent To  
Notes
2019-12-27 13:22:38R42

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-04-05 Cont ID  
Sent By lmarchan Date 2021-04-05 Time 09:05 Rev Time 0.00
Received By lmarchan Date 2021-01-21 Time 11:40 Sent To  
Notes
2021-04-05 09:06:01NO FEES DUE. LEM
2021-01-21 11:40:471/21/21 EMAILED IMPACT FEE OFFICE. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2020-01-27 Cont ID  
Sent By pvalenti Date 2020-01-27 Time 07:22 Rev Time 0.00
Received By pvalenti Date 2020-01-27 Time 07:22 Sent To  
Notes
2020-01-27 07:23:27IMPACT FEES - PAPER SUBMITTALS
  
 IMPACT REVIEW DENIED:
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2020-11-07 Cont ID  
Sent By medwards Date 2020-11-07 Time 09:21 Rev Time 0.00
Received By medwards Date 2020-11-07 Time 08:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2020-01-27 Cont ID  
Sent By ccole Date 2020-01-23 Time 12:19 Rev Time 0.00
Received By ccole Date 2020-01-23 Time 12:19 Sent To  
Notes
2020-01-27 08:40:011ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19121027
 1/23/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW ADDITION- SECTION R403.7 FBC EC.
  
 2) PROVIDE AN ENERGY COMPLIANCE REPORT- SECTION R101.5
 & R401.2 FBC EC
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2020-11-16 Cont ID  
Sent By lcrespo Date 2020-11-16 Time 09:13 Rev Time 0.00
Received By lcrespo Date 2020-11-16 Time 09:12 Sent To  
Notes
2020-11-16 09:13:2511/16/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2020-01-02 Cont ID  
Sent By lcrespo Date 2020-01-02 Time 10:35 Rev Time 0.00
Received By lcrespo Date 2020-01-02 Time 10:23 Sent To  
Notes
2020-01-02 10:36:0901/02/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM
 [email protected]
 561-701-6437
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2020-01-27 Cont ID  
Sent By pvalenti Date 2020-01-27 Time 07:43 Rev Time 0.00
Received By pvalenti Date 2020-01-27 Time 07:27 Sent To  
Notes
2020-01-27 07:54:20PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
 FBC M = FBC MECHANICAL
  
 ROOFING REVIEW APPROVED WITH PROVISO:
  
 FBC B 107.3.4.1, DEFERRED SUBMITTALS; PLEASE PROVIDE
 PRODUCT APPROVALS (REVIEW STAMPED AND SIGNED BY
 DESIGNER OF RECORD) FOR ROOFING MATERIALS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2020-11-06 Cont ID  
Sent By equinone Date 2020-11-06 Time 14:56 Rev Time 0.00
Received By equinone Date 2020-11-06 Time 14:56 Sent To  
Notes
2020-11-06 15:02:05CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED.
  
 SURVEY PAPER DRAWINGS HAVE ORIGINAL SEAL AND SIGNATURE.
  
 SHEET 7.1 ELECTRICAL PLANS AND SCHEDULES ARE STILL
 MISSING SIGNATURE AND INFORMATION FROM PERSON
 RESPONSIBLE FOR THE DESIGN. SEE BELOW
  
 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF
 PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR
 THE DESIGN, AND THAT PERSON'S INFORMATION SHOULD BE
 SHOWN IN THE TITLE BLOCK AREA. PROVIDE CORRECTION. FS
 481.229; WPB FBC 107.1, 107.2.1, 107.3.5.1.2
  
 SINCERELY,
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2020-11-19 Cont ID  
Sent By rthermid Date 2020-11-19 Time   Rev Time 0.00
Received By rthermid Date 2020-11-19 Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2020-01-09 Cont ID  
Sent By rfalcone Date 2020-01-09 Time 11:11 Rev Time 0.00
Received By rfalcone Date 2020-01-09 Time 11:11 Sent To I
Notes
2020-01-09 11:12:021/9/20 FAILED.
  
 PLEASE PROVIDE A SITE PLAN/SURVEY WITH THE PROPOSED
 ADDITION AND ITS SETBACKS FROM THE PROPERTY LINES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 RACHEL FALCONE, ASSOCIATE PLANNER
 DEVELOPMENT SERVICES DEPARTMENT
 E-MAIL: [email protected]
 TEL: (561) 822-1442
  