| Plan Review Stops For Permit 19121027 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2020-11-19 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-11-19 |
Time |
09:39 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-11-19 |
Time |
07:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2020-01-27 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-01-27 |
Time |
08:42 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-01-27 |
Time |
06:44 |
Sent To |
|
|
| Notes |
| 2020-01-27 08:44:10 | ***CORRECTIONS*** | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | BUILDING REVIEW DENIED: | | | | | | 1) FBC EB 402.1/811.1 & FBC EC R 502.1; PROVIDE ENERGY | | | & A/C CALCULATIONS INCLUDING NEW DOORS/WINDOWS/WALLS. | | | | | | 2) FBC B 1072.1/107.2.5; PROVIDE SURVEY EITH | | | MEASUREMENTS AND SET- BACKS TO ADDITION. | | | | | | 3) FBC B 109.3; THE VALUATION APPEARS TO BE VERY LOW. | | | RE-EVALUATE, THE VALUE MUST BE WITHIN THE RANGE OF THE | | | INDUSTRY STANDARD. | | | | | | 4) FBC B 107.2.1; PROVIDE THE WINDOW AND DOOR PRODUCT | | | APPROVALS (REVIEW STAMPED/SIGNED BY DESIGNER OF | | | RECORD). | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2020-11-19 |
|
|
Cont ID |
|
| Sent By |
equinone |
Date |
2020-11-17 |
Time |
11:55 |
Rev Time |
0.00 |
| Received By |
equinone |
Date |
2020-11-17 |
Time |
11:55 |
Sent To |
|
|
| Notes |
| 2020-11-17 12:07:08 | CODES IN EFFECT | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | REVIEW STATUS: FAILED | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FROM PREVIOUS REVIEW: | | | | | | 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF | | | PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR | | | THE DESIGN, AND THAT PERSON?S INFORMATION SHOULD BE | | | SHOWN IN THE TITLE BLOCK AREA. PROVIDE CORRECTION. FS | | | 481.229; WPB FBC 107.1, 107.2.1, 107.3.5.1.2 | | | | | | NOT CORRECTED. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | SINCERELY, | | | | | | ENRIQUE QUINONEZ | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2020-01-10 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2020-01-10 |
Time |
11:37 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2020-01-10 |
Time |
07:07 |
Sent To |
|
|
| Notes |
| 2020-01-10 11:37:09 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF | | | PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR | | | THE DESIGN, AND THAT PERSONS INFORMATION SHOULD BE | | | SHOWN IN THE TITLE BLOCK AREA. PROVIDE CORRECTION. FS | | | 481.229; WPB FBC 107.1, 107.2.1, 107.3.5.1.2 | | | 2. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS | | | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND | | | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS | | | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC | | | 109.3 | | | 3. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE | | | OUTLETS IN BATHROOM. PROVIDE CORRECTION. NEC 210.8; FBC | | | RE E3902.1 | | | 4. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED | | | PER CODE. ON FLOOR PLAN, SHOW ALL EXISTING ALARMS. IF | | | NONE ARE EXISTING OR NOT TO CODE, SHOW AS NEW | | | INSTALLATIONS, OR PROVIDE A NOTE REQUIRING COMPLIANCE. | | | FBC RE R314.3, R315.1; WPB FBC 107.2.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH | | | ITEM ALONG WITH THE CITY RESUBMITTAL FORM. | | | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL | | | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. | | | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD | | | REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2020-12-23 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2020-12-23 |
Time |
12:16 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2020-11-06 |
Time |
14:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2020-01-27 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-01-27 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2019-12-27 |
Time |
13:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2021-04-05 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2021-04-05 |
Time |
09:05 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-01-21 |
Time |
11:40 |
Sent To |
|
|
| Notes |
| 2021-04-05 09:06:01 | NO FEES DUE. LEM | | 2021-01-21 11:40:47 | 1/21/21 EMAILED IMPACT FEE OFFICE. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2020-01-27 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-01-27 |
Time |
07:22 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-01-27 |
Time |
07:22 |
Sent To |
|
|
| Notes |
| 2020-01-27 07:23:27 | IMPACT FEES - PAPER SUBMITTALS | | | | | | IMPACT REVIEW DENIED: | | | | | | PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL | | | (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE | | | PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE | | | RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS | | | APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE | | | QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE | | | FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD | | | MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2020-11-07 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2020-11-07 |
Time |
09:21 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2020-11-07 |
Time |
08:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2020-01-27 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2020-01-23 |
Time |
12:19 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2020-01-23 |
Time |
12:19 |
Sent To |
|
|
| Notes |
| 2020-01-27 08:40:01 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #19121027 | | | 1/23/20 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH | | | EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SUBMIT AC COOLING AND HEATING CALCULATIONS FOR THE | | | NEW ADDITION- SECTION R403.7 FBC EC. | | | | | | 2) PROVIDE AN ENERGY COMPLIANCE REPORT- SECTION R101.5 | | | & R401.2 FBC EC | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2020-11-16 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2020-11-16 |
Time |
09:13 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2020-11-16 |
Time |
09:12 |
Sent To |
|
|
| Notes |
| 2020-11-16 09:13:25 | 11/16/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES | | | FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, | | | STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT | | | THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK | | | OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2020-01-02 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2020-01-02 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2020-01-02 |
Time |
10:23 |
Sent To |
|
|
| Notes |
| 2020-01-02 10:36:09 | 01/02/20 REVIEWED FOR CODE COMPLIANCE (PLUMBING) | | | | | | BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE | | | COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN | | | PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM | | | THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND | | | NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF | | | PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY | | | ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM | | | REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES | | | / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO | | | AVOID VOIDING OF THE PERMIT. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 6:30 AM 7:30 / 2:00 PM TO 5:00 PM | | | [email protected] | | | 561-701-6437 | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2020-01-27 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2020-01-27 |
Time |
07:43 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2020-01-27 |
Time |
07:27 |
Sent To |
|
|
| Notes |
| 2020-01-27 07:54:20 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | | | | ROOFING REVIEW APPROVED WITH PROVISO: | | | | | | FBC B 107.3.4.1, DEFERRED SUBMITTALS; PLEASE PROVIDE | | | PRODUCT APPROVALS (REVIEW STAMPED AND SIGNED BY | | | DESIGNER OF RECORD) FOR ROOFING MATERIALS. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2020-11-06 |
|
|
Cont ID |
|
| Sent By |
equinone |
Date |
2020-11-06 |
Time |
14:56 |
Rev Time |
0.00 |
| Received By |
equinone |
Date |
2020-11-06 |
Time |
14:56 |
Sent To |
|
|
| Notes |
| 2020-11-06 15:02:05 | CODES IN EFFECT | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | REVIEW STATUS: FAILED. | | | | | | SURVEY PAPER DRAWINGS HAVE ORIGINAL SEAL AND SIGNATURE. | | | | | | SHEET 7.1 ELECTRICAL PLANS AND SCHEDULES ARE STILL | | | MISSING SIGNATURE AND INFORMATION FROM PERSON | | | RESPONSIBLE FOR THE DESIGN. SEE BELOW | | | | | | 1. PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF | | | PLAN IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR | | | THE DESIGN, AND THAT PERSON'S INFORMATION SHOULD BE | | | SHOWN IN THE TITLE BLOCK AREA. PROVIDE CORRECTION. FS | | | 481.229; WPB FBC 107.1, 107.2.1, 107.3.5.1.2 | | | | | | SINCERELY, | | | | | | ENRIQUE QUINONEZ | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2020-11-19 |
|
|
Cont ID |
|
| Sent By |
rthermid |
Date |
2020-11-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
rthermid |
Date |
2020-11-19 |
Time |
|
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2020-01-09 |
|
|
Cont ID |
|
| Sent By |
rfalcone |
Date |
2020-01-09 |
Time |
11:11 |
Rev Time |
0.00 |
| Received By |
rfalcone |
Date |
2020-01-09 |
Time |
11:11 |
Sent To |
I |
|
| Notes |
| 2020-01-09 11:12:02 | 1/9/20 FAILED. | | | | | | PLEASE PROVIDE A SITE PLAN/SURVEY WITH THE PROPOSED | | | ADDITION AND ITS SETBACKS FROM THE PROPERTY LINES. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME. | | | | | | RACHEL FALCONE, ASSOCIATE PLANNER | | | DEVELOPMENT SERVICES DEPARTMENT | | | E-MAIL: [email protected] | | | TEL: (561) 822-1442 | | | |
|
|